Tesla Inc: 1538000-xx-y {208V} outputs 6,561 W AC at 208 V, commercial single-phase (31.5 A continuous, 40 A OCPD), ranking #638 of 2,343 CEC inverters at 97.37% efficiency with a 270-480 V MPPT window and 480 V DC limit. All figures reconcile directly against federal energy archives, state electrical licensing boards, California Energy Commission datasheets, and National Electrical Code engineering constants.
- AC Output (Paco)
- 6,561 W
- AC Voltage
- 208 V, commercial single-phase
- Min PV Breaker
- 40 A (8 AWG Cu)
- CEC Efficiency
- 97.37%
How Does Tesla Inc: 1538000-xx-y {208V} Compare Against Peer CEC Listings?
Breaker sizing (40 A), 8 AWG Cu wire rules, and DC input limits for Tesla Inc: 1538000-xx-y {208V}.
Classified as a grid-tied PV inverter (listed since 2023-01-03), Tesla Inc: 1538000-xx-y {208V} requires 39.4 A design capacity -> 40 A breaker using 8 AWG Cu copper at 75 C terminals. Weighted efficiency sits at 97.37% (+0.55 pts vs overall CEC median) across 2,343 CEC models, while commercial 208 v, commercial single-phase switchgear interconnection uses 1,200a bus / 1,200a main (208v) or nec 705.11 supply-side tap.
Where Does Tesla Inc: 1538000-xx-y {208V} Fall Across Listed CEC Models?
Output power comparison showing where Tesla Inc: 1538000-xx-y {208V} sits among all 2,343 CEC-listed grid-support inverters. Review related calculators, peer benchmarks, and source citations below to validate design assumptions for your electrical service.
What Dataset Percentiles Define Tesla Inc: 1538000-xx-y {208V}?
Relative ranking of Tesla Inc: 1538000-xx-y {208V} on continuous AC power, CEC weighted efficiency, and OCPD breaker current.
What Do the Dataset Ranks Show for Tesla Inc: 1538000-xx-y {208V}?
Snapshot of Tesla Inc: 1538000-xx-y {208V} efficiency rank (#638), OCPD breaker size, MPPT span, and busbar verdict. All figures trace directly to published federal energy filings, state electrical boards, CEC datasheets, and NFPA 70 NEC tables.
97.37% CEC Weighted Efficiency
+0.96 pts vs the 96.41% 208 V median; overall power rank #1,340 (6,561 W, below CEC median; higher than 42.8% of peers).
40 A Required Backfeed OCPD
125% x 31.5 A = 39.4 A -> 40 A standard OCPD using 8 AWG Cu (75 C).
270 V - 480 V (Max 480 V DC)
Tracking span of 210.0 V; listed since 2023-01-03 (grid-tied PV inverter).
PASS (120% Commercial Busbar)
Evaluated for 208 V, commercial single-phase switchgear (200A Bus / 200A Main (208V) to 1,200A Bus / 1,200A Main (208V)) under NEC 705.12 / 705.11.
NEC 705.12 Backfeed OCPD & 120% Busbar Formula
I_cont = 6561.0W / 208 V -> 31.5 A | Breaker >= 1.25 * 31.5 = 39.4 A -> 40 A
CEC Inverters.csv for Tesla Inc: 1538000-xx-y {208V}: Paco=6561.0 W, Vac=208 V, Vdcmax=480.0 V, Eff=97.37%.
Result: Min 40 A breaker & 8 AWG Cu (75 C); 1,200A Bus / 1,200A Main (208V): PASS (120% Commercial Busbar).
What Are the Published CEC Specifications for Tesla Inc: 1538000-xx-y {208V}?
Complete California Energy Commission grid-support inverter ratings and hybrid battery capabilities for Tesla Inc: 1538000-xx-y {208V}. Data intervals combine current 2025 federal utility and BLS wage releases with verified state electrical board rosters.
| Parameter | Measured / Listed Value | Engineering Significance |
|---|---|---|
| Max Continuous AC Power (Paco) | 6,561 W | Determines required backfeed OCPD size via 125% continuous rule |
| Nominal AC Voltage (Vac) | 208 V, commercial single-phase | 240V split-phase residential vs. 208V/480V/MV commercial |
| Max DC Input Voltage (Vdcmax) | 480 V | Hard ceiling for cold-weather PV string Voc under NEC 690.7 |
| MPPT Operating Range | 270 V - 480 V | Optimal DC string Vmp window for full power harvest |
| Max Input DC Current (Idcmax) | 17.9687 A | Used to verify parallel string combiner limits |
| CEC Weighted Efficiency | 97.37% | Calculated AC/DC conversion ratio from CEC test protocol |
| CEC Listing Date & Hybrid | 2023-01-03 / Hybrid: No (Grid-Tied PV) | Utility interconnection approval metadata |
What Switchgear Limits Apply to Tesla Inc: 1538000-xx-y {208V} (208 V, commercial single-phase)?
