ABB: PVI-6000-OUTD-US-Z-A {277V} outputs 6,000 W AC at 480Y/277 V, 3-phase (7.2 A continuous, 15 A OCPD), ranking #1,161 of 2,343 CEC inverters at 96.82% efficiency with a 100-480 V MPPT window and 480 V DC limit. All figures reconcile directly against federal energy archives, state electrical licensing boards, California Energy Commission datasheets, and National Electrical Code engineering constants.
- AC Output (Paco)
- 6,000 W
- AC Voltage
- 480Y/277 V, 3-phase
- Min PV Breaker
- 15 A (14 AWG Cu)
- CEC Efficiency
- 96.82%
How Does ABB: PVI-6000-OUTD-US-Z-A {277V} Compare Against Peer CEC Listings?
Breaker sizing (15 A), 14 AWG Cu wire rules, and DC input limits for ABB: PVI-6000-OUTD-US-Z-A {277V}. Published percentiles compare local state, county, metro, and certified equipment metrics against nationwide residential electrical baselines.
For NEC 705.12 solar interconnection, ABB: PVI-6000-OUTD-US-Z-A {277V} outputs 7.2 A continuous AC at 480Y/277 V, 3-phase and needs a 15 A backfeed breaker on 14 AWG Cu (75 C). Commercial 480Y/277 V, 3-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (277V) or NEC 705.11 supply-side tap. Conversion efficiency scores 96.82% (#1,161 of 2,343, equal to overall CEC median).
Where Does ABB: PVI-6000-OUTD-US-Z-A {277V} Fall Across Listed CEC Models?
Output power comparison showing where ABB: PVI-6000-OUTD-US-Z-A {277V} sits among all 2,343 CEC-listed grid-support inverters. Homeowners and permit reviewers can filter tables below to benchmark specific ratings, wiring ages, and code allowances side by side.
What Dataset Percentiles Define ABB: PVI-6000-OUTD-US-Z-A {277V}?
Relative ranking of ABB: PVI-6000-OUTD-US-Z-A {277V} on continuous AC power, CEC weighted efficiency, and OCPD breaker current. Cross-check local Authority Having Jurisdiction amendments and serving utility net-metering terms before finalizing project sizing.
What Do the Dataset Ranks Show for ABB: PVI-6000-OUTD-US-Z-A {277V}?
Snapshot of ABB: PVI-6000-OUTD-US-Z-A {277V} efficiency rank (#1,161), OCPD breaker size, MPPT span, and busbar verdict. Review related calculators, peer benchmarks, and source citations below to validate design assumptions for your electrical service.
96.82% CEC Weighted Efficiency
equal to the 96.82% 277 V median; overall power rank #1,387 (6,000 W, below CEC median; higher than 39.4% of peers).
15 A Required Backfeed OCPD
125% x 7.2 A = 9.0 A -> 15 A standard OCPD using 14 AWG Cu (75 C).
100 V - 480 V (Max 480 V DC)
Tracking span of 380.0 V; listed since 2018-10-15 (grid-tied PV inverter).
PASS (120% Commercial Busbar)
Evaluated for 480Y/277 V, 3-phase switchgear (200A Bus / 200A Main (277V) to 1,200A Bus / 1,200A Main (277V)) under NEC 705.12 / 705.11.
NEC 705.12 Backfeed OCPD & 120% Busbar Formula
I_cont = 6000.0W / 480 V 3-phase -> 7.2 A | Breaker >= 1.25 * 7.2 = 9.0 A -> 15 A
CEC Inverters.csv for ABB: PVI-6000-OUTD-US-Z-A {277V}: Paco=6000.0 W, Vac=277 V, Vdcmax=480.0 V, Eff=96.82%.
Result: Min 15 A breaker & 14 AWG Cu (75 C); 1,200A Bus / 1,200A Main (277V): PASS (120% Commercial Busbar).
