First Solar Inc FS-3100-Plus is a 100.0 W STC (94.8 W PTC) Thin Film solar module ranking #21,563 of 21,677 CEC listings (below all-CEC median; higher than 0.5% of peers). It delivers 13.89% efficiency, 58.8 V Voc at 25 C, and 63.94 V cold Voc at -10 C (9 panels max per 600 V string).
- STC Wattage
- 100.0 W
- PTC Wattage
- 94.8 W
- Voc @ 25C
- 58.8 V
- Efficiency
- 13.89%
How Does First Solar Inc FS-3100-Plus Compare Against Peer CEC Listings?
How First Solar Inc First Solar Inc FS-3100-Plus handles rooftop heat (94.8 W PTC), 8 kW sizing, and cold winter string voltage.
For NEC string engineering, First Solar Inc FS-3100-Plus exhibits 2.33 A short-circuit current, requiring a 3.63 A (156%) conductor rating and 15 A OCPD under NEC 690.8. Ranked #21,563 of 21,677 (17.5 W below the 117.5 W Thin Film median), this compact residential or specialty off-grid module covers 57.6 m2 for an 8 kW system (100 panels for 10 kW). Higher 58.8 V open-circuit voltage caps 600 V residential strings at 9 panels at 14 F (-10 C).
Where Does First Solar Inc FS-3100-Plus Fall Across Listed CEC Models?
Where First Solar Inc FS-3100-Plus (100.0 W) sits inside the 21,677-panel CEC STC wattage curve relative to the 385.0 W median.
What Dataset Percentiles Define First Solar Inc FS-3100-Plus?
Percentile placement of First Solar Inc FS-3100-Plus across power density (138.9 W/m2), thermal retention, and nameplate STC wattage.
What Do the Dataset Ranks Show for First Solar Inc FS-3100-Plus?
Four critical engineering numbers homeowners and solar installers check first when reviewing First Solar Inc FS-3100-Plus specifications. Inspect manufacturer nameplate documentation, UL listing boundaries, and utility rate schedules closely before ordering electrical hardware.
100.0 W STC · Higher Than 0.5%
100.0 W STC (-285.0 W vs all-CEC median) vs 117.5 W Thin Film median.
13.89% Aperture Efficiency
Power density 138.9 W/m2 (6.02 percentage points below 19.91% CEC median). PTC/STC ratio: 94.8% (rank #1,790).
9 Panels Max @ -10 C (600 V)
Cold Voc reaches 63.94 V at -10 C (575.5 V string) and 65.42 V at -20 C (9 max).
80 Panels = 8,000 W STC
Occupies 57.6 m2 (620 sq ft) producing 7,584 W PTC; NEC 690.8 OCPD floor is 3.63 A (15 A breaker).
NEC 690.7(A) Cold-Temperature Voc & 690.8 OCPD Formula
Voc_cold = 58.8 * (1 + (-0.25/100) * (-10 - 25)) = 63.94 V | OCPD = 1.56 * 2.33 = 3.63 A
Inputs from CEC Modules.csv for First Solar Inc FS-3100-Plus: Voc=58.8 V, beta_Voc=-0.25%/C, Isc=2.33 A, STC=100.0 W, Area=0.72 m2.
Result: 9 panels max on 600 V (575.5 V); 80 panels for 8 kW (620 sq ft).
What Are the Published CEC Specifications for First Solar Inc FS-3100-Plus?
Verified electrical STC and PTC ratings, open-circuit voltage, short-circuit current, and physical area published for First Solar Inc FS-3100-Plus.
| Parameter | Measured / Listed Value | Engineering Significance |
|---|---|---|
| Nameplate Power (STC) | 100.0 W | Rated DC output under Standard Test Conditions (1000 W/m2, 25C cell) |
| Real-World Output (PTC) | 94.8 W (94.8% STC) | PVUSA Test Conditions rating used for utility interconnection |
| Open-Circuit Voltage (Voc) | 58.8 V | Primary cold-weather string sizing limit under NEC 690.7 |
| Short-Circuit Current (Isc) | 2.33 A | Determines 156% (1.25x1.25) OCPD fuse/breaker sizing under NEC 690.8 |
| Max Power Voltage / Current | 46.8 V / 2.14 A | Inverter MPPT operating window alignment |
| Voc Temp Coefficient (beta_Voc) | -0.25 %/C | Negative slope governing voltage rise below 25C |
| Module Efficiency & Area | 13.89% (0.72 m2) | Array roof footprint density |
| Cell Count & Technology | 146 cells (Thin Film) | Monofacial backsheet |
How Many First Solar Inc FS-3100-Plus Panels Build a 6 kW, 8 kW, or 10 kW Array?
Compare 6 kW, 8 kW, and 10 kW array footprints and Year-1 utility savings using First Solar Inc FS-3100-Plus (100.0 W).
| Target Array | Panels | Actual DC | Roof Area | US Avg ($/yr) | CA High ($/yr) |
|---|---|---|---|---|---|
| 6 kW Class | 60 | 6.0 kW | 465 sq ft | $1,502 | $2,539 |
| 8 kW Class | 80 | 8.0 kW | 620 sq ft | $2,002 | $3,386 |
| 10 kW Class | 100 | 10.0 kW | 775 sq ft | $2,503 | $4,232 |
How Many First Solar Inc FS-3100-Plus Modules Fit in a Cold-Weather String?
