ABB: PVI-6000-OUTD-US-A {277V} outputs 6,000 W AC at 480Y/277 V, 3-phase (7.2 A continuous, 15 A OCPD), ranking #1,161 of 2,343 CEC inverters at 96.82% efficiency with a 100-480 V MPPT window and 480 V DC limit. All figures reconcile directly against federal energy archives, state electrical licensing boards, California Energy Commission datasheets, and National Electrical Code engineering constants.
- AC Output (Paco)
- 6,000 W
- AC Voltage
- 480Y/277 V, 3-phase
- Min PV Breaker
- 15 A (14 AWG Cu)
- CEC Efficiency
- 96.82%
How Does ABB: PVI-6000-OUTD-US-A {277V} Compare Against Peer CEC Listings?
CEC efficiency rank (#1,161), 100-480 V MPPT tracking, and panel fit for ABB: PVI-6000-OUTD-US-A {277V}. Cross-check local Authority Having Jurisdiction amendments and serving utility net-metering terms before finalizing project sizing.
Operating at 480Y/277 V, 3-phase, ABB: PVI-6000-OUTD-US-A {277V} converts DC array energy at 96.82% CEC weighted efficiency (at overall CEC median; higher than 49.1% of peers) with a 480 V max DC input and 15.492 A max input current for NEC 690.7 string safety. Compare this 6,000 W grid-tied PV inverter directly with Shenzhen Growatt New Energy Co Ltd: GROWATT 6000MTLP-US {277V} (6,080 W). Commercial 480Y/277 V, 3-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (277V) or NEC 705.11 supply-side tap.
Where Does ABB: PVI-6000-OUTD-US-A {277V} Fall Across Listed CEC Models?
CEC inverter wattage histogram highlighting ABB: PVI-6000-OUTD-US-A {277V} at 6,000 W continuous AC output. Compare thermal ratings, overcurrent protection caps, and continuous load headroom carefully before expanding an existing home service panel.
What Dataset Percentiles Define ABB: PVI-6000-OUTD-US-A {277V}?
Dataset percentiles comparing ABB: PVI-6000-OUTD-US-A {277V} against 2,343 certified grid-support inverters nationwide. Homeowners and permit reviewers can filter tables below to benchmark specific ratings, wiring ages, and code allowances side by side.
What Do the Dataset Ranks Show for ABB: PVI-6000-OUTD-US-A {277V}?
Engineering highlights for ABB: PVI-6000-OUTD-US-A {277V} covering efficiency, 14 AWG Cu feeder, and panel compatibility. Regional housing vintage, storm hazard frequency, and wholesale utility prices directly govern residential upgrade payback across jurisdictions.
96.82% CEC Weighted Efficiency
equal to the 96.82% 277 V median; overall power rank #1,387 (6,000 W, below CEC median; higher than 39.4% of peers).
15 A Required Backfeed OCPD
125% x 7.2 A = 9.0 A -> 15 A standard OCPD using 14 AWG Cu (75 C).
100 V - 480 V (Max 480 V DC)
Tracking span of 380.0 V; listed since 2018-10-15 (grid-tied PV inverter).
PASS (120% Commercial Busbar)
Evaluated for 480Y/277 V, 3-phase switchgear (200A Bus / 200A Main (277V) to 1,200A Bus / 1,200A Main (277V)) under NEC 705.12 / 705.11.
NEC 705.12 Backfeed OCPD & 120% Busbar Formula
I_cont = 6000.0W / 480 V 3-phase -> 7.2 A | Breaker >= 1.25 * 7.2 = 9.0 A -> 15 A
CEC Inverters.csv for ABB: PVI-6000-OUTD-US-A {277V}: Paco=6000.0 W, Vac=277 V, Vdcmax=480.0 V, Eff=96.82%.
Result: Min 15 A breaker & 14 AWG Cu (75 C); 1,200A Bus / 1,200A Main (277V): PASS (120% Commercial Busbar).
What Are the Published CEC Specifications for ABB: PVI-6000-OUTD-US-A {277V}?
California Energy Commission Solar Equipment List parameters for ABB: PVI-6000-OUTD-US-A {277V} (grid-tied PV inverter) interconnection. Data intervals combine current 2025 federal utility and BLS wage releases with verified state electrical board rosters.
| Parameter | Measured / Listed Value | Engineering Significance |
|---|---|---|
| Max Continuous AC Power (Paco) | 6,000 W | Determines required backfeed OCPD size via 125% continuous rule |
| Nominal AC Voltage (Vac) | 480Y/277 V, 3-phase | 240V split-phase residential vs. 208V/480V/MV commercial |
| Max DC Input Voltage (Vdcmax) | 480 V | Hard ceiling for cold-weather PV string Voc under NEC 690.7 |
| MPPT Operating Range | 100 V - 480 V | Optimal DC string Vmp window for full power harvest |
| Max Input DC Current (Idcmax) | 15.492 A | Used to verify parallel string combiner limits |
| CEC Weighted Efficiency | 96.82% | Calculated AC/DC conversion ratio from CEC test protocol |
| CEC Listing Date & Hybrid | 2018-10-15 / Hybrid: No (Grid-Tied PV) | Utility interconnection approval metadata |
What Switchgear Limits Apply to ABB: PVI-6000-OUTD-US-A {277V} (480Y/277 V, 3-phase)?
