KACO new energy GmbH: KACO blueplanet 137 TL3 M1 WM OD IIPX {600V} outputs 138,663 W AC at 600 V, 3-phase (133.4 A continuous, 175 A OCPD), ranking #33 of 2,343 CEC inverters at 98.69% efficiency with a 875-1,300 V MPPT window and 1,300 V DC limit. All figures reconcile directly against federal energy archives, state electrical licensing boards, California Energy Commission datasheets, and National Electrical Code engineering constants.
- AC Output (Paco)
- 138,663 W
- AC Voltage
- 600 V, 3-phase
- Min PV Breaker
- 175 A (2/0 AWG Cu)
- CEC Efficiency
- 98.69%
How Does KACO new energy GmbH: KACO blueplanet 137 TL3 M1 WM OD IIPX {600V} Compare Against Peer CEC Listings?
CEC efficiency rank (#33), 875-1,300 V MPPT tracking, and panel fit for KACO new energy GmbH: KACO blueplanet 137 TL3 M1 WM OD IIPX {600V}.
KACO new energy GmbH: KACO blueplanet 137 TL3 M1 WM OD IIPX {600V} from KACO new energy GmbH outputs 133.4 A continuous AC at 600 V, 3-phase (138,663 W AC, rank #281). Paired with 2/0 AWG Cu conductors and a 175 A OCPD, its 98.69% CEC efficiency compares closely with LS Energy Solutions LLC: PBE-6140-R61-1A0-1000 {600V} (139,449 W). Keep NEC 690.7 winter string Voc below 1,300 V DC.
Where Does KACO new energy GmbH: KACO blueplanet 137 TL3 M1 WM OD IIPX {600V} Fall Across Listed CEC Models?
CEC inverter wattage histogram highlighting KACO new energy GmbH: KACO blueplanet 137 TL3 M1 WM OD IIPX {600V} at 138,663 W continuous AC output.
What Dataset Percentiles Define KACO new energy GmbH: KACO blueplanet 137 TL3 M1 WM OD IIPX {600V}?
Dataset percentiles comparing KACO new energy GmbH: KACO blueplanet 137 TL3 M1 WM OD IIPX {600V} against 2,343 certified grid-support inverters nationwide.
What Do the Dataset Ranks Show for KACO new energy GmbH: KACO blueplanet 137 TL3 M1 WM OD IIPX {600V}?
Engineering highlights for KACO new energy GmbH: KACO blueplanet 137 TL3 M1 WM OD IIPX {600V} covering efficiency, 2/0 AWG Cu feeder, and panel compatibility.
98.69% CEC Weighted Efficiency
+0.41 pts vs the 98.28% 600 V median; overall power rank #281 (138,663 W, top 12.1%; higher than 87.9% of peers).
175 A Required Backfeed OCPD
125% x 133.4 A = 166.8 A -> 175 A standard OCPD using 2/0 AWG Cu (75 C).
875 V - 1,300 V (Max 1,300 V DC)
Tracking span of 425.0 V; active in CEC directory (grid-tied PV inverter).
Supply-Side Tap (705.11) / Dedicated Switchboard
Evaluated for 600 V, 3-phase switchgear (200A Bus / 200A Main (600V) to 1,200A Bus / 1,200A Main (600V)) under NEC 705.12 / 705.11.
NEC 705.12 Backfeed OCPD & 120% Busbar Formula
I_cont = 138663.0W / 600 V 3-phase -> 133.4 A | Breaker >= 1.25 * 133.4 = 166.8 A -> 175 A
CEC Inverters.csv for KACO new energy GmbH: KACO blueplanet 137 TL3 M1 WM OD IIPX {600V}: Paco=138663.0 W, Vac=600 V, Vdcmax=1300.0 V, Eff=98.69%.
Result: Min 175 A breaker & 2/0 AWG Cu (75 C); 1,200A Bus / 1,200A Main (600V): PASS (120% Commercial Busbar).
What Are the Published CEC Specifications for KACO new energy GmbH: KACO blueplanet 137 TL3 M1 WM OD IIPX {600V}?
California Energy Commission Solar Equipment List parameters for KACO new energy GmbH: KACO blueplanet 137 TL3 M1 WM OD IIPX {600V} (grid-tied PV inverter) interconnection.
| Parameter | Measured / Listed Value | Engineering Significance |
|---|---|---|
| Max Continuous AC Power (Paco) | 138,663 W | Determines required backfeed OCPD size via 125% continuous rule |
| Nominal AC Voltage (Vac) | 600 V, 3-phase | 240V split-phase residential vs. 208V/480V/MV commercial |
| Max DC Input Voltage (Vdcmax) | 1,300 V | Hard ceiling for cold-weather PV string Voc under NEC 690.7 |
| MPPT Operating Range | 875 V - 1,300 V | Optimal DC string Vmp window for full power harvest |
| Max Input DC Current (Idcmax) | 143.232 A | Used to verify parallel string combiner limits |
| CEC Weighted Efficiency | 98.69% | Calculated AC/DC conversion ratio from CEC test protocol |
| Inverter Topology | Hybrid: No (Grid-Tied PV) | CEC Solar Equipment List grid-support certification |
What Switchgear Limits Apply to KACO new energy GmbH: KACO blueplanet 137 TL3 M1 WM OD IIPX {600V} (600 V, 3-phase)?
