KACO new energy GmbH: KACO blueplanet 125 TL3 M1 WM OD IIP0 {600V} — CEC Inverter Specifications

Manufacturer: KACO new energy GmbH Registry: CEC Verified Engineering Specification

KACO new energy GmbH: KACO blueplanet 125 TL3 M1 WM OD IIP0 {600V} outputs 138,663 W AC at 600 V, 3-phase (133.4 A continuous, 175 A OCPD), ranking #33 of 2,343 CEC inverters at 98.69% efficiency with a 875-1,300 V MPPT window and 1,300 V DC limit. All figures reconcile directly against federal energy archives, state electrical licensing boards, California Energy Commission datasheets, and National Electrical Code engineering constants.

AC Output (Paco)
138,663 W
AC Voltage
600 V, 3-phase
Min PV Breaker
175 A (2/0 AWG Cu)
CEC Efficiency
98.69%
Wall-mounted residential hybrid solar inverter and modular battery cabinet piped with galvanized EMT conduit
Wall-mounted residential hybrid solar inverter and modular battery cabinet piped with galvanized EMT conduit

How Does KACO new energy GmbH: KACO blueplanet 125 TL3 M1 WM OD IIP0 {600V} Compare Against Peer CEC Listings?

NEC 705.12 breaker requirements, efficiency placement, and 600 V, 3-phase grid-support overview for KACO new energy GmbH: KACO blueplanet 125 TL3 M1 WM OD IIP0 {600V}.

Rated at 138,663 W AC (133.4 A continuous), KACO new energy GmbH: KACO blueplanet 125 TL3 M1 WM OD IIP0 {600V} ranks #33 of 2,343 CEC units at 98.69% efficiency (+0.41 pts vs the 98.28% 600 V median). Minimum 75 C copper conductor sizing for its 175 A circuit is 2/0 AWG Cu per NEC Table 310.16. Cold-weather string Voc must remain under 1,300 V DC at record local winter lows.

Where Does KACO new energy GmbH: KACO blueplanet 125 TL3 M1 WM OD IIP0 {600V} Fall Across Listed CEC Models?

Marks KACO new energy GmbH: KACO blueplanet 125 TL3 M1 WM OD IIP0 {600V} (138,663 W AC) across the California Energy Commission inverter AC capacity distribution.

AC Power Distribution Across Listed CEC Inverters (up to 25 kW)Shows where KACO new energy GmbH: KACO blueplanet 125 TL3 M1 WM OD IIP0 {600V} (138,663 W AC) sits across CEC inverters. 190-2258 W AC: 584 entries1902258-4325 W AC: 158 entries4325-6392 W AC: 259 entries6392-8460 W AC: 270 entries63928460-10528 W AC: 258 entries10528-12595 W AC: 116 entries12595-14662 W AC: 17 entries1259514662-16730 W AC: 37 entries16730-18798 W AC: 7 entries18798-20865 W AC: 11 entries1879820865-22932 W AC: 5 entries22932-25000 W AC: 26 entries22932Median 7,680 W ACKACO new energy Gm: 138,663 W

What Dataset Percentiles Define KACO new energy GmbH: KACO blueplanet 125 TL3 M1 WM OD IIP0 {600V}?

Benchmarks KACO new energy GmbH: KACO blueplanet 125 TL3 M1 WM OD IIP0 {600V} continuous AC output, 98.69% CEC weighted efficiency, and 175 A OCPD breaker demand.

KACO new energy GmbH: KACO blueplanet 125 TL3 M1 WM OD IIP0 {600V} Technical ThresholdsPercentile comparison for KACO new energy GmbH: KACO blueplanet 125 TL3 M1 WM OD IIP0 {600V} AC output, weighted CEC efficiency, and OCPD sizing. 0% (Low)50% Median100% (Top)Rated AC Output138,663 WCEC Efficiency98.69%Backfeed Breaker175 A

What Do the Dataset Ranks Show for KACO new energy GmbH: KACO blueplanet 125 TL3 M1 WM OD IIP0 {600V}?

Four key NEC 705.12 and California Energy Commission metrics defining KACO new energy GmbH: KACO blueplanet 125 TL3 M1 WM OD IIP0 {600V} by KACO new energy GmbH.

Eff #33 / 2,343

98.69% CEC Weighted Efficiency

+0.41 pts vs the 98.28% 600 V median; overall power rank #281 (138,663 W, top 12.1%; higher than 87.9% of peers).

NEC 705.12 Check

175 A Required Backfeed OCPD

125% x 133.4 A = 166.8 A -> 175 A standard OCPD using 2/0 AWG Cu (75 C).

