ABB: UNO-DM-60-TL-PLUS-US-SC-RA {208V} outputs 6,000 W AC at 208 V, commercial single-phase (28.8 A continuous, 40 A OCPD), ranking #1,430 of 2,343 CEC inverters at 96.57% efficiency with a 240-480 V MPPT window and 480 V DC limit. All figures reconcile directly against federal energy archives, state electrical licensing boards, California Energy Commission datasheets, and National Electrical Code engineering constants.
- AC Output (Paco)
- 6,000 W
- AC Voltage
- 208 V, commercial single-phase
- Min PV Breaker
- 40 A (8 AWG Cu)
- CEC Efficiency
- 96.57%
How Does ABB: UNO-DM-60-TL-PLUS-US-SC-RA {208V} Compare Against Peer CEC Listings?
NEC 705.12 breaker requirements, efficiency placement, and 208 V, commercial single-phase grid-support overview for ABB: UNO-DM-60-TL-PLUS-US-SC-RA {208V}. Homeowners and permit reviewers can filter tables below to benchmark specific ratings, wiring ages, and code allowances side by side.
Ranking #1,387 of 2,343 CEC inverters (below CEC median; higher than 39.4% of peers), ABB: UNO-DM-60-TL-PLUS-US-SC-RA {208V} is a grid-tied PV inverter delivering 6,000 W continuous AC at 208 V, commercial single-phase (28.8 A continuous). Commercial 208 V, commercial single-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (208V) or NEC 705.11 supply-side tap. Weighted CEC efficiency reaches 96.57% (+0.16 pts vs the 96.41% 208 V median) against peers like Delta Electronics: E8-TL-US(AC) {208V} (6,500 W).
Where Does ABB: UNO-DM-60-TL-PLUS-US-SC-RA {208V} Fall Across Listed CEC Models?
Marks ABB: UNO-DM-60-TL-PLUS-US-SC-RA {208V} (6,000 W AC) across the California Energy Commission inverter AC capacity distribution. Use these verified dataset benchmarks alongside a licensed electrician load calculation to compare residential upgrade bids with confidence.
What Dataset Percentiles Define ABB: UNO-DM-60-TL-PLUS-US-SC-RA {208V}?
Benchmarks ABB: UNO-DM-60-TL-PLUS-US-SC-RA {208V} continuous AC output, 96.57% CEC weighted efficiency, and 40 A OCPD breaker demand. Inspect manufacturer nameplate documentation, UL listing boundaries, and utility rate schedules closely before ordering electrical hardware.
What Do the Dataset Ranks Show for ABB: UNO-DM-60-TL-PLUS-US-SC-RA {208V}?
Four key NEC 705.12 and California Energy Commission metrics defining ABB: UNO-DM-60-TL-PLUS-US-SC-RA {208V} by ABB. Published percentiles compare local state, county, metro, and certified equipment metrics against nationwide residential electrical baselines.
96.57% CEC Weighted Efficiency
+0.16 pts vs the 96.41% 208 V median; overall power rank #1,387 (6,000 W, below CEC median; higher than 39.4% of peers).
40 A Required Backfeed OCPD
125% x 28.8 A = 36.0 A -> 40 A standard OCPD using 8 AWG Cu (75 C).
240 V - 480 V (Max 480 V DC)
Tracking span of 240.0 V; listed since 2020-08-21 (grid-tied PV inverter).
PASS (120% Commercial Busbar)
Evaluated for 208 V, commercial single-phase switchgear (200A Bus / 200A Main (208V) to 1,200A Bus / 1,200A Main (208V)) under NEC 705.12 / 705.11.
NEC 705.12 Backfeed OCPD & 120% Busbar Formula
I_cont = 6000.0W / 208 V -> 28.8 A | Breaker >= 1.25 * 28.8 = 36.0 A -> 40 A
CEC Inverters.csv for ABB: UNO-DM-60-TL-PLUS-US-SC-RA {208V}: Paco=6000.0 W, Vac=208 V, Vdcmax=480.0 V, Eff=96.57%.
Result: Min 40 A breaker & 8 AWG Cu (75 C); 1,200A Bus / 1,200A Main (208V): PASS (120% Commercial Busbar).
What Are the Published CEC Specifications for ABB: UNO-DM-60-TL-PLUS-US-SC-RA {208V}?
Official laboratory CEC ratings, MPPT operating window, and DC voltage bounds recorded for ABB: UNO-DM-60-TL-PLUS-US-SC-RA {208V}. Always verify current state NEC adoption cycles, local utility interconnection tariffs, and panel busbar ratings before pulling project permits.
| Parameter | Measured / Listed Value | Engineering Significance |
|---|---|---|
| Max Continuous AC Power (Paco) | 6,000 W | Determines required backfeed OCPD size via 125% continuous rule |
| Nominal AC Voltage (Vac) | 208 V, commercial single-phase | 240V split-phase residential vs. 208V/480V/MV commercial |
| Max DC Input Voltage (Vdcmax) | 480 V | Hard ceiling for cold-weather PV string Voc under NEC 690.7 |
| MPPT Operating Range | 240 V - 480 V | Optimal DC string Vmp window for full power harvest |
| Max Input DC Current (Idcmax) | 18.2732 A | Used to verify parallel string combiner limits |
| CEC Weighted Efficiency | 96.57% | Calculated AC/DC conversion ratio from CEC test protocol |
| CEC Listing Date & Hybrid | 2020-08-21 / Hybrid: No (Grid-Tied PV) | Utility interconnection approval metadata |
What Switchgear Limits Apply to ABB: UNO-DM-60-TL-PLUS-US-SC-RA {208V} (208 V, commercial single-phase)?
