Tesla Inc: 1707000-XX-Y {240V 115kW} outputs 11,508 W AC at 240 V (48.0 A continuous, 60 A OCPD), ranking #782 of 2,343 CEC inverters at 97.19% efficiency with a 270-480 V MPPT window and 480 V DC limit. All figures reconcile directly against federal energy archives, state electrical licensing boards, California Energy Commission datasheets, and National Electrical Code engineering constants.
- AC Output (Paco)
- 11,508 W
- AC Voltage
- 240 V
- Min PV Breaker
- 60 A (6 AWG Cu)
- CEC Efficiency
- 97.19%
How Does Tesla Inc: 1707000-XX-Y {240V 115kW} Compare Against Peer CEC Listings?
Breaker sizing (60 A), 6 AWG Cu wire rules, and DC input limits for Tesla Inc: 1707000-XX-Y {240V 115kW}.
Classified as a hybrid battery-capable inverter (active in CEC directory), Tesla Inc: 1707000-XX-Y {240V 115kW} requires 60.0 A design capacity -> 60 A breaker using 6 AWG Cu copper at 75 C terminals. Weighted efficiency sits at 97.19% (+0.37 pts vs overall CEC median) across 2,343 CEC models, while its 60 a backfeed breaker exceeds a 200a/200a panel's 40 a ceiling, requiring a 175 a main derate, 225 a busbar, or nec 705.11 tap.
Where Does Tesla Inc: 1707000-XX-Y {240V 115kW} Fall Across Listed CEC Models?
Output power comparison showing where Tesla Inc: 1707000-XX-Y {240V 115kW} sits among all 2,343 CEC-listed grid-support inverters. All figures trace directly to published federal energy filings, state electrical boards, CEC datasheets, and NFPA 70 NEC tables.
What Dataset Percentiles Define Tesla Inc: 1707000-XX-Y {240V 115kW}?
Relative ranking of Tesla Inc: 1707000-XX-Y {240V 115kW} on continuous AC power, CEC weighted efficiency, and OCPD breaker current.
What Do the Dataset Ranks Show for Tesla Inc: 1707000-XX-Y {240V 115kW}?
Snapshot of Tesla Inc: 1707000-XX-Y {240V 115kW} efficiency rank (#782), OCPD breaker size, MPPT span, and busbar verdict.
97.19% CEC Weighted Efficiency
+0.51 pts vs the 96.68% 240 V median; overall power rank #766 (11,508 W, top 32.7%; higher than 67.3% of peers).
60 A Required Backfeed OCPD
125% x 48.0 A = 60.0 A -> 60 A standard OCPD using 6 AWG Cu (75 C).
270 V - 480 V (Max 480 V DC)
Tracking span of 210.0 V; active in CEC directory (hybrid battery-capable inverter).
Needs Derate / Tap 705.11
200A/200A panel allows 40A PV backfeed; 200A/175A derate allows 65A; 225A/200A allows 70A.
NEC 705.12 Backfeed OCPD & 120% Busbar Formula
I_cont = 11508.0W / 240 V -> 48.0 A | Breaker >= 1.25 * 48.0 = 60.0 A -> 60 A
CEC Inverters.csv for Tesla Inc: 1707000-XX-Y {240V 115kW}: Paco=11508.0 W, Vac=240 V, Vdcmax=480.0 V, Eff=97.19%.
Result: Min 60 A breaker & 6 AWG Cu (75 C); 200A Bus / 200A Main: Needs Derate / Tap 705.11.
What Are the Published CEC Specifications for Tesla Inc: 1707000-XX-Y {240V 115kW}?
Complete California Energy Commission grid-support inverter ratings and hybrid battery capabilities for Tesla Inc: 1707000-XX-Y {240V 115kW}. Cross-check local Authority Having Jurisdiction amendments and serving utility net-metering terms before finalizing project sizing.
| Parameter | Measured / Listed Value | Engineering Significance |
|---|---|---|
| Max Continuous AC Power (Paco) | 11,508 W | Determines required backfeed OCPD size via 125% continuous rule |
| Nominal AC Voltage (Vac) | 240 V | 240V split-phase residential vs. 208V/480V/MV commercial |
| Max DC Input Voltage (Vdcmax) | 480 V | Hard ceiling for cold-weather PV string Voc under NEC 690.7 |
| MPPT Operating Range | 270 V - 480 V | Optimal DC string Vmp window for full power harvest |
| Max Input DC Current (Idcmax) | 31.576 A | Used to verify parallel string combiner limits |
| CEC Weighted Efficiency | 97.19% | Calculated AC/DC conversion ratio from CEC test protocol |
| Inverter Topology | Hybrid: Yes (Battery Capable) | CEC Solar Equipment List grid-support certification |
Can a Residential Panel Meet 120% Busbar Limits for Tesla Inc: 1707000-XX-Y {240V 115kW}?