NEC 705.12(B)(3)(2) backfeed compliance table for Tesla Inc: 1538000-xx-y {208V} at 208 V, commercial single-phase.
| Switchboard / Interconnect | 120% Max Backfeed | Required PV OCPD | Compliance Verdict |
|---|---|---|---|
| 200A Bus / 200A Main (208V) | 40 A | 40 A | PASS (120% Commercial Busbar) |
| 400A Bus / 400A Main (208V) | 80 A | 40 A | PASS (120% Commercial Busbar) |
| 600A Bus / 600A Main (208V) | 120 A | 40 A | PASS (120% Commercial Busbar) |
| 800A Bus / 800A Main (208V) | 160 A | 40 A | PASS (120% Commercial Busbar) |
| 1,200A Bus / 1,200A Main (208V) | 240 A | 40 A | PASS (120% Commercial Busbar) |
Which CEC PV Module Strings Pair With Tesla Inc: 1538000-xx-y {208V}?
Minimum and maximum series solar module strings fitting Tesla Inc: 1538000-xx-y {208V} MPPT and 480 V limits. Every reported metric links directly to federal public records or state regulatory filings with zero paid contractor placements.
| CEC Module | STC (W) | -10 C Voc | Valid String Range | Max String DC |
|---|---|---|---|---|
| AXITEC AC-590TGB/144TS | 590.0 W | 56.24 V | 7 to 8 panels | 4.72 kW |
| Aptos Solar Technology LLC DNA-108-MFN10-440W | 440.0 W | 42.15 V | 9 to 11 panels | 4.84 kW |
| Boviet Solar Technology Co Ltd BVM7610M-425-H-HC-BF | 425.0 W | 44.75 V | 8 to 10 panels | 4.25 kW |
| CSI Solar Co Ltd CS6P-200P | 200.0 W | 40.6 V | 10 to 11 panels | 2.2 kW |
Which Competing Grid-Support Inverters Compare to Tesla Inc: 1538000-xx-y {208V}?
Peer 208 V, commercial single-phase CEC inverters near 6,561 W AC output such as Delta Electronics: SOLIVIA 66 NA G4 TL {208V}.
| Alternative Inverter | AC Output | Delta | Vac | Max DC | CEC Eff |
|---|---|---|---|---|---|
| Delta Electronics: SOLIVIA 66 NA G4 TL {208V} Delta Electronics |
6,600 W | +39 W | 208.0 V | 500.0 V | 97.02% |
| Delta Electronics: SOLIVIA 76 NA G4 TL {208V} Delta Electronics |
6,600 W | +39 W | 208.0 V | 500.0 V | 97.02% |
| Altenergy Power System Inc: ELS-76 {208V} Altenergy Power System Inc |
6,606 W | +45 W | 208.0 V | 60.0 V | 93.96% |
| Delta Electronics: E8-TL-US(AC) {208V} Delta Electronics |
6,500 W | -61 W | 208.0 V | 480.0 V | 97.65% |
What Are the Interconnection Limits and Best-Fit Uses for Tesla Inc: 1538000-xx-y {208V}?
Check Tesla Inc: 1538000-xx-y {208V} (6,561 W AC, 40 A OCPD) against your main panel busbar, winter string Voc, and IEEE 1547 outage rules.
- Anti-islanding shutdown: grid-tied inverters shut off within 2 seconds during blackouts under IEEE 1547 unless paired with a battery microgrid interconnect.
- Busbar 120% limit: Commercial 208 V, commercial single-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (208V) or NEC 705.11 supply-side tap.
- Cold Voc hard ceiling: never allow winter open-circuit PV string voltage to exceed 480 V DC on Tesla Inc: 1538000-xx-y {208V}.
Tesla Inc: 1538000-xx-y {208V} Panel & Wire Spec
Size 75 C copper conductors at 8 AWG Cu on a 40 A OCPD breaker (31.5 A continuous).
Alternative Inverter Comparison
Compare efficiency (97.37%) and MPPT window (270-480 V) directly against Delta Electronics: SOLIVIA 66 NA G4 TL {208V} (6,600 W).
Which Homeowner Electrical & Solar Questions Come Up Most Often?
Answers for Tesla Inc: 1538000-xx-y {208V} by Tesla Inc covering breaker sizing, MPPT limits, and 208 V, commercial single-phase interconnection.
What breaker and wire size does Tesla Inc: 1538000-xx-y {208V} require?
At 6,561 W continuous AC (208 V, commercial single-phase), continuous current is 31.5 A; 125% NEC 690.8/705.12 sizing requires a 40 A breaker and 8 AWG Cu (75 C) wire.
What commercial switchgear or feeder sizing does Tesla Inc: 1538000-xx-y {208V} require?
At 6,561 W AC and 208 V, commercial single-phase, continuous line current is 31.5 A, requiring a 40 A OCPD and 1,200A Bus / 1,200A Main (208V) or NEC 705.11 interconnection.
How does Tesla Inc: 1538000-xx-y {208V} compare to Delta Electronics: SOLIVIA 66 NA G4 TL {208V}?
Tesla Inc: 1538000-xx-y {208V} delivers 6,561 W AC at 97.37% CEC efficiency with a 480 V DC ceiling, while Delta Electronics: SOLIVIA 66 NA G4 TL {208V} outputs 6,600 W at 208 V, commercial single-phase.
Sources
- CEC Solar Equipment List — Grid-Support Inverters (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
- CEC Solar Equipment List — PV Modules (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
- NFPA 70 National Electrical Code (Section Numbers & Standard Engineering Tables Only) — National Fire Protection Association (NFPA), 2020 / 2023 / 2026 Editions (retrieved 2026-11-23)