Panelboard and switchgear backfeed allowances for KACO new energy GmbH: KACO blueplanet 137 TL3 M1 WM OD IIPX {600V} (175 A OCPD).
| Switchboard / Interconnect | 120% Max Backfeed | Required PV OCPD | Compliance Verdict |
|---|---|---|---|
| 200A Bus / 200A Main (600V) | 40 A | 175 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| 400A Bus / 400A Main (600V) | 80 A | 175 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| 600A Bus / 600A Main (600V) | 120 A | 175 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| 800A Bus / 800A Main (600V) | 160 A | 175 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| 1,200A Bus / 1,200A Main (600V) | 240 A | 175 A | PASS (120% Commercial Busbar) |
Which CEC PV Module Strings Pair With KACO new energy GmbH: KACO blueplanet 137 TL3 M1 WM OD IIPX {600V}?
Representative PV panel pairings verified under NEC 690.7 cold Voc for KACO new energy GmbH: KACO blueplanet 137 TL3 M1 WM OD IIPX {600V}.
| CEC Module | STC (W) | -10 C Voc | Valid String Range | Max String DC |
|---|---|---|---|---|
| AXITEC AC-590TGB/144TS | 590.0 W | 56.24 V | 21 to 23 panels | 13.57 kW |
| Aptos Solar Technology LLC DNA-108-MFN10-440W | 440.0 W | 42.15 V | 27 to 30 panels | 13.2 kW |
| Boviet Solar Technology Co Ltd BVM7610M-425-H-HC-BF | 425.0 W | 44.75 V | 26 to 29 panels | 12.32 kW |
| CSI Solar Co Ltd CS6P-200P | 200.0 W | 40.6 V | 31 to 32 panels | 6.4 kW |
Which Competing Grid-Support Inverters Compare to KACO new energy GmbH: KACO blueplanet 137 TL3 M1 WM OD IIPX {600V}?
Four alternative CEC inverters matched to KACO new energy GmbH: KACO blueplanet 137 TL3 M1 WM OD IIPX {600V} (138,663 W AC), led by LS Energy Solutions LLC: PBE-6140-R61-1A0-1000 {600V}.
| Alternative Inverter | AC Output | Delta | Vac | Max DC | CEC Eff |
|---|---|---|---|---|---|
| LS Energy Solutions LLC: PBE-6140-R61-1A0-1000 {600V} LS Energy Solutions LLC |
139,449 W | +786 W | 600.0 V | 1350.0 V | 98.27% |
| Ginlong Technologies Co Ltd: Solis-125K-EHV-5G-US-PLUS {600V} Ginlong Technologies Co Ltd |
136,724 W | -1939 W | 600.0 V | 1300.0 V | 98.09% |
| Siemens Industry Inc: blueplanet125 TL3 GEN2 M1 WM OD USP0 {600V} Siemens Industry Inc |
136,470 W | -2193 W | 600.0 V | 1300.0 V | 98.68% |
| Siemens Industry Inc: blueplanet125 TL3 GEN2 M1 WM OD USPX {600V} Siemens Industry Inc |
136,470 W | -2193 W | 600.0 V | 1300.0 V | 98.68% |
What Are the Interconnection Limits and Best-Fit Uses for KACO new energy GmbH: KACO blueplanet 137 TL3 M1 WM OD IIPX {600V}?
Check KACO new energy GmbH: KACO blueplanet 137 TL3 M1 WM OD IIPX {600V} (138,663 W AC, 175 A OCPD) against your main panel busbar, winter string Voc, and IEEE 1547 outage rules.
- Anti-islanding shutdown: grid-tied inverters shut off within 2 seconds during blackouts under IEEE 1547 unless paired with a battery microgrid interconnect.
- Busbar 120% limit: Commercial 600 V, 3-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (600V) or NEC 705.11 supply-side tap.
- Cold Voc hard ceiling: never allow winter open-circuit PV string voltage to exceed 1,300 V DC on KACO new energy GmbH: KACO blueplanet 137 TL3 M1 WM OD IIPX {600V}.
KACO new energy GmbH: KACO blueplanet 137 TL3 M1 WM OD IIPX {600V} Panel & Wire Spec
Size 75 C copper conductors at 2/0 AWG Cu on a 175 A OCPD breaker (133.4 A continuous).
Alternative Inverter Comparison
Compare efficiency (98.69%) and MPPT window (875-1,300 V) directly against LS Energy Solutions LLC: PBE-6140-R61-1A0-1000 {600V} (139,449 W).
Which Homeowner Electrical & Solar Questions Come Up Most Often?
Answers for KACO new energy GmbH: KACO blueplanet 137 TL3 M1 WM OD IIPX {600V} by KACO new energy GmbH covering breaker sizing, MPPT limits, and 600 V, 3-phase interconnection.
What breaker and wire size does KACO new energy GmbH: KACO blueplanet 137 TL3 M1 WM OD IIPX {600V} require?
At 138,663 W continuous AC (600 V, 3-phase), continuous current is 133.4 A; 125% NEC 690.8/705.12 sizing requires a 175 A breaker and 2/0 AWG Cu (75 C) wire.
What commercial switchgear or feeder sizing does KACO new energy GmbH: KACO blueplanet 137 TL3 M1 WM OD IIPX {600V} require?
At 138,663 W AC and 600 V, 3-phase, continuous line current is 133.4 A, requiring a 175 A OCPD and 1,200A Bus / 1,200A Main (600V) or NEC 705.11 interconnection.
How does KACO new energy GmbH: KACO blueplanet 137 TL3 M1 WM OD IIPX {600V} compare to LS Energy Solutions LLC: PBE-6140-R61-1A0-1000 {600V}?
KACO new energy GmbH: KACO blueplanet 137 TL3 M1 WM OD IIPX {600V} delivers 138,663 W AC at 98.69% CEC efficiency with a 1,300 V DC ceiling, while LS Energy Solutions LLC: PBE-6140-R61-1A0-1000 {600V} outputs 139,449 W at 600 V, 3-phase.