Skip to main content
WireAndSun
Calculators
CEC Grid-Support Inverter

Yaskawa Solectria Solar: XGI 1500 200/200-480 {480V} — CEC Inverter Specifications

Manufacturer: Yaskawa Solectria Solar Registry: CEC Verified Engineering Specification

Yaskawa Solectria Solar: XGI 1500 200/200-480 {480V} outputs 200,000 W AC at 480 V, 3-phase (240.6 A continuous, 400 A OCPD), ranking #130 of 2,343 CEC inverters at 98.38% efficiency with a 860-1,250 V MPPT window and 1,250 V DC limit. All figures reconcile directly against federal energy archives, state electrical licensing boards, California Energy Commission datasheets, and National Electrical Code engineering constants.

AC Output (Paco)
200,000 W
AC Voltage
480 V, 3-phase
Min PV Breaker
400 A (parallel Cu feeders)
CEC Efficiency
98.38%
Wall-mounted residential hybrid solar inverter and modular battery cabinet piped with galvanized EMT conduit
Wall-mounted residential hybrid solar inverter and modular battery cabinet piped with galvanized EMT conduit

How Does Yaskawa Solectria Solar: XGI 1500 200/200-480 {480V} Compare Against Peer CEC Listings?

NEC 705.12 breaker requirements, efficiency placement, and 480 V, 3-phase grid-support overview for Yaskawa Solectria Solar: XGI 1500 200/200-480 {480V}.

Ranking #247 of 2,343 CEC inverters (top 10.7%; higher than 89.3% of peers), Yaskawa Solectria Solar: XGI 1500 200/200-480 {480V} is a grid-tied PV inverter delivering 200,000 W continuous AC at 480 V, 3-phase (240.6 A continuous). Commercial 480 V, 3-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (480V) or NEC 705.11 supply-side tap. Weighted CEC efficiency reaches 98.38% (+0.36 pts vs the 98.02% 480 V median) against peers like Chint Power Systems America: SCH200K-T-US-480 {480V} (200,000 W).

Where Does Yaskawa Solectria Solar: XGI 1500 200/200-480 {480V} Fall Across Listed CEC Models?

Marks Yaskawa Solectria Solar: XGI 1500 200/200-480 {480V} (200,000 W AC) across the California Energy Commission inverter AC capacity distribution.

AC Power Distribution Across Listed CEC Inverters (up to 25 kW)Shows where Yaskawa Solectria Solar: XGI 1500 200/200-480 {480V} (200,000 W AC) sits across CEC inverters. 190-2258 W AC: 584 entries1902258-4325 W AC: 158 entries4325-6392 W AC: 259 entries6392-8460 W AC: 270 entries63928460-10528 W AC: 258 entries10528-12595 W AC: 116 entries12595-14662 W AC: 17 entries1259514662-16730 W AC: 37 entries16730-18798 W AC: 7 entries18798-20865 W AC: 11 entries1879820865-22932 W AC: 5 entries22932-25000 W AC: 26 entries22932Median 7,680 W ACYaskawa Solectria : 200,000 W

What Dataset Percentiles Define Yaskawa Solectria Solar: XGI 1500 200/200-480 {480V}?

Benchmarks Yaskawa Solectria Solar: XGI 1500 200/200-480 {480V} continuous AC output, 98.38% CEC weighted efficiency, and 400 A OCPD breaker demand.

Yaskawa Solectria Solar: XGI 1500 200/200-480 {480V} Technical ThresholdsPercentile comparison for Yaskawa Solectria Solar: XGI 1500 200/200-480 {480V} AC output, weighted CEC efficiency, and OCPD sizing. 0% (Low)50% Median100% (Top)Rated AC Output200,000 WCEC Efficiency98.38%Backfeed Breaker400 A

What Do the Dataset Ranks Show for Yaskawa Solectria Solar: XGI 1500 200/200-480 {480V}?

Four key NEC 705.12 and California Energy Commission metrics defining Yaskawa Solectria Solar: XGI 1500 200/200-480 {480V} by Yaskawa Solectria Solar.

Eff #130 / 2,343

98.38% CEC Weighted Efficiency

+0.36 pts vs the 98.02% 480 V median; overall power rank #247 (200,000 W, top 10.7%; higher than 89.3% of peers).

NEC 705.12 Check

400 A Required Backfeed OCPD

125% x 240.6 A = 300.8 A -> 400 A standard OCPD using parallel Cu feeders (75 C).

MPPT Window

860 V - 1,250 V (Max 1,250 V DC)

Tracking span of 390.0 V; active in CEC directory (grid-tied PV inverter).

