KACO new energy GmbH: KACO blueplanet 150 TL3 M1 WM OD IIQX {660V} outputs 151,228 W AC at 660 V, 3-phase (132.3 A continuous, 175 A OCPD), ranking #24 of 2,343 CEC inverters at 98.78% efficiency with a 960-1,300 V MPPT window and 1,300 V DC limit. All figures reconcile directly against federal energy archives, state electrical licensing boards, California Energy Commission datasheets, and National Electrical Code engineering constants.
- AC Output (Paco)
- 151,228 W
- AC Voltage
- 660 V, 3-phase
- Min PV Breaker
- 175 A (2/0 AWG Cu)
- CEC Efficiency
- 98.78%
How Does KACO new energy GmbH: KACO blueplanet 150 TL3 M1 WM OD IIQX {660V} Compare Against Peer CEC Listings?
How KACO new energy GmbH KACO new energy GmbH: KACO blueplanet 150 TL3 M1 WM OD IIQX {660V} compares on 98.78% efficiency, MPPT span, and 120% busbar interconnection.
KACO new energy GmbH certifies KACO new energy GmbH: KACO blueplanet 150 TL3 M1 WM OD IIQX {660V} (grid-tied PV inverter, active in CEC directory) at 151,228 W AC (2,690,652 W below the 2,841,880 W 660 V median). Its 1,300 V DC ceiling pairs with an MPPT window of 960-1,300 V (span 340.0 V). Under NEC 690.8/705.12, 125% sizing demands 2/0 AWG Cu conductors on a 175 A OCPD.
Where Does KACO new energy GmbH: KACO blueplanet 150 TL3 M1 WM OD IIQX {660V} Fall Across Listed CEC Models?
Position of KACO new energy GmbH: KACO blueplanet 150 TL3 M1 WM OD IIQX {660V} (151,228 W AC) relative to the 7,680 W CEC median inverter.
What Dataset Percentiles Define KACO new energy GmbH: KACO blueplanet 150 TL3 M1 WM OD IIQX {660V}?
Percentile placement of KACO new energy GmbH: KACO blueplanet 150 TL3 M1 WM OD IIQX {660V} across AC power class, conversion efficiency, and backfeed breaker size.
What Do the Dataset Ranks Show for KACO new energy GmbH: KACO blueplanet 150 TL3 M1 WM OD IIQX {660V}?
Primary electrical sizing limits, efficiency ranks, and NEC 705.12 / 690.7 thresholds for KACO new energy GmbH: KACO blueplanet 150 TL3 M1 WM OD IIQX {660V}.
98.78% CEC Weighted Efficiency
+0.57 pts vs the 98.21% 660 V median; overall power rank #269 (151,228 W, top 11.5%; higher than 88.5% of peers).
175 A Required Backfeed OCPD
125% x 132.3 A = 165.4 A -> 175 A standard OCPD using 2/0 AWG Cu (75 C).
960 V - 1,300 V (Max 1,300 V DC)
Tracking span of 340.0 V; active in CEC directory (grid-tied PV inverter).
Supply-Side Tap (705.11) / Dedicated Switchboard
Evaluated for 660 V, 3-phase switchgear (200A Bus / 200A Main (660V) to 1,200A Bus / 1,200A Main (660V)) under NEC 705.12 / 705.11.
NEC 705.12 Backfeed OCPD & 120% Busbar Formula
I_cont = 151228.0W / 660 V 3-phase -> 132.3 A | Breaker >= 1.25 * 132.3 = 165.4 A -> 175 A
CEC Inverters.csv for KACO new energy GmbH: KACO blueplanet 150 TL3 M1 WM OD IIQX {660V}: Paco=151228.0 W, Vac=660 V, Vdcmax=1300.0 V, Eff=98.78%.
Result: Min 175 A breaker & 2/0 AWG Cu (75 C); 1,200A Bus / 1,200A Main (660V): PASS (120% Commercial Busbar).
What Are the Published CEC Specifications for KACO new energy GmbH: KACO blueplanet 150 TL3 M1 WM OD IIQX {660V}?
Official California Energy Commission electrical test parameters, AC voltage, and DC limits for KACO new energy GmbH: KACO blueplanet 150 TL3 M1 WM OD IIQX {660V}.
| Parameter | Measured / Listed Value | Engineering Significance |
|---|---|---|
| Max Continuous AC Power (Paco) | 151,228 W | Determines required backfeed OCPD size via 125% continuous rule |
| Nominal AC Voltage (Vac) | 660 V, 3-phase | 240V split-phase residential vs. 208V/480V/MV commercial |
| Max DC Input Voltage (Vdcmax) | 1,300 V | Hard ceiling for cold-weather PV string Voc under NEC 690.7 |
| MPPT Operating Range | 960 V - 1,300 V | Optimal DC string Vmp window for full power harvest |
| Max Input DC Current (Idcmax) | 146.508 A | Used to verify parallel string combiner limits |
| CEC Weighted Efficiency | 98.78% | Calculated AC/DC conversion ratio from CEC test protocol |
| Inverter Topology | Hybrid: No (Grid-Tied PV) | CEC Solar Equipment List grid-support certification |
What Switchgear Limits Apply to KACO new energy GmbH: KACO blueplanet 150 TL3 M1 WM OD IIQX {660V} (660 V, 3-phase)?
