Chint Power Systems America: CPS ECB625KTL-M/US-480 {480V} outputs 62,500 W AC at 480 V, 3-phase (75.2 A continuous, 100 A OCPD), ranking #647 of 2,343 CEC inverters at 97.36% efficiency with a 750-1,100 V MPPT window and 1,100 V DC limit. All figures reconcile directly against federal energy archives, state electrical licensing boards, California Energy Commission datasheets, and National Electrical Code engineering constants.
- AC Output (Paco)
- 62,500 W
- AC Voltage
- 480 V, 3-phase
- Min PV Breaker
- 100 A (3 AWG Cu)
- CEC Efficiency
- 97.36%
How Does Chint Power Systems America: CPS ECB625KTL-M/US-480 {480V} Compare Against Peer CEC Listings?
How Chint Power Systems America Chint Power Systems America: CPS ECB625KTL-M/US-480 {480V} compares on 97.36% efficiency, MPPT span, and 120% busbar interconnection.
With a 750-1,100 V MPPT tracking band and 1,100 V DC ceiling, Chint Power Systems America: CPS ECB625KTL-M/US-480 {480V} handles 62,500 W continuous AC (12,500 W above the 50,000 W 480 V median). Commercial 480 V, 3-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (480V) or NEC 705.11 supply-side tap. Installers comparing Chint Power Systems America against BYD Auto Industry Company Limited: BEG60KTL-U-R1 {480V} (60,276 W) should verify whether listed since 2025-06-23 grid-support firmware meets local IEEE 1547 utility rules.
Where Does Chint Power Systems America: CPS ECB625KTL-M/US-480 {480V} Fall Across Listed CEC Models?
Position of Chint Power Systems America: CPS ECB625KTL-M/US-480 {480V} (62,500 W AC) relative to the 7,680 W CEC median inverter.
What Dataset Percentiles Define Chint Power Systems America: CPS ECB625KTL-M/US-480 {480V}?
Percentile placement of Chint Power Systems America: CPS ECB625KTL-M/US-480 {480V} across AC power class, conversion efficiency, and backfeed breaker size.
What Do the Dataset Ranks Show for Chint Power Systems America: CPS ECB625KTL-M/US-480 {480V}?
Primary electrical sizing limits, efficiency ranks, and NEC 705.12 / 690.7 thresholds for Chint Power Systems America: CPS ECB625KTL-M/US-480 {480V}.
97.36% CEC Weighted Efficiency
-0.66 pts vs the 98.02% 480 V median; overall power rank #393 (62,500 W, top 16.8%; higher than 83.2% of peers).
100 A Required Backfeed OCPD
125% x 75.2 A = 94.0 A -> 100 A standard OCPD using 3 AWG Cu (75 C).
750 V - 1,100 V (Max 1,100 V DC)
Tracking span of 350.0 V; listed since 2025-06-23 (grid-tied PV inverter).
Supply-Side Tap (705.11) / Dedicated Switchboard
Evaluated for 480 V, 3-phase switchgear (200A Bus / 200A Main (480V) to 1,200A Bus / 1,200A Main (480V)) under NEC 705.12 / 705.11.
NEC 705.12 Backfeed OCPD & 120% Busbar Formula
I_cont = 62500.0W / 480 V 3-phase -> 75.2 A | Breaker >= 1.25 * 75.2 = 94.0 A -> 100 A
CEC Inverters.csv for Chint Power Systems America: CPS ECB625KTL-M/US-480 {480V}: Paco=62500.0 W, Vac=480 V, Vdcmax=1100.0 V, Eff=97.36%.
Result: Min 100 A breaker & 3 AWG Cu (75 C); 1,200A Bus / 1,200A Main (480V): PASS (120% Commercial Busbar).
What Are the Published CEC Specifications for Chint Power Systems America: CPS ECB625KTL-M/US-480 {480V}?
Official California Energy Commission electrical test parameters, AC voltage, and DC limits for Chint Power Systems America: CPS ECB625KTL-M/US-480 {480V}.
| Parameter | Measured / Listed Value | Engineering Significance |
|---|---|---|
| Max Continuous AC Power (Paco) | 62,500 W | Determines required backfeed OCPD size via 125% continuous rule |
| Nominal AC Voltage (Vac) | 480 V, 3-phase | 240V split-phase residential vs. 208V/480V/MV commercial |
| Max DC Input Voltage (Vdcmax) | 1,100 V | Hard ceiling for cold-weather PV string Voc under NEC 690.7 |
| MPPT Operating Range | 750 V - 1,100 V | Optimal DC string Vmp window for full power harvest |
| Max Input DC Current (Idcmax) | 69.3998 A | Used to verify parallel string combiner limits |
| CEC Weighted Efficiency | 97.36% | Calculated AC/DC conversion ratio from CEC test protocol |
| CEC Listing Date & Hybrid | 2025-06-23 / Hybrid: No (Grid-Tied PV) | Utility interconnection approval metadata |
What Switchgear Limits Apply to Chint Power Systems America: CPS ECB625KTL-M/US-480 {480V} (480 V, 3-phase)?
