WSTECH GmbH: APS800-ES-1-440-5 {440V} outputs 814,167 W AC at 440 V, 3-phase (1068.3 A continuous, 1,350 A OCPD), ranking #769 of 2,343 CEC inverters at 97.2% efficiency with a 648-1,500 V MPPT window and 1,500 V DC limit. All figures reconcile directly against federal energy archives, state electrical licensing boards, California Energy Commission datasheets, and National Electrical Code engineering constants.
- AC Output (Paco)
- 814,167 W
- AC Voltage
- 440 V, 3-phase
- Min PV Breaker
- 1,350 A (parallel Cu feeders)
- CEC Efficiency
- 97.2%
How Does WSTECH GmbH: APS800-ES-1-440-5 {440V} Compare Against Peer CEC Listings?
CEC efficiency rank (#769), 648-1,500 V MPPT tracking, and panel fit for WSTECH GmbH: APS800-ES-1-440-5 {440V}. Cross-check local Authority Having Jurisdiction amendments and serving utility net-metering terms before finalizing project sizing.
WSTECH GmbH: APS800-ES-1-440-5 {440V} from WSTECH GmbH outputs 1068.3 A continuous AC at 440 V, 3-phase (814,167 W AC, rank #177). Paired with parallel Cu feeders conductors and a 1,350 A OCPD, its 97.2% CEC efficiency compares closely with EPC Power Corp: 50-200100 {720V} (561,806 W). Keep NEC 690.7 winter string Voc below 1,500 V DC.
Where Does WSTECH GmbH: APS800-ES-1-440-5 {440V} Fall Across Listed CEC Models?
CEC inverter wattage histogram highlighting WSTECH GmbH: APS800-ES-1-440-5 {440V} at 814,167 W continuous AC output. Published percentiles compare local state, county, metro, and certified equipment metrics against nationwide residential electrical baselines.
What Dataset Percentiles Define WSTECH GmbH: APS800-ES-1-440-5 {440V}?
Dataset percentiles comparing WSTECH GmbH: APS800-ES-1-440-5 {440V} against 2,343 certified grid-support inverters nationwide. Always verify current state NEC adoption cycles, local utility interconnection tariffs, and panel busbar ratings before pulling project permits.
What Do the Dataset Ranks Show for WSTECH GmbH: APS800-ES-1-440-5 {440V}?
Engineering highlights for WSTECH GmbH: APS800-ES-1-440-5 {440V} covering efficiency, parallel Cu feeders feeder, and panel compatibility. All figures trace directly to published federal energy filings, state electrical boards, CEC datasheets, and NFPA 70 NEC tables.
97.2% CEC Weighted Efficiency
-0.27 pts vs the 97.47% 440 V median; overall power rank #177 (814,167 W, top 7.6%; higher than 92.4% of peers).
1,350 A Required Backfeed OCPD
125% x 1068.3 A = 1335.4 A -> 1,350 A standard OCPD using parallel Cu feeders (75 C).
648 V - 1,500 V (Max 1,500 V DC)
Tracking span of 852.0 V; active in CEC directory (grid-tied PV inverter).
Supply-Side Tap (705.11) / Dedicated Switchboard
Evaluated for 440 V, 3-phase switchgear (200A Bus / 200A Main (440V) to 1,200A Bus / 1,200A Main (440V)) under NEC 705.12 / 705.11.
NEC 705.12 Backfeed OCPD & 120% Busbar Formula
I_cont = 814167.0W / 440 V 3-phase -> 1068.3 A | Breaker >= 1.25 * 1068.3 = 1335.4 A -> 1,350 A
CEC Inverters.csv for WSTECH GmbH: APS800-ES-1-440-5 {440V}: Paco=814167.0 W, Vac=440 V, Vdcmax=1500.0 V, Eff=97.2%.
Result: Min 1,350 A breaker & parallel Cu feeders (75 C); 1,200A Bus / 1,200A Main (440V): Supply-Side Tap (705.11) / Dedicated Switchboard.
What Are the Published CEC Specifications for WSTECH GmbH: APS800-ES-1-440-5 {440V}?
California Energy Commission Solar Equipment List parameters for WSTECH GmbH: APS800-ES-1-440-5 {440V} (grid-tied PV inverter) interconnection. Use these verified dataset benchmarks alongside a licensed electrician load calculation to compare residential upgrade bids with confidence.
| Parameter | Measured / Listed Value | Engineering Significance |
|---|---|---|
| Max Continuous AC Power (Paco) | 814,167 W | Determines required backfeed OCPD size via 125% continuous rule |
| Nominal AC Voltage (Vac) | 440 V, 3-phase | 240V split-phase residential vs. 208V/480V/MV commercial |
| Max DC Input Voltage (Vdcmax) | 1,500 V | Hard ceiling for cold-weather PV string Voc under NEC 690.7 |
| MPPT Operating Range | 648 V - 1,500 V | Optimal DC string Vmp window for full power harvest |
| Max Input DC Current (Idcmax) | 837.619 A | Used to verify parallel string combiner limits |
| CEC Weighted Efficiency | 97.2% | Calculated AC/DC conversion ratio from CEC test protocol |
| Inverter Topology | Hybrid: No (Grid-Tied PV) | CEC Solar Equipment List grid-support certification |
What Switchgear Limits Apply to WSTECH GmbH: APS800-ES-1-440-5 {440V} (440 V, 3-phase)?