MPPT Window

875 V - 1,300 V (Max 1,300 V DC)

Tracking span of 425.0 V; active in CEC directory (grid-tied PV inverter).

Commercial / 3-Phase Fit

Supply-Side Tap (705.11) / Dedicated Switchboard

Evaluated for 600 V, 3-phase switchgear (200A Bus / 200A Main (600V) to 1,200A Bus / 1,200A Main (600V)) under NEC 705.12 / 705.11.

NEC 705.12 Backfeed OCPD & 120% Busbar Formula

I_cont = 138663.0W / 600 V 3-phase -> 133.4 A | Breaker >= 1.25 * 133.4 = 166.8 A -> 175 A

CEC Inverters.csv for KACO new energy GmbH: KACO blueplanet 125 TL3 M1 WM OD IIP0 {600V}: Paco=138663.0 W, Vac=600 V, Vdcmax=1300.0 V, Eff=98.69%.

Result: Min 175 A breaker & 2/0 AWG Cu (75 C); 1,200A Bus / 1,200A Main (600V): PASS (120% Commercial Busbar).

What Are the Published CEC Specifications for KACO new energy GmbH: KACO blueplanet 125 TL3 M1 WM OD IIP0 {600V}?

Official laboratory CEC ratings, MPPT operating window, and DC voltage bounds recorded for KACO new energy GmbH: KACO blueplanet 125 TL3 M1 WM OD IIP0 {600V}.

Official California Energy Commission (NREL SAM) test parameters for KACO new energy GmbH: KACO blueplanet 125 TL3 M1 WM OD IIP0 {600V}.
ParameterMeasured / Listed ValueEngineering Significance
Max Continuous AC Power (Paco) 138,663 W Determines required backfeed OCPD size via 125% continuous rule
Nominal AC Voltage (Vac) 600 V, 3-phase 240V split-phase residential vs. 208V/480V/MV commercial
Max DC Input Voltage (Vdcmax) 1,300 V Hard ceiling for cold-weather PV string Voc under NEC 690.7
MPPT Operating Range 875 V - 1,300 V Optimal DC string Vmp window for full power harvest
Max Input DC Current (Idcmax) 143.232 A Used to verify parallel string combiner limits
CEC Weighted Efficiency 98.69% Calculated AC/DC conversion ratio from CEC test protocol
Inverter Topology Hybrid: No (Grid-Tied PV) CEC Solar Equipment List grid-support certification

What Switchgear Limits Apply to KACO new energy GmbH: KACO blueplanet 125 TL3 M1 WM OD IIP0 {600V} (600 V, 3-phase)?

Evaluates KACO new energy GmbH: KACO blueplanet 125 TL3 M1 WM OD IIP0 {600V} (175 A OCPD) across standard 100 A to 225 A busbars or commercial switchboards.

Evaluates KACO new energy GmbH: KACO blueplanet 125 TL3 M1 WM OD IIP0 {600V} (175 A required OCPD at 600 V, 3-phase) across standard distribution busbars.
Switchboard / Interconnect120% Max BackfeedRequired PV OCPDCompliance Verdict
200A Bus / 200A Main (600V) 40 A 175 A Supply-Side Tap (705.11) / Dedicated Switchboard
400A Bus / 400A Main (600V) 80 A 175 A Supply-Side Tap (705.11) / Dedicated Switchboard
600A Bus / 600A Main (600V) 120 A 175 A Supply-Side Tap (705.11) / Dedicated Switchboard
800A Bus / 800A Main (600V) 160 A 175 A Supply-Side Tap (705.11) / Dedicated Switchboard
1,200A Bus / 1,200A Main (600V) 240 A 175 A PASS (120% Commercial Busbar)

Which CEC PV Module Strings Pair With KACO new energy GmbH: KACO blueplanet 125 TL3 M1 WM OD IIP0 {600V}?

Sample PV string lengths aligned within 875-1,300 V MPPT and 1,300 V DC max at -10 C. Published percentiles compare local state, county, metro, and certified equipment metrics against nationwide residential electrical baselines.

Sampled CEC PV modules aligned within 875.0-1300.0 V MPPT and 1300.0 V max DC at -10 C.
CEC ModuleSTC (W)-10 C VocValid String RangeMax String DC
AXITEC AC-590TGB/144TS 590.0 W 56.24 V 21 to 23 panels 13.57 kW
Aptos Solar Technology LLC DNA-108-MFN10-440W 440.0 W 42.15 V 27 to 30 panels 13.2 kW
Boviet Solar Technology Co Ltd BVM7610M-425-H-HC-BF 425.0 W 44.75 V 26 to 29 panels 12.32 kW
CSI Solar Co Ltd CS6P-200P 200.0 W 40.6 V 31 to 32 panels 6.4 kW

Which Competing Grid-Support Inverters Compare to KACO new energy GmbH: KACO blueplanet 125 TL3 M1 WM OD IIP0 {600V}?