Panelboard and switchgear backfeed allowances for ABB: PVI-6000-OUTD-US-A {277V} (15 A OCPD). Review related calculators, peer benchmarks, and source citations below to validate design assumptions for your electrical service.
| Switchboard / Interconnect | 120% Max Backfeed | Required PV OCPD | Compliance Verdict |
|---|---|---|---|
| 200A Bus / 200A Main (277V) | 40 A | 15 A | PASS (120% Commercial Busbar) |
| 400A Bus / 400A Main (277V) | 80 A | 15 A | PASS (120% Commercial Busbar) |
| 600A Bus / 600A Main (277V) | 120 A | 15 A | PASS (120% Commercial Busbar) |
| 800A Bus / 800A Main (277V) | 160 A | 15 A | PASS (120% Commercial Busbar) |
| 1,200A Bus / 1,200A Main (277V) | 240 A | 15 A | PASS (120% Commercial Busbar) |
Which CEC PV Module Strings Pair With ABB: PVI-6000-OUTD-US-A {277V}?
Representative PV panel pairings verified under NEC 690.7 cold Voc for ABB: PVI-6000-OUTD-US-A {277V}. Every reported metric links directly to federal public records or state regulatory filings with zero paid contractor placements.
| CEC Module | STC (W) | -10 C Voc | Valid String Range | Max String DC |
|---|---|---|---|---|
| AXITEC AC-590TGB/144TS | 590.0 W | 56.24 V | 3 to 8 panels | 4.72 kW |
| Aptos Solar Technology LLC DNA-108-MFN10-440W | 440.0 W | 42.15 V | 3 to 11 panels | 4.84 kW |
| Boviet Solar Technology Co Ltd BVM7610M-425-H-HC-BF | 425.0 W | 44.75 V | 3 to 10 panels | 4.25 kW |
| CSI Solar Co Ltd CS6P-200P | 200.0 W | 40.6 V | 4 to 11 panels | 2.2 kW |
Which Competing Grid-Support Inverters Compare to ABB: PVI-6000-OUTD-US-A {277V}?
Four alternative CEC inverters matched to ABB: PVI-6000-OUTD-US-A {277V} (6,000 W AC), led by Shenzhen Growatt New Energy Co Ltd: GROWATT 6000MTLP-US {277V}.
| Alternative Inverter | AC Output | Delta | Vac | Max DC | CEC Eff |
|---|---|---|---|---|---|
| Shenzhen Growatt New Energy Co Ltd: GROWATT 6000MTLP-US {277V} Shenzhen Growatt New Energy Co Ltd |
6,080 W | +80 W | 277.0 V | 550.0 V | 97.0% |
| Shenzhen Growatt New Energy Co Ltd: GROWATT 5000MTLP-US {277V} Shenzhen Growatt New Energy Co Ltd |
5,060 W | -940 W | 277.0 V | 550.0 V | 97.1% |
| Shenzhen Growatt New Energy Co Ltd: GROWATT 7000MTLP-US {277V} Shenzhen Growatt New Energy Co Ltd |
7,016 W | +1016 W | 277.0 V | 480.0 V | 96.5% |
| Shenzhen Growatt New Energy Co Ltd: GROWATT 4000MTLP-US {277V} Shenzhen Growatt New Energy Co Ltd |
4,060 W | -1940 W | 277.0 V | 550.0 V | 97.23% |
What Are the Interconnection Limits and Best-Fit Uses for ABB: PVI-6000-OUTD-US-A {277V}?
Check ABB: PVI-6000-OUTD-US-A {277V} (6,000 W AC, 15 A OCPD) against your main panel busbar, winter string Voc, and IEEE 1547 outage rules.
- Anti-islanding shutdown: grid-tied inverters shut off within 2 seconds during blackouts under IEEE 1547 unless paired with a battery microgrid interconnect.
- Busbar 120% limit: Commercial 480Y/277 V, 3-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (277V) or NEC 705.11 supply-side tap.
- Cold Voc hard ceiling: never allow winter open-circuit PV string voltage to exceed 480 V DC on ABB: PVI-6000-OUTD-US-A {277V}.
ABB: PVI-6000-OUTD-US-A {277V} Panel & Wire Spec
Size 75 C copper conductors at 14 AWG Cu on a 15 A OCPD breaker (7.2 A continuous).
Alternative Inverter Comparison
Compare efficiency (96.82%) and MPPT window (100-480 V) directly against Shenzhen Growatt New Energy Co Ltd: GROWATT 6000MTLP-US {277V} (6,080 W).
Which Homeowner Electrical & Solar Questions Come Up Most Often?
Answers for ABB: PVI-6000-OUTD-US-A {277V} by ABB covering breaker sizing, MPPT limits, and 480Y/277 V, 3-phase interconnection.
What breaker and wire size does ABB: PVI-6000-OUTD-US-A {277V} require?
At 6,000 W continuous AC (480Y/277 V, 3-phase), continuous current is 7.2 A; 125% NEC 690.8/705.12 sizing requires a 15 A breaker and 14 AWG Cu (75 C) wire.
What commercial switchgear or feeder sizing does ABB: PVI-6000-OUTD-US-A {277V} require?
At 6,000 W AC and 480Y/277 V, 3-phase, continuous line current is 7.2 A, requiring a 15 A OCPD and 1,200A Bus / 1,200A Main (277V) or NEC 705.11 interconnection.
How does ABB: PVI-6000-OUTD-US-A {277V} compare to Shenzhen Growatt New Energy Co Ltd: GROWATT 6000MTLP-US {277V}?
ABB: PVI-6000-OUTD-US-A {277V} delivers 6,000 W AC at 96.82% CEC efficiency with a 480 V DC ceiling, while Shenzhen Growatt New Energy Co Ltd: GROWATT 6000MTLP-US {277V} outputs 6,080 W at 480Y/277 V, 3-phase.