Suntech Power STP285-24/Vd is a 285.0 W STC (258.6 W PTC) Multi-c-Si solar module ranking #17,598 of 21,677 CEC listings (below all-CEC median; higher than 17.3% of peers). It delivers 14.69% efficiency, 44.8 V Voc at 25 C, and 49.71 V cold Voc at -10 C (12 panels max per 600 V string).
- STC Wattage
- 285.0 W
- PTC Wattage
- 258.6 W
- Voc @ 25C
- 44.8 V
- Efficiency
- 14.69%
How Does Suntech Power STP285-24/Vd Compare Against Peer CEC Listings?
How Suntech Power Suntech Power STP285-24/Vd handles rooftop heat (258.6 W PTC), 8 kW sizing, and cold winter string voltage.
Suntech Power builds the Suntech Power STP285-24/Vd (Multi-c-Si) as a compact residential or specialty off-grid module delivering 146.9 W/m2 (5.22 percentage points below 19.91% CEC median). Compared against Gintung Energy ASEC-285G6S (285.0 W), this model holds typical 90.7% PTC-to-STC thermal output (258.6 W real-world rating). Mid-range 44.8 V open-circuit voltage allows up to 12 panels per 600 V string at 14 F, while NEC 690.8 sets a 13.06 A overcurrent floor served by a 15 A breaker.
Where Does Suntech Power STP285-24/Vd Fall Across Listed CEC Models?
Where Suntech Power STP285-24/Vd (285.0 W) sits inside the 21,677-panel CEC STC wattage curve relative to the 385.0 W median.
What Dataset Percentiles Define Suntech Power STP285-24/Vd?
Percentile placement of Suntech Power STP285-24/Vd across power density (146.9 W/m2), thermal retention, and nameplate STC wattage.
What Do the Dataset Ranks Show for Suntech Power STP285-24/Vd?
Four critical engineering numbers homeowners and solar installers check first when reviewing Suntech Power STP285-24/Vd specifications. Review related calculators, peer benchmarks, and source citations below to validate design assumptions for your electrical service.
285.0 W STC · Higher Than 17.3%
285.0 W STC (-100.0 W vs all-CEC median) vs 278.8 W Multi-c-Si median.
14.69% Aperture Efficiency
Power density 146.9 W/m2 (5.22 percentage points below 19.91% CEC median). PTC/STC ratio: 90.7% (rank #17,330).
12 Panels Max @ -10 C (600 V)
Cold Voc reaches 49.71 V at -10 C (596.5 V string) and 51.11 V at -20 C (11 max).
29 Panels = 8,265 W STC
Occupies 56.3 m2 (606 sq ft) producing 7,499 W PTC; NEC 690.8 OCPD floor is 13.06 A (15 A breaker).
NEC 690.7(A) Cold-Temperature Voc & 690.8 OCPD Formula
Voc_cold = 44.8 * (1 + (-0.313/100) * (-10 - 25)) = 49.71 V | OCPD = 1.56 * 8.37 = 13.06 A
Inputs from CEC Modules.csv for Suntech Power STP285-24/Vd: Voc=44.8 V, beta_Voc=-0.313%/C, Isc=8.37 A, STC=285.0 W, Area=1.94 m2.
Result: 12 panels max on 600 V (596.5 V); 29 panels for 8 kW (606 sq ft).
What Are the Published CEC Specifications for Suntech Power STP285-24/Vd?
Verified electrical STC and PTC ratings, open-circuit voltage, short-circuit current, and physical area published for Suntech Power STP285-24/Vd.
| Parameter | Measured / Listed Value | Engineering Significance |
|---|---|---|
| Nameplate Power (STC) | 285.0 W | Rated DC output under Standard Test Conditions (1000 W/m2, 25C cell) |
| Real-World Output (PTC) | 258.6 W (90.7% STC) | PVUSA Test Conditions rating used for utility interconnection |
| Open-Circuit Voltage (Voc) | 44.8 V | Primary cold-weather string sizing limit under NEC 690.7 |
| Short-Circuit Current (Isc) | 8.37 A | Determines 156% (1.25x1.25) OCPD fuse/breaker sizing under NEC 690.8 |
| Max Power Voltage / Current | 35.8 V / 7.95 A | Inverter MPPT operating window alignment |
| Voc Temp Coefficient (beta_Voc) | -0.313 %/C | Negative slope governing voltage rise below 25C |
| Module Efficiency & Area | 14.69% (1.94 m2) | Array roof footprint density |
| Cell Count & Technology | 72 cells (Multi-c-Si) | Monofacial backsheet |
How Many Suntech Power STP285-24/Vd Panels Build a 6 kW, 8 kW, or 10 kW Array?
Compare 6 kW, 8 kW, and 10 kW array footprints and Year-1 utility savings using Suntech Power STP285-24/Vd (285.0 W).
| Target Array | Panels | Actual DC | Roof Area | US Avg ($/yr) | CA High ($/yr) |
|---|---|---|---|---|---|
| 6 kW Class | 22 | 6.27 kW | 459 sq ft | $1,569 | $2,654 |
| 8 kW Class | 29 | 8.27 kW | 606 sq ft | $2,070 | $3,500 |
| 10 kW Class | 36 | 10.26 kW | 752 sq ft | $2,568 | $4,342 |
Which Sibling Wattage & Trim Variants Belong to This Suntech Power Series?
