JA Solar JAP6-60-280/4BB/RE is a 280.0 W STC (256.7 W PTC) Multi-c-Si solar module ranking #17,941 of 21,677 CEC listings (below all-CEC median; higher than 15.8% of peers). It delivers 17.12% efficiency, 38.85 V Voc at 25 C, and 42.94 V cold Voc at -10 C (13 panels max per 600 V string).
- STC Wattage
- 280.0 W
- PTC Wattage
- 256.7 W
- Voc @ 25C
- 38.85 V
- Efficiency
- 17.12%
How Does JA Solar JAP6-60-280/4BB/RE Compare Against Peer CEC Listings?
CEC rank, roof space requirements, and NEC 690.7/690.8 limits for JA Solar JAP6-60-280/4BB/RE (Multi-c-Si) residential solar systems.
Homeowners evaluating JA Solar JAP6-60-280/4BB/RE need 22 panels for 6 kW or 29 panels (510 sq ft) for an 8 kW array—useful on tight dormer roofs or battery cabins, though 8 kW requires 29 panels (510 sq ft). Under NEC 690.7(A), beta_Voc (-0.301%/C) pushes open-circuit voltage to 42.94 V at 14 F and 44.11 V at -4 F. Monofacial backsheet sealing targets flush dark shingle rooftop mounts.
Where Does JA Solar JAP6-60-280/4BB/RE Fall Across Listed CEC Models?
Comparison of JA Solar JAP6-60-280/4BB/RE (280.0 W STC) against all 21,677 California Energy Commission certified photovoltaic modules.
What Dataset Percentiles Define JA Solar JAP6-60-280/4BB/RE?
Relative ranking of JA Solar JAP6-60-280/4BB/RE across nameplate watts, 91.7% PTC thermal ratio, and module aperture efficiency.
What Do the Dataset Ranks Show for JA Solar JAP6-60-280/4BB/RE?
Summary of JA Solar JAP6-60-280/4BB/RE output rank, 8 kW array size (29 panels), efficiency rating, and 600 V string limit.
280.0 W STC · Higher Than 15.8%
280.0 W STC (-105.0 W vs all-CEC median) vs 278.8 W Multi-c-Si median.
17.12% Aperture Efficiency
Power density 171.3 W/m2 (2.79 percentage points below 19.91% CEC median). PTC/STC ratio: 91.7% (rank #15,053).
13 Panels Max @ -10 C (600 V)
Cold Voc reaches 42.94 V at -10 C (558.2 V string) and 44.11 V at -20 C (13 max).
29 Panels = 8,120 W STC
Occupies 47.4 m2 (510 sq ft) producing 7,444 W PTC; NEC 690.8 OCPD floor is 14.55 A (15 A breaker).
NEC 690.7(A) Cold-Temperature Voc & 690.8 OCPD Formula
Voc_cold = 38.85 * (1 + (-0.301/100) * (-10 - 25)) = 42.94 V | OCPD = 1.56 * 9.33 = 14.55 A
Inputs from CEC Modules.csv for JA Solar JAP6-60-280/4BB/RE: Voc=38.85 V, beta_Voc=-0.301%/C, Isc=9.33 A, STC=280.0 W, Area=1.635 m2.
Result: 13 panels max on 600 V (558.2 V); 29 panels for 8 kW (510 sq ft).
What Are the Published CEC Specifications for JA Solar JAP6-60-280/4BB/RE?
Complete CEC test sheet for JA Solar JAP6-60-280/4BB/RE including Isc (9.33 A), Voc (38.85 V), and thermal temperature coefficients.
| Parameter | Measured / Listed Value | Engineering Significance |
|---|---|---|
| Nameplate Power (STC) | 280.0 W | Rated DC output under Standard Test Conditions (1000 W/m2, 25C cell) |
| Real-World Output (PTC) | 256.7 W (91.7% STC) | PVUSA Test Conditions rating used for utility interconnection |
| Open-Circuit Voltage (Voc) | 38.85 V | Primary cold-weather string sizing limit under NEC 690.7 |
| Short-Circuit Current (Isc) | 9.33 A | Determines 156% (1.25x1.25) OCPD fuse/breaker sizing under NEC 690.8 |
| Max Power Voltage / Current | 31.88 V / 8.78 A | Inverter MPPT operating window alignment |
| Voc Temp Coefficient (beta_Voc) | -0.301 %/C | Negative slope governing voltage rise below 25C |
| Module Efficiency & Area | 17.12% (1.635 m2) | Array roof footprint density |
| Cell Count & Technology | 60 cells (Multi-c-Si) | Monofacial backsheet |
How Many JA Solar JAP6-60-280/4BB/RE Panels Build a 6 kW, 8 kW, or 10 kW Array?
Residential array count and annual electric bill savings at 18.54 c/kWh US avg vs. California tariffs using JA Solar JAP6-60-280/4BB/RE.
| Target Array | Panels | Actual DC | Roof Area | US Avg ($/yr) | CA High ($/yr) |
|---|---|---|---|---|---|
| 6 kW Class | 22 | 6.16 kW | 387 sq ft | $1,542 | $2,607 |
| 8 kW Class | 29 | 8.12 kW | 510 sq ft | $2,032 | $3,437 |
| 10 kW Class | 36 | 10.08 kW | 634 sq ft | $2,523 | $4,266 |
Which Sibling Wattage & Trim Variants Belong to This JA Solar Series?
