Yaskawa Solectria Solar: XGI 1500 250/250-600 {600V} outputs 250,000 W AC at 600 V, 3-phase (240.6 A continuous, 400 A OCPD), ranking #290 of 2,343 CEC inverters at 98.11% efficiency with a 860-1,250 V MPPT window and 1,250 V DC limit. All figures reconcile directly against federal energy archives, state electrical licensing boards, California Energy Commission datasheets, and National Electrical Code engineering constants.
- AC Output (Paco)
- 250,000 W
- AC Voltage
- 600 V, 3-phase
- Min PV Breaker
- 400 A (parallel Cu feeders)
- CEC Efficiency
- 98.11%
How Does Yaskawa Solectria Solar: XGI 1500 250/250-600 {600V} Compare Against Peer CEC Listings?
Breaker sizing (400 A), parallel Cu feeders wire rules, and DC input limits for Yaskawa Solectria Solar: XGI 1500 250/250-600 {600V}.
Classified as a grid-tied PV inverter (active in CEC directory), Yaskawa Solectria Solar: XGI 1500 250/250-600 {600V} requires 300.8 A design capacity -> 400 A breaker using parallel Cu feeders copper at 75 C terminals. Weighted efficiency sits at 98.11% (+1.29 pts vs overall CEC median) across 2,343 CEC models, while commercial 600 v, 3-phase switchgear interconnection uses 1,200a bus / 1,200a main (600v) or nec 705.11 supply-side tap.
Where Does Yaskawa Solectria Solar: XGI 1500 250/250-600 {600V} Fall Across Listed CEC Models?
Output power comparison showing where Yaskawa Solectria Solar: XGI 1500 250/250-600 {600V} sits among all 2,343 CEC-listed grid-support inverters.
What Dataset Percentiles Define Yaskawa Solectria Solar: XGI 1500 250/250-600 {600V}?
Relative ranking of Yaskawa Solectria Solar: XGI 1500 250/250-600 {600V} on continuous AC power, CEC weighted efficiency, and OCPD breaker current.
What Do the Dataset Ranks Show for Yaskawa Solectria Solar: XGI 1500 250/250-600 {600V}?
Snapshot of Yaskawa Solectria Solar: XGI 1500 250/250-600 {600V} efficiency rank (#290), OCPD breaker size, MPPT span, and busbar verdict.
98.11% CEC Weighted Efficiency
-0.17 pts vs the 98.28% 600 V median; overall power rank #226 (250,000 W, top 9.8%; higher than 90.2% of peers).
400 A Required Backfeed OCPD
125% x 240.6 A = 300.8 A -> 400 A standard OCPD using parallel Cu feeders (75 C).
860 V - 1,250 V (Max 1,250 V DC)
Tracking span of 390.0 V; active in CEC directory (grid-tied PV inverter).
Supply-Side Tap (705.11) / Dedicated Switchboard
Evaluated for 600 V, 3-phase switchgear (200A Bus / 200A Main (600V) to 1,200A Bus / 1,200A Main (600V)) under NEC 705.12 / 705.11.
NEC 705.12 Backfeed OCPD & 120% Busbar Formula
I_cont = 250000.0W / 600 V 3-phase -> 240.6 A | Breaker >= 1.25 * 240.6 = 300.8 A -> 400 A
CEC Inverters.csv for Yaskawa Solectria Solar: XGI 1500 250/250-600 {600V}: Paco=250000.0 W, Vac=600 V, Vdcmax=1250.0 V, Eff=98.11%.
Result: Min 400 A breaker & parallel Cu feeders (75 C); 1,200A Bus / 1,200A Main (600V): Supply-Side Tap (705.11) / Dedicated Switchboard.
What Are the Published CEC Specifications for Yaskawa Solectria Solar: XGI 1500 250/250-600 {600V}?
Complete California Energy Commission grid-support inverter ratings and hybrid battery capabilities for Yaskawa Solectria Solar: XGI 1500 250/250-600 {600V}.
| Parameter | Measured / Listed Value | Engineering Significance |
|---|---|---|
| Max Continuous AC Power (Paco) | 250,000 W | Determines required backfeed OCPD size via 125% continuous rule |
| Nominal AC Voltage (Vac) | 600 V, 3-phase | 240V split-phase residential vs. 208V/480V/MV commercial |
| Max DC Input Voltage (Vdcmax) | 1,250 V | Hard ceiling for cold-weather PV string Voc under NEC 690.7 |
| MPPT Operating Range | 860 V - 1,250 V | Optimal DC string Vmp window for full power harvest |
| Max Input DC Current (Idcmax) | 231.648 A | Used to verify parallel string combiner limits |
| CEC Weighted Efficiency | 98.11% | Calculated AC/DC conversion ratio from CEC test protocol |
| Inverter Topology | Hybrid: No (Grid-Tied PV) | CEC Solar Equipment List grid-support certification |
What Switchgear Limits Apply to Yaskawa Solectria Solar: XGI 1500 250/250-600 {600V} (600 V, 3-phase)?