Evaluates ABB: UNO-DM-60-TL-PLUS-US-SC-RA {208V} (40 A OCPD) across standard 100 A to 225 A busbars or commercial switchboards.
| Switchboard / Interconnect | 120% Max Backfeed | Required PV OCPD | Compliance Verdict |
|---|---|---|---|
| 200A Bus / 200A Main (208V) | 40 A | 40 A | PASS (120% Commercial Busbar) |
| 400A Bus / 400A Main (208V) | 80 A | 40 A | PASS (120% Commercial Busbar) |
| 600A Bus / 600A Main (208V) | 120 A | 40 A | PASS (120% Commercial Busbar) |
| 800A Bus / 800A Main (208V) | 160 A | 40 A | PASS (120% Commercial Busbar) |
| 1,200A Bus / 1,200A Main (208V) | 240 A | 40 A | PASS (120% Commercial Busbar) |
Which CEC PV Module Strings Pair With ABB: UNO-DM-60-TL-PLUS-US-SC-RA {208V}?
Sample PV string lengths aligned within 240-480 V MPPT and 480 V DC max at -10 C. Compare thermal ratings, overcurrent protection caps, and continuous load headroom carefully before expanding an existing home service panel.
| CEC Module | STC (W) | -10 C Voc | Valid String Range | Max String DC |
|---|---|---|---|---|
| AXITEC AC-590TGB/144TS | 590.0 W | 56.24 V | 6 to 8 panels | 4.72 kW |
| Aptos Solar Technology LLC DNA-108-MFN10-440W | 440.0 W | 42.15 V | 8 to 11 panels | 4.84 kW |
| Boviet Solar Technology Co Ltd BVM7610M-425-H-HC-BF | 425.0 W | 44.75 V | 7 to 10 panels | 4.25 kW |
| CSI Solar Co Ltd CS6P-200P | 200.0 W | 40.6 V | 9 to 11 panels | 2.2 kW |
Which Competing Grid-Support Inverters Compare to ABB: UNO-DM-60-TL-PLUS-US-SC-RA {208V}?
Competing CEC grid-support inverters near 6,000 W AC and 208 V, commercial single-phase, led by Delta Electronics: E8-TL-US(AC) {208V}.
| Alternative Inverter | AC Output | Delta | Vac | Max DC | CEC Eff |
|---|---|---|---|---|---|
| Delta Electronics: E8-TL-US(AC) {208V} Delta Electronics |
6,500 W | +500 W | 208.0 V | 480.0 V | 97.65% |
| Delta Electronics: SOLIVIA 66 NA G4 TL {208V} Delta Electronics |
6,600 W | +600 W | 208.0 V | 500.0 V | 97.02% |
| Delta Electronics: SOLIVIA 76 NA G4 TL {208V} Delta Electronics |
6,600 W | +600 W | 208.0 V | 500.0 V | 97.02% |
| Altenergy Power System Inc: ELS-76 {208V} Altenergy Power System Inc |
6,606 W | +606 W | 208.0 V | 60.0 V | 93.96% |
What Are the Interconnection Limits and Best-Fit Uses for ABB: UNO-DM-60-TL-PLUS-US-SC-RA {208V}?
Check ABB: UNO-DM-60-TL-PLUS-US-SC-RA {208V} (6,000 W AC, 40 A OCPD) against your main panel busbar, winter string Voc, and IEEE 1547 outage rules.
- Anti-islanding shutdown: grid-tied inverters shut off within 2 seconds during blackouts under IEEE 1547 unless paired with a battery microgrid interconnect.
- Busbar 120% limit: Commercial 208 V, commercial single-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (208V) or NEC 705.11 supply-side tap.
- Cold Voc hard ceiling: never allow winter open-circuit PV string voltage to exceed 480 V DC on ABB: UNO-DM-60-TL-PLUS-US-SC-RA {208V}.
ABB: UNO-DM-60-TL-PLUS-US-SC-RA {208V} Panel & Wire Spec
Size 75 C copper conductors at 8 AWG Cu on a 40 A OCPD breaker (28.8 A continuous).
Alternative Inverter Comparison
Compare efficiency (96.57%) and MPPT window (240-480 V) directly against Delta Electronics: E8-TL-US(AC) {208V} (6,500 W).
Which Homeowner Electrical & Solar Questions Come Up Most Often?
Answers for ABB: UNO-DM-60-TL-PLUS-US-SC-RA {208V} by ABB covering breaker sizing, MPPT limits, and 208 V, commercial single-phase interconnection.
What breaker and wire size does ABB: UNO-DM-60-TL-PLUS-US-SC-RA {208V} require?
At 6,000 W continuous AC (208 V, commercial single-phase), continuous current is 28.8 A; 125% NEC 690.8/705.12 sizing requires a 40 A breaker and 8 AWG Cu (75 C) wire.
What commercial switchgear or feeder sizing does ABB: UNO-DM-60-TL-PLUS-US-SC-RA {208V} require?
At 6,000 W AC and 208 V, commercial single-phase, continuous line current is 28.8 A, requiring a 40 A OCPD and 1,200A Bus / 1,200A Main (208V) or NEC 705.11 interconnection.
How does ABB: UNO-DM-60-TL-PLUS-US-SC-RA {208V} compare to Delta Electronics: E8-TL-US(AC) {208V}?
ABB: UNO-DM-60-TL-PLUS-US-SC-RA {208V} delivers 6,000 W AC at 96.57% CEC efficiency with a 480 V DC ceiling, while Delta Electronics: E8-TL-US(AC) {208V} outputs 6,500 W at 208 V, commercial single-phase.