NEC 705.12(B)(3)(2) backfeed compliance table for Tesla Inc: 1707000-XX-Y {240V 115kW} at 240 V. Compare thermal ratings, overcurrent protection caps, and continuous load headroom carefully before expanding an existing home service panel.
| Panel Configuration | 120% Max Backfeed | Required PV OCPD | Compliance Verdict |
|---|---|---|---|
| 100A Bus / 100A Main | 20 A | 60 A | Needs Derate / Tap 705.11 |
| 150A Bus / 150A Main | 30 A | 60 A | Needs Derate / Tap 705.11 |
| 200A Bus / 200A Main | 40 A | 60 A | Needs Derate / Tap 705.11 |
| 200A Bus / 175A Main | 65 A | 60 A | PASS (120% Rule) |
| 225A Bus / 200A Main | 70 A | 60 A | PASS (120% Rule) |
Which CEC PV Module Strings Pair With Tesla Inc: 1707000-XX-Y {240V 115kW}?
Minimum and maximum series solar module strings fitting Tesla Inc: 1707000-XX-Y {240V 115kW} MPPT and 480 V limits.
| CEC Module | STC (W) | -10 C Voc | Valid String Range | Max String DC |
|---|---|---|---|---|
| AXITEC AC-590TGB/144TS | 590.0 W | 56.24 V | 7 to 8 panels | 4.72 kW |
| Aptos Solar Technology LLC DNA-108-MFN10-440W | 440.0 W | 42.15 V | 9 to 11 panels | 4.84 kW |
| Boviet Solar Technology Co Ltd BVM7610M-425-H-HC-BF | 425.0 W | 44.75 V | 8 to 10 panels | 4.25 kW |
| CSI Solar Co Ltd CS6P-200P | 200.0 W | 40.6 V | 10 to 11 panels | 2.2 kW |
Which Competing Grid-Support Inverters Compare to Tesla Inc: 1707000-XX-Y {240V 115kW}?
Peer 240 V CEC inverters near 11,508 W AC output such as Dyness Digital Energy Technology Co LTD: TX114K-HM {240V}.
| Alternative Inverter | AC Output | Delta | Vac | Max DC | CEC Eff |
|---|---|---|---|---|---|
| Dyness Digital Energy Technology Co LTD: TX114K-HM {240V} Dyness Digital Energy Technology Co LTD |
11,498 W | -10 W | 240.0 V | 500.0 V | 96.41% |
| Dyness Digital Energy Technology Co LTD: TX114K-AM {240V} Dyness Digital Energy Technology Co LTD |
11,519 W | +11 W | 240.0 V | 490.0 V | 96.21% |
| Base Power Inc: MIN 11400TL-XH-US {240V} Base Power Inc |
11,520 W | +12 W | 240.0 V | 480.0 V | 97.76% |
| Delta Electronics: S12_BDI {240V} Delta Electronics |
11,589 W | +81 W | 240.0 V | 480.0 V | 96.99% |
What Are the Interconnection Limits and Best-Fit Uses for Tesla Inc: 1707000-XX-Y {240V 115kW}?
Check Tesla Inc: 1707000-XX-Y {240V 115kW} (11,508 W AC, 60 A OCPD) against your main panel busbar, winter string Voc, and IEEE 1547 outage rules.
- Anti-islanding shutdown: grid-tied inverters shut off within 2 seconds during blackouts under IEEE 1547 unless paired with a battery microgrid interconnect.
- Busbar 120% limit: Its 60 A backfeed breaker exceeds a 200A/200A panel's 40 A ceiling, requiring a 175 A main derate, 225 A busbar, or NEC 705.11 tap.
- Cold Voc hard ceiling: never allow winter open-circuit PV string voltage to exceed 480 V DC on Tesla Inc: 1707000-XX-Y {240V 115kW}.
Tesla Inc: 1707000-XX-Y {240V 115kW} Panel & Wire Spec
Size 75 C copper conductors at 6 AWG Cu on a 60 A OCPD breaker (48.0 A continuous).
Alternative Inverter Comparison
Compare efficiency (97.19%) and MPPT window (270-480 V) directly against Dyness Digital Energy Technology Co LTD: TX114K-HM {240V} (11,498 W).
Which Homeowner Electrical & Solar Questions Come Up Most Often?
Answers for Tesla Inc: 1707000-XX-Y {240V 115kW} by Tesla Inc covering breaker sizing, MPPT limits, and 240 V interconnection.
What breaker and wire size does Tesla Inc: 1707000-XX-Y {240V 115kW} require?
At 11,508 W continuous AC (240 V), continuous current is 48.0 A; 125% NEC 690.8/705.12 sizing requires a 60 A breaker and 6 AWG Cu (75 C) wire.
Does Tesla Inc: 1707000-XX-Y {240V 115kW} fit a 200 A main panel under the 120% busbar rule?
A 200 A busbar with a 200 A main allows 40 A of solar backfeed. Requiring 60 A at 240 V means Needs Derate / Tap 705.11.
How does Tesla Inc: 1707000-XX-Y {240V 115kW} compare to Dyness Digital Energy Technology Co LTD: TX114K-HM {240V}?
Tesla Inc: 1707000-XX-Y {240V 115kW} delivers 11,508 W AC at 97.19% CEC efficiency with a 480 V DC ceiling, while Dyness Digital Energy Technology Co LTD: TX114K-HM {240V} outputs 11,498 W at 240 V.
Sources
- CEC Solar Equipment List — Grid-Support Inverters (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
- CEC Solar Equipment List — PV Modules (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
- NFPA 70 National Electrical Code (Section Numbers & Standard Engineering Tables Only) — National Fire Protection Association (NFPA), 2020 / 2023 / 2026 Editions (retrieved 2026-11-23)