What Are the Published CEC Specifications for ABB: PVI-6000-OUTD-US-Z-A {277V}?
Complete California Energy Commission grid-support inverter ratings and hybrid battery capabilities for ABB: PVI-6000-OUTD-US-Z-A {277V}. Use these verified dataset benchmarks alongside a licensed electrician load calculation to compare residential upgrade bids with confidence.
| Parameter | Measured / Listed Value | Engineering Significance |
|---|---|---|
| Max Continuous AC Power (Paco) | 6,000 W | Determines required backfeed OCPD size via 125% continuous rule |
| Nominal AC Voltage (Vac) | 480Y/277 V, 3-phase | 240V split-phase residential vs. 208V/480V/MV commercial |
| Max DC Input Voltage (Vdcmax) | 480 V | Hard ceiling for cold-weather PV string Voc under NEC 690.7 |
| MPPT Operating Range | 100 V - 480 V | Optimal DC string Vmp window for full power harvest |
| Max Input DC Current (Idcmax) | 15.492 A | Used to verify parallel string combiner limits |
| CEC Weighted Efficiency | 96.82% | Calculated AC/DC conversion ratio from CEC test protocol |
| CEC Listing Date & Hybrid | 2018-10-15 / Hybrid: No (Grid-Tied PV) | Utility interconnection approval metadata |
What Switchgear Limits Apply to ABB: PVI-6000-OUTD-US-Z-A {277V} (480Y/277 V, 3-phase)?
NEC 705.12(B)(3)(2) backfeed compliance table for ABB: PVI-6000-OUTD-US-Z-A {277V} at 480Y/277 V, 3-phase. Compare thermal ratings, overcurrent protection caps, and continuous load headroom carefully before expanding an existing home service panel.
| Switchboard / Interconnect | 120% Max Backfeed | Required PV OCPD | Compliance Verdict |
|---|---|---|---|
| 200A Bus / 200A Main (277V) | 40 A | 15 A | PASS (120% Commercial Busbar) |
| 400A Bus / 400A Main (277V) | 80 A | 15 A | PASS (120% Commercial Busbar) |
| 600A Bus / 600A Main (277V) | 120 A | 15 A | PASS (120% Commercial Busbar) |
| 800A Bus / 800A Main (277V) | 160 A | 15 A | PASS (120% Commercial Busbar) |
| 1,200A Bus / 1,200A Main (277V) | 240 A | 15 A | PASS (120% Commercial Busbar) |
Which CEC PV Module Strings Pair With ABB: PVI-6000-OUTD-US-Z-A {277V}?
Minimum and maximum series solar module strings fitting ABB: PVI-6000-OUTD-US-Z-A {277V} MPPT and 480 V limits. All figures trace directly to published federal energy filings, state electrical boards, CEC datasheets, and NFPA 70 NEC tables.
| CEC Module | STC (W) | -10 C Voc | Valid String Range | Max String DC |
|---|---|---|---|---|
| AXITEC AC-590TGB/144TS | 590.0 W | 56.24 V | 3 to 8 panels | 4.72 kW |
| Aptos Solar Technology LLC DNA-108-MFN10-440W | 440.0 W | 42.15 V | 3 to 11 panels | 4.84 kW |
| Boviet Solar Technology Co Ltd BVM7610M-425-H-HC-BF | 425.0 W | 44.75 V | 3 to 10 panels | 4.25 kW |
| CSI Solar Co Ltd CS6P-200P | 200.0 W | 40.6 V | 4 to 11 panels | 2.2 kW |
Which Competing Grid-Support Inverters Compare to ABB: PVI-6000-OUTD-US-Z-A {277V}?