Competing CEC grid-support inverters near 138,663 W AC and 600 V, 3-phase, led by LS Energy Solutions LLC: PBE-6140-R61-1A0-1000 {600V}.

Alternative CEC inverters at comparable AC output power and voltage class.
Alternative InverterAC OutputDeltaVacMax DCCEC Eff
LS Energy Solutions LLC: PBE-6140-R61-1A0-1000 {600V}
LS Energy Solutions LLC
139,449 W +786 W 600.0 V 1350.0 V 98.27%
Ginlong Technologies Co Ltd: Solis-125K-EHV-5G-US-PLUS {600V}
Ginlong Technologies Co Ltd
136,724 W -1939 W 600.0 V 1300.0 V 98.09%
Siemens Industry Inc: blueplanet125 TL3 GEN2 M1 WM OD USP0 {600V}
Siemens Industry Inc
136,470 W -2193 W 600.0 V 1300.0 V 98.68%
Siemens Industry Inc: blueplanet125 TL3 GEN2 M1 WM OD USPX {600V}
Siemens Industry Inc
136,470 W -2193 W 600.0 V 1300.0 V 98.68%
What to Check & Best-Fit Scenarios

What Are the Interconnection Limits and Best-Fit Uses for KACO new energy GmbH: KACO blueplanet 125 TL3 M1 WM OD IIP0 {600V}?

Check KACO new energy GmbH: KACO blueplanet 125 TL3 M1 WM OD IIP0 {600V} (138,663 W AC, 175 A OCPD) against your main panel busbar, winter string Voc, and IEEE 1547 outage rules.

  • Anti-islanding shutdown: grid-tied inverters shut off within 2 seconds during blackouts under IEEE 1547 unless paired with a battery microgrid interconnect.
  • Busbar 120% limit: Commercial 600 V, 3-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (600V) or NEC 705.11 supply-side tap.
  • Cold Voc hard ceiling: never allow winter open-circuit PV string voltage to exceed 1,300 V DC on KACO new energy GmbH: KACO blueplanet 125 TL3 M1 WM OD IIP0 {600V}.

KACO new energy GmbH: KACO blueplanet 125 TL3 M1 WM OD IIP0 {600V} Panel & Wire Spec

Size 75 C copper conductors at 2/0 AWG Cu on a 175 A OCPD breaker (133.4 A continuous).

Alternative Inverter Comparison

Compare efficiency (98.69%) and MPPT window (875-1,300 V) directly against LS Energy Solutions LLC: PBE-6140-R61-1A0-1000 {600V} (139,449 W).

Which Homeowner Electrical & Solar Questions Come Up Most Often?

Answers for KACO new energy GmbH: KACO blueplanet 125 TL3 M1 WM OD IIP0 {600V} by KACO new energy GmbH covering breaker sizing, MPPT limits, and 600 V, 3-phase interconnection.

What breaker and wire size does KACO new energy GmbH: KACO blueplanet 125 TL3 M1 WM OD IIP0 {600V} require?

At 138,663 W continuous AC (600 V, 3-phase), continuous current is 133.4 A; 125% NEC 690.8/705.12 sizing requires a 175 A breaker and 2/0 AWG Cu (75 C) wire.

What commercial switchgear or feeder sizing does KACO new energy GmbH: KACO blueplanet 125 TL3 M1 WM OD IIP0 {600V} require?

At 138,663 W AC and 600 V, 3-phase, continuous line current is 133.4 A, requiring a 175 A OCPD and 1,200A Bus / 1,200A Main (600V) or NEC 705.11 interconnection.

How does KACO new energy GmbH: KACO blueplanet 125 TL3 M1 WM OD IIP0 {600V} compare to LS Energy Solutions LLC: PBE-6140-R61-1A0-1000 {600V}?

KACO new energy GmbH: KACO blueplanet 125 TL3 M1 WM OD IIP0 {600V} delivers 138,663 W AC at 98.69% CEC efficiency with a 1,300 V DC ceiling, while LS Energy Solutions LLC: PBE-6140-R61-1A0-1000 {600V} outputs 139,449 W at 600 V, 3-phase.

Sources

  1. CEC Solar Equipment List — Grid-Support Inverters (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
  2. CEC Solar Equipment List — PV Modules (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
  3. NFPA 70 National Electrical Code (Section Numbers & Standard Engineering Tables Only) — National Fire Protection Association (NFPA), 2020 / 2023 / 2026 Editions (retrieved 2026-11-23)

Which Regional Electrical & Panel Upgrade Metros Compare Closest?