Check whether Chint Power Systems America: CPS ECB625KTL-M/US-480 {480V} (100 A breaker) fits without main breaker derate or supply-side taps.
| Switchboard / Interconnect | 120% Max Backfeed | Required PV OCPD | Compliance Verdict |
|---|---|---|---|
| 200A Bus / 200A Main (480V) | 40 A | 100 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| 400A Bus / 400A Main (480V) | 80 A | 100 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| 600A Bus / 600A Main (480V) | 120 A | 100 A | PASS (120% Commercial Busbar) |
| 800A Bus / 800A Main (480V) | 160 A | 100 A | PASS (120% Commercial Busbar) |
| 1,200A Bus / 1,200A Main (480V) | 240 A | 100 A | PASS (120% Commercial Busbar) |
Which CEC PV Module Strings Pair With Chint Power Systems America: CPS ECB625KTL-M/US-480 {480V}?
Verified cold-weather (-10 C) series module counts matched to Chint Power Systems America: CPS ECB625KTL-M/US-480 {480V}'s 1,100 V DC ceiling.
| CEC Module | STC (W) | -10 C Voc | Valid String Range | Max String DC |
|---|---|---|---|---|
| AXITEC AC-590TGB/144TS | 590.0 W | 56.24 V | 18 to 19 panels | 11.21 kW |
| Aptos Solar Technology LLC DNA-108-MFN10-440W | 440.0 W | 42.15 V | 23 to 26 panels | 11.44 kW |
| Boviet Solar Technology Co Ltd BVM7610M-425-H-HC-BF | 425.0 W | 44.75 V | 22 to 24 panels | 10.2 kW |
| CSI Solar Co Ltd CS6P-200P | 200.0 W | 40.6 V | 26 to 27 panels | 5.4 kW |
Which Competing Grid-Support Inverters Compare to Chint Power Systems America: CPS ECB625KTL-M/US-480 {480V}?
Alternative CEC inverters comparable to Chint Power Systems America: CPS ECB625KTL-M/US-480 {480V}, including BYD Auto Industry Company Limited: BEG60KTL-U-R1 {480V} (60,276 W) at 480 V, 3-phase.
| Alternative Inverter | AC Output | Delta | Vac | Max DC | CEC Eff |
|---|---|---|---|---|---|
| BYD Auto Industry Company Limited: BEG60KTL-U-R1 {480V} BYD Auto Industry Company Limited |
60,276 W | -2224 W | 480.0 V | 950.0 V | 95.69% |
| ABB: PVS-60-TL-R-US {480V} ABB |
60,033 W | -2467 W | 480.0 V | 800.0 V | 98.18% |
| ABB: PVS-60-TL-S-R-US {480V} ABB |
60,033 W | -2467 W | 480.0 V | 800.0 V | 98.18% |
| ABB: PVS-60-TL-S-US {480V} ABB |
60,033 W | -2467 W | 480.0 V | 800.0 V | 98.18% |
What Are the Interconnection Limits and Best-Fit Uses for Chint Power Systems America: CPS ECB625KTL-M/US-480 {480V}?
Check Chint Power Systems America: CPS ECB625KTL-M/US-480 {480V} (62,500 W AC, 100 A OCPD) against your main panel busbar, winter string Voc, and IEEE 1547 outage rules.
- Anti-islanding shutdown: grid-tied inverters shut off within 2 seconds during blackouts under IEEE 1547 unless paired with a battery microgrid interconnect.
- Busbar 120% limit: Commercial 480 V, 3-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (480V) or NEC 705.11 supply-side tap.
- Cold Voc hard ceiling: never allow winter open-circuit PV string voltage to exceed 1,100 V DC on Chint Power Systems America: CPS ECB625KTL-M/US-480 {480V}.
Chint Power Systems America: CPS ECB625KTL-M/US-480 {480V} Panel & Wire Spec
Size 75 C copper conductors at 3 AWG Cu on a 100 A OCPD breaker (75.2 A continuous).
Alternative Inverter Comparison
Compare efficiency (97.36%) and MPPT window (750-1,100 V) directly against BYD Auto Industry Company Limited: BEG60KTL-U-R1 {480V} (60,276 W).
Which Homeowner Electrical & Solar Questions Come Up Most Often?
Answers for Chint Power Systems America: CPS ECB625KTL-M/US-480 {480V} by Chint Power Systems America covering breaker sizing, MPPT limits, and 480 V, 3-phase interconnection.
What breaker and wire size does Chint Power Systems America: CPS ECB625KTL-M/US-480 {480V} require?
At 62,500 W continuous AC (480 V, 3-phase), continuous current is 75.2 A; 125% NEC 690.8/705.12 sizing requires a 100 A breaker and 3 AWG Cu (75 C) wire.
What commercial switchgear or feeder sizing does Chint Power Systems America: CPS ECB625KTL-M/US-480 {480V} require?
At 62,500 W AC and 480 V, 3-phase, continuous line current is 75.2 A, requiring a 100 A OCPD and 1,200A Bus / 1,200A Main (480V) or NEC 705.11 interconnection.
How does Chint Power Systems America: CPS ECB625KTL-M/US-480 {480V} compare to BYD Auto Industry Company Limited: BEG60KTL-U-R1 {480V}?
Chint Power Systems America: CPS ECB625KTL-M/US-480 {480V} delivers 62,500 W AC at 97.36% CEC efficiency with a 1,100 V DC ceiling, while BYD Auto Industry Company Limited: BEG60KTL-U-R1 {480V} outputs 60,276 W at 480 V, 3-phase.
Sources
- CEC Solar Equipment List — Grid-Support Inverters (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
- CEC Solar Equipment List — PV Modules (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
- NFPA 70 National Electrical Code (Section Numbers & Standard Engineering Tables Only) — National Fire Protection Association (NFPA), 2020 / 2023 / 2026 Editions (retrieved 2026-11-23)