Peer 480Y/277 V, 3-phase CEC inverters near 6,000 W AC output such as Shenzhen Growatt New Energy Co Ltd: GROWATT 6000MTLP-US {277V}.
| Alternative Inverter | AC Output | Delta | Vac | Max DC | CEC Eff |
|---|---|---|---|---|---|
| Shenzhen Growatt New Energy Co Ltd: GROWATT 6000MTLP-US {277V} Shenzhen Growatt New Energy Co Ltd |
6,080 W | +80 W | 277.0 V | 550.0 V | 97.0% |
| Shenzhen Growatt New Energy Co Ltd: GROWATT 5000MTLP-US {277V} Shenzhen Growatt New Energy Co Ltd |
5,060 W | -940 W | 277.0 V | 550.0 V | 97.1% |
| Shenzhen Growatt New Energy Co Ltd: GROWATT 7000MTLP-US {277V} Shenzhen Growatt New Energy Co Ltd |
7,016 W | +1016 W | 277.0 V | 480.0 V | 96.5% |
| Shenzhen Growatt New Energy Co Ltd: GROWATT 4000MTLP-US {277V} Shenzhen Growatt New Energy Co Ltd |
4,060 W | -1940 W | 277.0 V | 550.0 V | 97.23% |
What Are the Interconnection Limits and Best-Fit Uses for ABB: PVI-6000-OUTD-US-Z-A {277V}?
Check ABB: PVI-6000-OUTD-US-Z-A {277V} (6,000 W AC, 15 A OCPD) against your main panel busbar, winter string Voc, and IEEE 1547 outage rules.
- Anti-islanding shutdown: grid-tied inverters shut off within 2 seconds during blackouts under IEEE 1547 unless paired with a battery microgrid interconnect.
- Busbar 120% limit: Commercial 480Y/277 V, 3-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (277V) or NEC 705.11 supply-side tap.
- Cold Voc hard ceiling: never allow winter open-circuit PV string voltage to exceed 480 V DC on ABB: PVI-6000-OUTD-US-Z-A {277V}.
ABB: PVI-6000-OUTD-US-Z-A {277V} Panel & Wire Spec
Size 75 C copper conductors at 14 AWG Cu on a 15 A OCPD breaker (7.2 A continuous).
Alternative Inverter Comparison
Compare efficiency (96.82%) and MPPT window (100-480 V) directly against Shenzhen Growatt New Energy Co Ltd: GROWATT 6000MTLP-US {277V} (6,080 W).
Which Homeowner Electrical & Solar Questions Come Up Most Often?
Answers for ABB: PVI-6000-OUTD-US-Z-A {277V} by ABB covering breaker sizing, MPPT limits, and 480Y/277 V, 3-phase interconnection.
What breaker and wire size does ABB: PVI-6000-OUTD-US-Z-A {277V} require?
At 6,000 W continuous AC (480Y/277 V, 3-phase), continuous current is 7.2 A; 125% NEC 690.8/705.12 sizing requires a 15 A breaker and 14 AWG Cu (75 C) wire.
What commercial switchgear or feeder sizing does ABB: PVI-6000-OUTD-US-Z-A {277V} require?
At 6,000 W AC and 480Y/277 V, 3-phase, continuous line current is 7.2 A, requiring a 15 A OCPD and 1,200A Bus / 1,200A Main (277V) or NEC 705.11 interconnection.
How does ABB: PVI-6000-OUTD-US-Z-A {277V} compare to Shenzhen Growatt New Energy Co Ltd: GROWATT 6000MTLP-US {277V}?
ABB: PVI-6000-OUTD-US-Z-A {277V} delivers 6,000 W AC at 96.82% CEC efficiency with a 480 V DC ceiling, while Shenzhen Growatt New Energy Co Ltd: GROWATT 6000MTLP-US {277V} outputs 6,080 W at 480Y/277 V, 3-phase.
Sources
- CEC Solar Equipment List — Grid-Support Inverters (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
- CEC Solar Equipment List — PV Modules (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
- NFPA 70 National Electrical Code (Section Numbers & Standard Engineering Tables Only) — National Fire Protection Association (NFPA), 2020 / 2023 / 2026 Editions (retrieved 2026-11-23)