Related JA Solar power steps and black/silver trims consolidated into this JA Solar JAP6-60-280/4BB/RE series guide.
| Model Variant | STC (W) | PTC (W) | Voc (V) | Vmp (V) | Eff (%) |
|---|---|---|---|---|---|
| JA Solar JAP6-60-275/4BB/RE | 275.0 W | 252.0 W | 38.46 V | 31.54 V | 16.82% |
| JA Solar JAP6-60-280/4BB/RE | 280.0 W | 256.7 W | 38.85 V | 31.88 V | 17.12% |
How Many JA Solar JAP6-60-280/4BB/RE Modules Fit in a Cold-Weather String?
Verify freezing-morning voltage rise for JA Solar JAP6-60-280/4BB/RE (38.85 V STC) before wiring 600 V or 1,000 V strings.
| Ambient Min Temp | Cold Voc / Panel | Max Panels (600 V) | 600 V String Voc | Max Panels (1000 V) |
|---|---|---|---|---|
| -20 C (-4 F) | 44.11 V | 13 panels | 573.4 V | 22 panels |
| -10 C (14 F) | 42.94 V | 13 panels | 558.2 V | 23 panels |
| 0 C (32 F) | 41.77 V | 14 panels | 584.8 V | 23 panels |
| 25 C (77 F STC) | 38.85 V | 15 panels | 582.8 V | 25 panels |
Which Cross-Brand Solar Modules Compare Closest to JA Solar JAP6-60-280/4BB/RE?
Four comparable CEC modules such as Centrosolar America TM6 280xx (280.0 W) for side-by-side solar quote checks. Regional housing vintage, storm hazard frequency, and wholesale utility prices directly govern residential upgrade payback across jurisdictions.
| Alternative Module | STC (W) | Delta vs This | Voc (V) | Eff (%) | PTC/STC |
|---|---|---|---|---|---|
| Centrosolar America TM6 280xx Centrosolar America |
280.0 W | Tie (0 W) | 38.7 V | 17.14% | 90.6% |
| Centrosolar America TM6S 280xx Centrosolar America |
280.0 W | Tie (0 W) | 38.7 V | 17.14% | 90.6% |
| GCL System Integration Technology Co Ltd GCL-M6/60280 GCL System Integration Technology Co Ltd |
280.0 W | Tie (0 W) | 38.7 V | 17.18% | 90.1% |
| GCL System Integration Technology Co Ltd GCL-P6/60280 GCL System Integration Technology Co Ltd |
280.0 W | Tie (0 W) | 38.7 V | 17.18% | 90.6% |
What Are the Design Limits and Best-Fit Uses for JA Solar JAP6-60-280/4BB/RE?
Evaluate JA Solar JAP6-60-280/4BB/RE (280.0 W STC, 38.85 V Voc) against your roof geometry, winter climate, and inverter voltage ceiling before finalizing bids.
- Winter overvoltage boundary: at -20 C (-4 F), JA Solar JAP6-60-280/4BB/RE reaches 44.11 V per panel—exceeding 13 panels in series voids 600 V inverter warranties.
- Footprint constraint: 29 panels for an 8 kW build require 510 sq ft of unshaded roof plane — useful on tight dormer roofs or battery cabins, though 8 kW requires 29 panels (510 sq ft).
- 2026 tax credit baseline: cash residential installs of JA Solar JAP6-60-280/4BB/RE carry 0% federal 25D credit after 2025-12-31, making 18.54 c/kWh+ utility avoidance key.
JA Solar JAP6-60-280/4BB/RE 8 kW Residential Fit
Needs 29 modules (510 sq ft) with a 15 A string OCPD, offsetting ~$2,032/yr at US average tariffs.
Cold-Climate String Design (-10 C / -20 C)
Cap 600 V series strings at 13 panels (-10 C) or 13 panels (-20 C), or compare Centrosolar America TM6 280xx.
Bifacial / High-Heat Roof Check
Monofacial backsheet sealing targets flush dark shingle rooftop mounts. Real-world output tracks 256.7 W PTC.
Which Homeowner Electrical & Solar Questions Come Up Most Often?
Technical answers for JA Solar JAP6-60-280/4BB/RE by JA Solar grounded in CEC test data and NEC 690.7/690.8 limits.
Why is JA Solar JAP6-60-280/4BB/RE PTC wattage (256.7 W) lower than STC (280.0 W)?
Laboratory STC tests at 25 C cell temperature, whereas real rooftop heat lowers voltage to 256.7 W PTC (91.7% retention) across JA Solar JAP6-60-280/4BB/RE's 1.635 m2 aperture.
Who should skip JA Solar JAP6-60-280/4BB/RE on a complex residential roof?
Homes with chopped dormers or heavy chimney shade should compare smaller modules or microinverters if 29 JA Solar JAP6-60-280/4BB/RE panels (510 sq ft) leave unusable roof gaps vs. Centrosolar America TM6 280xx.
What is the 1,000 V commercial string limit for JA Solar JAP6-60-280/4BB/RE?
On 1,000 V commercial inverters at -10 C (42.94 V cold Voc), JA Solar JAP6-60-280/4BB/RE fits up to 23 panels per series string.
Sources
- CEC Solar Equipment List — PV Modules (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
- NFPA 70 National Electrical Code (Section Numbers & Standard Engineering Tables Only) — National Fire Protection Association (NFPA), 2020 / 2023 / 2026 Editions (retrieved 2026-11-23)