All closely matched Suntech Power wattages and cosmetic trims sharing the Suntech Power STP285-24/Vd architecture. Published percentiles compare local state, county, metro, and certified equipment metrics against nationwide residential electrical baselines.
| Model Variant | STC (W) | PTC (W) | Voc (V) | Vmp (V) | Eff (%) |
|---|---|---|---|---|---|
| Suntech Power STP275-24/Vd | 275.0 W | 249.3 W | 44.7 V | 35.1 V | 14.17% |
| Suntech Power STP280-24/Vd | 280.0 W | 254.0 W | 44.8 V | 35.2 V | 14.43% |
| Suntech Power STP285-24/Vd | 285.0 W | 258.6 W | 44.8 V | 35.8 V | 14.69% |
| Suntech Power STP290-24/Vd | 290.0 W | 263.3 W | 44.8 V | 36.5 V | 14.95% |
| Suntech Power STP295-24/Vd | 295.0 W | 267.2 W | 44.9 V | 36.8 V | 15.2% |
How Many Suntech Power STP285-24/Vd Modules Fit in a Cold-Weather String?
Maximum series module counts for Suntech Power STP285-24/Vd from 25 C down to -20 C (-4 F) under NEC 690.7.
| Ambient Min Temp | Cold Voc / Panel | Max Panels (600 V) | 600 V String Voc | Max Panels (1000 V) |
|---|---|---|---|---|
| -20 C (-4 F) | 51.11 V | 11 panels | 562.2 V | 19 panels |
| -10 C (14 F) | 49.71 V | 12 panels | 596.5 V | 20 panels |
| 0 C (32 F) | 48.31 V | 12 panels | 579.7 V | 20 panels |
| 25 C (77 F STC) | 44.8 V | 13 panels | 582.4 V | 22 panels |
Which Cross-Brand Solar Modules Compare Closest to Suntech Power STP285-24/Vd?
Alternative CEC solar modules from competing brands near Suntech Power STP285-24/Vd (285.0 W), including Gintung Energy ASEC-285G6S.
| Alternative Module | STC (W) | Delta vs This | Voc (V) | Eff (%) | PTC/STC |
|---|---|---|---|---|---|
| Gintung Energy ASEC-285G6S Gintung Energy |
285.0 W | Tie (0 W) | 44.69 V | 14.57% | 89.7% |
| Gintung Energy ASEC-285G6M Gintung Energy |
285.0 W | Tie (0 W) | 44.53 V | 14.57% | 89.5% |
| AXITEC AC-285P/156-72S AXITEC |
285.0 W | Tie (0 W) | 44.51 V | 14.72% | 90.0% |
| Centrosolar America DP72 285 Centrosolar America |
285.0 W | Tie (0 W) | 44.32 V | 14.66% | 88.5% |
What Are the Design Limits and Best-Fit Uses for Suntech Power STP285-24/Vd?
Evaluate Suntech Power STP285-24/Vd (285.0 W STC, 44.8 V Voc) against your roof geometry, winter climate, and inverter voltage ceiling before finalizing bids.
- Winter overvoltage boundary: at -20 C (-4 F), Suntech Power STP285-24/Vd reaches 51.11 V per panel—exceeding 11 panels in series voids 600 V inverter warranties.
- Footprint constraint: 29 panels for an 8 kW build require 606 sq ft of unshaded roof plane — useful on tight dormer roofs or battery cabins, though 8 kW requires 29 panels (606 sq ft).
- 2026 tax credit baseline: cash residential installs of Suntech Power STP285-24/Vd carry 0% federal 25D credit after 2025-12-31, making 18.54 c/kWh+ utility avoidance key.
Suntech Power STP285-24/Vd 8 kW Residential Fit
Needs 29 modules (606 sq ft) with a 15 A string OCPD, offsetting ~$2,070/yr at US average tariffs.
Cold-Climate String Design (-10 C / -20 C)
Cap 600 V series strings at 12 panels (-10 C) or 11 panels (-20 C), or compare Gintung Energy ASEC-285G6S.
Bifacial / High-Heat Roof Check
Monofacial backsheet sealing targets flush dark shingle rooftop mounts. Real-world output tracks 258.6 W PTC.
Which Homeowner Electrical & Solar Questions Come Up Most Often?
Technical answers for Suntech Power STP285-24/Vd by Suntech Power grounded in CEC test data and NEC 690.7/690.8 limits.
What fuse or breaker size does NEC 690.8 require for Suntech Power STP285-24/Vd?
Multiplying Suntech Power STP285-24/Vd's 8.37 A short-circuit current by 1.56 equals 13.06 A minimum ampacity, requiring at least a 15 A overcurrent fuse or breaker.
Can Suntech Power STP285-24/Vd pair with microinverters instead of a 600 V string inverter?
Yes—if the microinverter DC input ceiling exceeds 49.71 V cold Voc at 14 F and handles 8.37 A Isc; string inverters cap Suntech Power STP285-24/Vd at 12 panels on 600 V.
Is Suntech Power STP285-24/Vd eligible for the 30% federal 25D solar credit in 2026?
No. Federal Section 25D expired December 31, 2025 under Public Law 119-21, so 2026 cash installs of Suntech Power STP285-24/Vd rely on utility bill offset (~$2,070/yr at 8 kW) rather than 25D.
Sources
- CEC Solar Equipment List — PV Modules (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
- NFPA 70 National Electrical Code (Section Numbers & Standard Engineering Tables Only) — National Fire Protection Association (NFPA), 2020 / 2023 / 2026 Editions (retrieved 2026-11-23)