Check whether KACO new energy GmbH: KACO blueplanet 150 TL3 M1 WM OD IIQX {660V} (175 A breaker) fits without main breaker derate or supply-side taps.
| Switchboard / Interconnect | 120% Max Backfeed | Required PV OCPD | Compliance Verdict |
|---|---|---|---|
| 200A Bus / 200A Main (660V) | 40 A | 175 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| 400A Bus / 400A Main (660V) | 80 A | 175 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| 600A Bus / 600A Main (660V) | 120 A | 175 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| 800A Bus / 800A Main (660V) | 160 A | 175 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| 1,200A Bus / 1,200A Main (660V) | 240 A | 175 A | PASS (120% Commercial Busbar) |
Which CEC PV Module Strings Pair With KACO new energy GmbH: KACO blueplanet 150 TL3 M1 WM OD IIQX {660V}?
Verified cold-weather (-10 C) series module counts matched to KACO new energy GmbH: KACO blueplanet 150 TL3 M1 WM OD IIQX {660V}'s 1,300 V DC ceiling.
| CEC Module | STC (W) | -10 C Voc | Valid String Range | Max String DC |
|---|---|---|---|---|
| AXITEC AC-590TGB/144TS | 590.0 W | 56.24 V | 23 panels (fixed) | 13.57 kW |
| Aptos Solar Technology LLC DNA-108-MFN10-440W | 440.0 W | 42.15 V | 29 to 30 panels | 13.2 kW |
| Boviet Solar Technology Co Ltd BVM7610M-425-H-HC-BF | 425.0 W | 44.75 V | 28 to 29 panels | 12.32 kW |
| Chint New Energy Technology Co Ltd CHSM72M(DG)/F-BH-515 | 515.0 W | 53.76 V | 24 panels (fixed) | 12.36 kW |
Which Competing Grid-Support Inverters Compare to KACO new energy GmbH: KACO blueplanet 150 TL3 M1 WM OD IIQX {660V}?
Alternative CEC inverters comparable to KACO new energy GmbH: KACO blueplanet 150 TL3 M1 WM OD IIQX {660V}, including SMA America: SHP 172-US-21 {660V} (172,000 W) at 660 V, 3-phase.
| Alternative Inverter | AC Output | Delta | Vac | Max DC | CEC Eff |
|---|---|---|---|---|---|
| SMA America: SHP 172-US-21 {660V} SMA America |
172,000 W | +20772 W | 660.0 V | 1200.0 V | 98.57% |
| SMA America: SHP FLEX-US-21 {660V} SMA America |
172,810 W | +21582 W | 660.0 V | 1200.0 V | 98.57% |
| EPC Power Corp: 50-200100 {660V} EPC Power Corp |
515,072 W | +363844 W | 660.0 V | 1500.0 V | 98.47% |
| INGETEAM POWER TECHNOLOGY SA: INGECON SUN 1715TL U B660 {660V} INGETEAM POWER TECHNOLOGY SA |
1,390,614 W | +1239386 W | 660.0 V | 1200.0 V | 97.22% |
What Are the Interconnection Limits and Best-Fit Uses for KACO new energy GmbH: KACO blueplanet 150 TL3 M1 WM OD IIQX {660V}?
Check KACO new energy GmbH: KACO blueplanet 150 TL3 M1 WM OD IIQX {660V} (151,228 W AC, 175 A OCPD) against your main panel busbar, winter string Voc, and IEEE 1547 outage rules.
- Anti-islanding shutdown: grid-tied inverters shut off within 2 seconds during blackouts under IEEE 1547 unless paired with a battery microgrid interconnect.
- Busbar 120% limit: Commercial 660 V, 3-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (660V) or NEC 705.11 supply-side tap.
- Cold Voc hard ceiling: never allow winter open-circuit PV string voltage to exceed 1,300 V DC on KACO new energy GmbH: KACO blueplanet 150 TL3 M1 WM OD IIQX {660V}.
KACO new energy GmbH: KACO blueplanet 150 TL3 M1 WM OD IIQX {660V} Panel & Wire Spec
Size 75 C copper conductors at 2/0 AWG Cu on a 175 A OCPD breaker (132.3 A continuous).
Alternative Inverter Comparison
Compare efficiency (98.78%) and MPPT window (960-1,300 V) directly against SMA America: SHP 172-US-21 {660V} (172,000 W).
Which Homeowner Electrical & Solar Questions Come Up Most Often?
Answers for KACO new energy GmbH: KACO blueplanet 150 TL3 M1 WM OD IIQX {660V} by KACO new energy GmbH covering breaker sizing, MPPT limits, and 660 V, 3-phase interconnection.
What breaker and wire size does KACO new energy GmbH: KACO blueplanet 150 TL3 M1 WM OD IIQX {660V} require?
At 151,228 W continuous AC (660 V, 3-phase), continuous current is 132.3 A; 125% NEC 690.8/705.12 sizing requires a 175 A breaker and 2/0 AWG Cu (75 C) wire.
What commercial switchgear or feeder sizing does KACO new energy GmbH: KACO blueplanet 150 TL3 M1 WM OD IIQX {660V} require?
At 151,228 W AC and 660 V, 3-phase, continuous line current is 132.3 A, requiring a 175 A OCPD and 1,200A Bus / 1,200A Main (660V) or NEC 705.11 interconnection.
How does KACO new energy GmbH: KACO blueplanet 150 TL3 M1 WM OD IIQX {660V} compare to SMA America: SHP 172-US-21 {660V}?
KACO new energy GmbH: KACO blueplanet 150 TL3 M1 WM OD IIQX {660V} delivers 151,228 W AC at 98.78% CEC efficiency with a 1,300 V DC ceiling, while SMA America: SHP 172-US-21 {660V} outputs 172,000 W at 660 V, 3-phase.
Sources
- CEC Solar Equipment List — Grid-Support Inverters (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
- CEC Solar Equipment List — PV Modules (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
- NFPA 70 National Electrical Code (Section Numbers & Standard Engineering Tables Only) — National Fire Protection Association (NFPA), 2020 / 2023 / 2026 Editions (retrieved 2026-11-23)