Commercial / 3-Phase Fit

Supply-Side Tap (705.11) / Dedicated Switchboard

Evaluated for 480 V, 3-phase switchgear (200A Bus / 200A Main (480V) to 1,200A Bus / 1,200A Main (480V)) under NEC 705.12 / 705.11.

NEC 705.12 Backfeed OCPD & 120% Busbar Formula

I_cont = 200000.0W / 480 V 3-phase -> 240.6 A | Breaker >= 1.25 * 240.6 = 300.8 A -> 400 A

CEC Inverters.csv for Yaskawa Solectria Solar: XGI 1500 200/200-480 {480V}: Paco=200000.0 W, Vac=480 V, Vdcmax=1250.0 V, Eff=98.38%.

Result: Min 400 A breaker & parallel Cu feeders (75 C); 1,200A Bus / 1,200A Main (480V): Supply-Side Tap (705.11) / Dedicated Switchboard.

What Are the Published CEC Specifications for Yaskawa Solectria Solar: XGI 1500 200/200-480 {480V}?

Official laboratory CEC ratings, MPPT operating window, and DC voltage bounds recorded for Yaskawa Solectria Solar: XGI 1500 200/200-480 {480V}.

Official California Energy Commission (NREL SAM) test parameters for Yaskawa Solectria Solar: XGI 1500 200/200-480 {480V}.
ParameterMeasured / Listed ValueEngineering Significance
Max Continuous AC Power (Paco) 200,000 W Determines required backfeed OCPD size via 125% continuous rule
Nominal AC Voltage (Vac) 480 V, 3-phase 240V split-phase residential vs. 208V/480V/MV commercial
Max DC Input Voltage (Vdcmax) 1,250 V Hard ceiling for cold-weather PV string Voc under NEC 690.7
MPPT Operating Range 860 V - 1,250 V Optimal DC string Vmp window for full power harvest
Max Input DC Current (Idcmax) 184.821 A Used to verify parallel string combiner limits
CEC Weighted Efficiency 98.38% Calculated AC/DC conversion ratio from CEC test protocol
Inverter Topology Hybrid: No (Grid-Tied PV) CEC Solar Equipment List grid-support certification

What Switchgear Limits Apply to Yaskawa Solectria Solar: XGI 1500 200/200-480 {480V} (480 V, 3-phase)?

Evaluates Yaskawa Solectria Solar: XGI 1500 200/200-480 {480V} (400 A OCPD) across standard 100 A to 225 A busbars or commercial switchboards.

Evaluates Yaskawa Solectria Solar: XGI 1500 200/200-480 {480V} (400 A required OCPD at 480 V, 3-phase) across standard distribution busbars.
Switchboard / Interconnect120% Max BackfeedRequired PV OCPDCompliance Verdict
200A Bus / 200A Main (480V) 40 A 400 A Supply-Side Tap (705.11) / Dedicated Switchboard
400A Bus / 400A Main (480V) 80 A 400 A Supply-Side Tap (705.11) / Dedicated Switchboard
600A Bus / 600A Main (480V) 120 A 400 A Supply-Side Tap (705.11) / Dedicated Switchboard
800A Bus / 800A Main (480V) 160 A 400 A Supply-Side Tap (705.11) / Dedicated Switchboard
1,200A Bus / 1,200A Main (480V) 240 A 400 A Supply-Side Tap (705.11) / Dedicated Switchboard

Which CEC PV Module Strings Pair With Yaskawa Solectria Solar: XGI 1500 200/200-480 {480V}?

Sample PV string lengths aligned within 860-1,250 V MPPT and 1,250 V DC max at -10 C. Use these verified dataset benchmarks alongside a licensed electrician load calculation to compare residential upgrade bids with confidence.

Sampled CEC PV modules aligned within 860.0-1250.0 V MPPT and 1250.0 V max DC at -10 C.
CEC ModuleSTC (W)-10 C VocValid String RangeMax String DC
AXITEC AC-590TGB/144TS 590.0 W 56.24 V 21 to 22 panels 12.98 kW
Aptos Solar Technology LLC DNA-108-MFN10-440W 440.0 W 42.15 V 26 to 29 panels 12.76 kW
Boviet Solar Technology Co Ltd BVM7610M-425-H-HC-BF 425.0 W 44.75 V 25 to 27 panels 11.47 kW
CSI Solar Co Ltd CS6P-200P 200.0 W 40.6 V 30 panels (fixed) 6.0 kW

Which Competing Grid-Support Inverters Compare to Yaskawa Solectria Solar: XGI 1500 200/200-480 {480V}?