Panelboard and switchgear backfeed allowances for WSTECH GmbH: APS800-ES-1-440-5 {440V} (1,350 A OCPD). Every reported metric links directly to federal public records or state regulatory filings with zero paid contractor placements.
| Switchboard / Interconnect | 120% Max Backfeed | Required PV OCPD | Compliance Verdict |
|---|---|---|---|
| 200A Bus / 200A Main (440V) | 40 A | 1,350 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| 400A Bus / 400A Main (440V) | 80 A | 1,350 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| 600A Bus / 600A Main (440V) | 120 A | 1,350 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| 800A Bus / 800A Main (440V) | 160 A | 1,350 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| 1,200A Bus / 1,200A Main (440V) | 240 A | 1,350 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
Which CEC PV Module Strings Pair With WSTECH GmbH: APS800-ES-1-440-5 {440V}?
Representative PV panel pairings verified under NEC 690.7 cold Voc for WSTECH GmbH: APS800-ES-1-440-5 {440V}. Review related calculators, peer benchmarks, and source citations below to validate design assumptions for your electrical service.
| CEC Module | STC (W) | -10 C Voc | Valid String Range | Max String DC |
|---|---|---|---|---|
| AXITEC AC-590TGB/144TS | 590.0 W | 56.24 V | 16 to 26 panels | 15.34 kW |
| Aptos Solar Technology LLC DNA-108-MFN10-440W | 440.0 W | 42.15 V | 20 to 35 panels | 15.4 kW |
| Boviet Solar Technology Co Ltd BVM7610M-425-H-HC-BF | 425.0 W | 44.75 V | 19 to 33 panels | 14.03 kW |
| CSI Solar Co Ltd CS6P-200P | 200.0 W | 40.6 V | 23 to 36 panels | 7.2 kW |
Which Competing Grid-Support Inverters Compare to WSTECH GmbH: APS800-ES-1-440-5 {440V}?
Four alternative CEC inverters matched to WSTECH GmbH: APS800-ES-1-440-5 {440V} (814,167 W AC), led by EPC Power Corp: 50-200100 {720V}.
| Alternative Inverter | AC Output | Delta | Vac | Max DC | CEC Eff |
|---|---|---|---|---|---|
| EPC Power Corp: 50-200100 {720V} EPC Power Corp |
561,806 W | -252361 W | 720.0 V | 1500.0 V | 98.58% |
| ABB: PVS-175-TL-POWER-MODULE-1-US {800V} ABB |
179,574 W | -634593 W | 800.0 V | 1200.0 V | 97.39% |
| LS Energy Solutions LLC: PBE-6140-R61-1A0-1000 {600V} LS Energy Solutions LLC |
139,449 W | -674718 W | 600.0 V | 1350.0 V | 98.27% |
| JingTsing Technology Ltd: JTES-PCS125K-1000/480-L03C1 {480V} JingTsing Technology Ltd |
127,819 W | -686348 W | 480.0 V | 950.0 V | 98.0% |
What Are the Interconnection Limits and Best-Fit Uses for WSTECH GmbH: APS800-ES-1-440-5 {440V}?
Check WSTECH GmbH: APS800-ES-1-440-5 {440V} (814,167 W AC, 1,350 A OCPD) against your main panel busbar, winter string Voc, and IEEE 1547 outage rules.
- Anti-islanding shutdown: grid-tied inverters shut off within 2 seconds during blackouts under IEEE 1547 unless paired with a battery microgrid interconnect.
- Busbar 120% limit: Commercial 440 V, 3-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (440V) or NEC 705.11 supply-side tap.
- Cold Voc hard ceiling: never allow winter open-circuit PV string voltage to exceed 1,500 V DC on WSTECH GmbH: APS800-ES-1-440-5 {440V}.
WSTECH GmbH: APS800-ES-1-440-5 {440V} Panel & Wire Spec
Size 75 C copper conductors at parallel Cu feeders on a 1,350 A OCPD breaker (1068.3 A continuous).
Alternative Inverter Comparison
Compare efficiency (97.2%) and MPPT window (648-1,500 V) directly against EPC Power Corp: 50-200100 {720V} (561,806 W).
Which Homeowner Electrical & Solar Questions Come Up Most Often?
Answers for WSTECH GmbH: APS800-ES-1-440-5 {440V} by WSTECH GmbH covering breaker sizing, MPPT limits, and 440 V, 3-phase interconnection.
What breaker and wire size does WSTECH GmbH: APS800-ES-1-440-5 {440V} require?
At 814,167 W continuous AC (440 V, 3-phase), continuous current is 1068.3 A; 125% NEC 690.8/705.12 sizing requires a 1,350 A breaker and parallel Cu feeders (75 C) wire.
What commercial switchgear or feeder sizing does WSTECH GmbH: APS800-ES-1-440-5 {440V} require?
At 814,167 W AC and 440 V, 3-phase, continuous line current is 1068.3 A, requiring a 1,350 A OCPD and 1,200A Bus / 1,200A Main (440V) or NEC 705.11 interconnection.
How does WSTECH GmbH: APS800-ES-1-440-5 {440V} compare to EPC Power Corp: 50-200100 {720V}?
WSTECH GmbH: APS800-ES-1-440-5 {440V} delivers 814,167 W AC at 97.2% CEC efficiency with a 1,500 V DC ceiling, while EPC Power Corp: 50-200100 {720V} outputs 561,806 W at 440 V, 3-phase.
Sources
- CEC Solar Equipment List — Grid-Support Inverters (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
- CEC Solar Equipment List — PV Modules (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
- NFPA 70 National Electrical Code (Section Numbers & Standard Engineering Tables Only) — National Fire Protection Association (NFPA), 2020 / 2023 / 2026 Editions (retrieved 2026-11-23)