Maximum series module counts for First Solar Inc FS-3100-Plus from 25 C down to -20 C (-4 F) under NEC 690.7.
| Ambient Min Temp | Cold Voc / Panel | Max Panels (600 V) | 600 V String Voc | Max Panels (1000 V) |
|---|---|---|---|---|
| -20 C (-4 F) | 65.42 V | 9 panels | 588.8 V | 15 panels |
| -10 C (14 F) | 63.94 V | 9 panels | 575.5 V | 15 panels |
| 0 C (32 F) | 62.47 V | 9 panels | 562.2 V | 16 panels |
| 25 C (77 F STC) | 58.8 V | 10 panels | 588.0 V | 17 panels |
Which Cross-Brand Solar Modules Compare Closest to First Solar Inc FS-3100-Plus?
Alternative CEC solar modules from competing brands near First Solar Inc FS-3100-Plus (100.0 W), including Zhongshan Ruike New Energy Co Ltd RK-105-2.
| Alternative Module | STC (W) | Delta vs This | Voc (V) | Eff (%) | PTC/STC |
|---|---|---|---|---|---|
| Zhongshan Ruike New Energy Co Ltd RK-105-2 Zhongshan Ruike New Energy Co Ltd |
105.0 W | +5.0 W | 59.1 V | 14.58% | 94.4% |
| Zhongshan Ruike New Energy Co Ltd RK-75-2 Zhongshan Ruike New Energy Co Ltd |
75.0 W | -25.0 W | 58.5 V | 10.42% | 93.9% |
| Centrosolar America VS-140C1 Centrosolar America |
140.0 W | +40.0 W | 60.6 V | 12.89% | 92.7% |
| Miasole FLEX-03 120N Miasole |
115.1 W | +15.1 W | 37.8 V | 12.82% | 90.9% |
What Are the Design Limits and Best-Fit Uses for First Solar Inc FS-3100-Plus?
Evaluate First Solar Inc FS-3100-Plus (100.0 W STC, 58.8 V Voc) against your roof geometry, winter climate, and inverter voltage ceiling before finalizing bids.
- Winter overvoltage boundary: at -20 C (-4 F), First Solar Inc FS-3100-Plus reaches 65.42 V per panel—exceeding 9 panels in series voids 600 V inverter warranties.
- Footprint constraint: 80 panels for an 8 kW build require 620 sq ft of unshaded roof plane — useful on tight dormer roofs or battery cabins, though 8 kW requires 80 panels (620 sq ft).
- 2026 tax credit baseline: cash residential installs of First Solar Inc FS-3100-Plus carry 0% federal 25D credit after 2025-12-31, making 18.54 c/kWh+ utility avoidance key.
First Solar Inc FS-3100-Plus 8 kW Residential Fit
Needs 80 modules (620 sq ft) with a 15 A string OCPD, offsetting ~$2,002/yr at US average tariffs.
Cold-Climate String Design (-10 C / -20 C)
Cap 600 V series strings at 9 panels (-10 C) or 9 panels (-20 C), or compare Zhongshan Ruike New Energy Co Ltd RK-105-2.
Bifacial / High-Heat Roof Check
Monofacial backsheet sealing targets flush dark shingle rooftop mounts. Real-world output tracks 94.8 W PTC.
Which Homeowner Electrical & Solar Questions Come Up Most Often?
Technical answers for First Solar Inc FS-3100-Plus by First Solar Inc grounded in CEC test data and NEC 690.7/690.8 limits.
Why is First Solar Inc FS-3100-Plus PTC wattage (94.8 W) lower than STC (100.0 W)?
Laboratory STC tests at 25 C cell temperature, whereas real rooftop heat lowers voltage to 94.8 W PTC (94.8% retention) across First Solar Inc FS-3100-Plus's 0.72 m2 aperture.
Who should skip First Solar Inc FS-3100-Plus on a complex residential roof?
Homes with chopped dormers or heavy chimney shade should compare smaller modules or microinverters if 80 First Solar Inc FS-3100-Plus panels (620 sq ft) leave unusable roof gaps vs. Zhongshan Ruike New Energy Co Ltd RK-105-2.
What is the 1,000 V commercial string limit for First Solar Inc FS-3100-Plus?
On 1,000 V commercial inverters at -10 C (63.94 V cold Voc), First Solar Inc FS-3100-Plus fits up to 15 panels per series string. Review current municipal Authority Having Jurisdiction (AHJ) code amendments affecting First Solar Inc FS-3100-Plus.
Sources
- CEC Solar Equipment List — PV Modules (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
- NFPA 70 National Electrical Code (Section Numbers & Standard Engineering Tables Only) — National Fire Protection Association (NFPA), 2020 / 2023 / 2026 Editions (retrieved 2026-11-23)