NEC 705.12(B)(3)(2) backfeed compliance table for Yaskawa Solectria Solar: XGI 1500 250/250-600 {600V} at 600 V, 3-phase.
| Switchboard / Interconnect | 120% Max Backfeed | Required PV OCPD | Compliance Verdict |
|---|---|---|---|
| 200A Bus / 200A Main (600V) | 40 A | 400 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| 400A Bus / 400A Main (600V) | 80 A | 400 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| 600A Bus / 600A Main (600V) | 120 A | 400 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| 800A Bus / 800A Main (600V) | 160 A | 400 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| 1,200A Bus / 1,200A Main (600V) | 240 A | 400 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
Which CEC PV Module Strings Pair With Yaskawa Solectria Solar: XGI 1500 250/250-600 {600V}?
Minimum and maximum series solar module strings fitting Yaskawa Solectria Solar: XGI 1500 250/250-600 {600V} MPPT and 1,250 V limits.
| CEC Module | STC (W) | -10 C Voc | Valid String Range | Max String DC |
|---|---|---|---|---|
| AXITEC AC-590TGB/144TS | 590.0 W | 56.24 V | 21 to 22 panels | 12.98 kW |
| Aptos Solar Technology LLC DNA-108-MFN10-440W | 440.0 W | 42.15 V | 26 to 29 panels | 12.76 kW |
| Boviet Solar Technology Co Ltd BVM7610M-425-H-HC-BF | 425.0 W | 44.75 V | 25 to 27 panels | 11.47 kW |
| CSI Solar Co Ltd CS6P-200P | 200.0 W | 40.6 V | 30 panels (fixed) | 6.0 kW |
Which Competing Grid-Support Inverters Compare to Yaskawa Solectria Solar: XGI 1500 250/250-600 {600V}?
Peer 600 V, 3-phase CEC inverters near 250,000 W AC output such as Chint Power Systems America: SCH250K-T-US-600 {600V}.
| Alternative Inverter | AC Output | Delta | Vac | Max DC | CEC Eff |
|---|---|---|---|---|---|
| Chint Power Systems America: SCH250K-T-US-600 {600V} Chint Power Systems America |
250,000 W | Tie (0 W) | 600.0 V | 1300.0 V | 98.21% |
| SolarEdge Technologies Ltd: SE250KUS {600V} SolarEdge Technologies Ltd |
249,907 W | -93 W | 600.0 V | 1320.0 V | 98.7% |
| Ginlong Technologies Co Ltd: S6-GU250K-EHV-US-M12 {600V} Ginlong Technologies Co Ltd |
248,751 W | -1249 W | 600.0 V | 1300.0 V | 98.62% |
| SolarEdge Technologies Ltd: SE285KUS {600V} SolarEdge Technologies Ltd |
284,159 W | +34159 W | 600.0 V | 1320.0 V | 98.61% |
What Are the Interconnection Limits and Best-Fit Uses for Yaskawa Solectria Solar: XGI 1500 250/250-600 {600V}?
Check Yaskawa Solectria Solar: XGI 1500 250/250-600 {600V} (250,000 W AC, 400 A OCPD) against your main panel busbar, winter string Voc, and IEEE 1547 outage rules.
- Anti-islanding shutdown: grid-tied inverters shut off within 2 seconds during blackouts under IEEE 1547 unless paired with a battery microgrid interconnect.
- Busbar 120% limit: Commercial 600 V, 3-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (600V) or NEC 705.11 supply-side tap.
- Cold Voc hard ceiling: never allow winter open-circuit PV string voltage to exceed 1,250 V DC on Yaskawa Solectria Solar: XGI 1500 250/250-600 {600V}.
Yaskawa Solectria Solar: XGI 1500 250/250-600 {600V} Panel & Wire Spec
Size 75 C copper conductors at parallel Cu feeders on a 400 A OCPD breaker (240.6 A continuous).
Alternative Inverter Comparison
Compare efficiency (98.11%) and MPPT window (860-1,250 V) directly against Chint Power Systems America: SCH250K-T-US-600 {600V} (250,000 W).
Which Homeowner Electrical & Solar Questions Come Up Most Often?
Answers for Yaskawa Solectria Solar: XGI 1500 250/250-600 {600V} by Yaskawa Solectria Solar covering breaker sizing, MPPT limits, and 600 V, 3-phase interconnection.
What breaker and wire size does Yaskawa Solectria Solar: XGI 1500 250/250-600 {600V} require?
At 250,000 W continuous AC (600 V, 3-phase), continuous current is 240.6 A; 125% NEC 690.8/705.12 sizing requires a 400 A breaker and parallel Cu feeders (75 C) wire.
What commercial switchgear or feeder sizing does Yaskawa Solectria Solar: XGI 1500 250/250-600 {600V} require?
At 250,000 W AC and 600 V, 3-phase, continuous line current is 240.6 A, requiring a 400 A OCPD and 1,200A Bus / 1,200A Main (600V) or NEC 705.11 interconnection.
How does Yaskawa Solectria Solar: XGI 1500 250/250-600 {600V} compare to Chint Power Systems America: SCH250K-T-US-600 {600V}?
Yaskawa Solectria Solar: XGI 1500 250/250-600 {600V} delivers 250,000 W AC at 98.11% CEC efficiency with a 1,250 V DC ceiling, while Chint Power Systems America: SCH250K-T-US-600 {600V} outputs 250,000 W at 600 V, 3-phase.
Sources
- CEC Solar Equipment List — Grid-Support Inverters (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
- CEC Solar Equipment List — PV Modules (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
- NFPA 70 National Electrical Code (Section Numbers & Standard Engineering Tables Only) — National Fire Protection Association (NFPA), 2020 / 2023 / 2026 Editions (retrieved 2026-11-23)