Competing CEC grid-support inverters near 200,000 W AC and 480 V, 3-phase, led by Chint Power Systems America: SCH200K-T-US-480 {480V}.

Alternative CEC inverters at comparable AC output power and voltage class.
Alternative InverterAC OutputDeltaVacMax DCCEC Eff
Chint Power Systems America: SCH200K-T-US-480 {480V}
Chint Power Systems America
200,000 W Tie (0 W) 480.0 V 1300.0 V 97.72%
EPC Power Corp: HY LC12/6-7 {480V}
EPC Power Corp
220,033 W +20033 W 480.0 V 600.0 V 95.51%
DYNAPOWER COMPANY LLC: MPS-250 {480V}
DYNAPOWER COMPANY LLC
248,910 W +48910 W 480.0 V 600.0 V 95.24%
DYNAPOWER COMPANY LLC: MPS-250HV {480V}
DYNAPOWER COMPANY LLC
249,619 W +49619 W 480.0 V 830.0 V 96.2%
What to Check & Best-Fit Scenarios

What Are the Interconnection Limits and Best-Fit Uses for Yaskawa Solectria Solar: XGI 1500 200/200-480 {480V}?

Check Yaskawa Solectria Solar: XGI 1500 200/200-480 {480V} (200,000 W AC, 400 A OCPD) against your main panel busbar, winter string Voc, and IEEE 1547 outage rules.

  • Anti-islanding shutdown: grid-tied inverters shut off within 2 seconds during blackouts under IEEE 1547 unless paired with a battery microgrid interconnect.
  • Busbar 120% limit: Commercial 480 V, 3-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (480V) or NEC 705.11 supply-side tap.
  • Cold Voc hard ceiling: never allow winter open-circuit PV string voltage to exceed 1,250 V DC on Yaskawa Solectria Solar: XGI 1500 200/200-480 {480V}.

Yaskawa Solectria Solar: XGI 1500 200/200-480 {480V} Panel & Wire Spec

Size 75 C copper conductors at parallel Cu feeders on a 400 A OCPD breaker (240.6 A continuous).

Alternative Inverter Comparison

Compare efficiency (98.38%) and MPPT window (860-1,250 V) directly against Chint Power Systems America: SCH200K-T-US-480 {480V} (200,000 W).

Which Homeowner Electrical & Solar Questions Come Up Most Often?

Answers for Yaskawa Solectria Solar: XGI 1500 200/200-480 {480V} by Yaskawa Solectria Solar covering breaker sizing, MPPT limits, and 480 V, 3-phase interconnection.

What breaker and wire size does Yaskawa Solectria Solar: XGI 1500 200/200-480 {480V} require?

At 200,000 W continuous AC (480 V, 3-phase), continuous current is 240.6 A; 125% NEC 690.8/705.12 sizing requires a 400 A breaker and parallel Cu feeders (75 C) wire.

What commercial switchgear or feeder sizing does Yaskawa Solectria Solar: XGI 1500 200/200-480 {480V} require?

At 200,000 W AC and 480 V, 3-phase, continuous line current is 240.6 A, requiring a 400 A OCPD and 1,200A Bus / 1,200A Main (480V) or NEC 705.11 interconnection.

How does Yaskawa Solectria Solar: XGI 1500 200/200-480 {480V} compare to Chint Power Systems America: SCH200K-T-US-480 {480V}?

Yaskawa Solectria Solar: XGI 1500 200/200-480 {480V} delivers 200,000 W AC at 98.38% CEC efficiency with a 1,250 V DC ceiling, while Chint Power Systems America: SCH200K-T-US-480 {480V} outputs 200,000 W at 480 V, 3-phase.

Sources

  1. CEC Solar Equipment List — Grid-Support Inverters (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
  2. CEC Solar Equipment List — PV Modules (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
  3. NFPA 70 National Electrical Code (Section Numbers & Standard Engineering Tables Only) — National Fire Protection Association (NFPA), 2020 / 2023 / 2026 Editions (retrieved 2026-11-23)

Which Regional Electrical & Panel Upgrade Metros Compare Closest?

Check Wiring & Solar Numbers Before Getting Quotes

Verify panel capacity for solar, electrical box space, proper wire gauge for EV chargers, and 2026 home solar payback using local utility rates.

Verify State-Licensed Electricians & Safety Recalls

Look up active state electrician licenses (TX, WA, CO, OR, DE), check local power-outage history, and inspect federal product recall notices.