SolarEdge Technologies Ltd: SE666KUS {480V} outputs 33,300 W AC at 480 V, 3-phase (40.1 A continuous, 60 A OCPD), ranking #193 of 2,343 CEC inverters at 98.29% efficiency with a 790-950 V MPPT window and 950 V DC limit. All figures reconcile directly against federal energy archives, state electrical licensing boards, California Energy Commission datasheets, and National Electrical Code engineering constants.
- AC Output (Paco)
- 33,300 W
- AC Voltage
- 480 V, 3-phase
- Min PV Breaker
- 60 A (6 AWG Cu)
- CEC Efficiency
- 98.29%
How Does SolarEdge Technologies Ltd: SE666KUS {480V} Compare Against Peer CEC Listings?
How SolarEdge Technologies Ltd SolarEdge Technologies Ltd: SE666KUS {480V} compares on 98.29% efficiency, MPPT span, and 120% busbar interconnection.
SolarEdge Technologies Ltd certifies SolarEdge Technologies Ltd: SE666KUS {480V} (grid-tied PV inverter, listed since 2023-02-01) at 33,300 W AC (16,700 W below the 50,000 W 480 V median). Its 950 V DC ceiling pairs with an MPPT window of 790-950 V (span 160.0 V). Under NEC 690.8/705.12, 125% sizing demands 6 AWG Cu conductors on a 60 A OCPD.
Where Does SolarEdge Technologies Ltd: SE666KUS {480V} Fall Across Listed CEC Models?
Position of SolarEdge Technologies Ltd: SE666KUS {480V} (33,300 W AC) relative to the 7,680 W CEC median inverter.
What Dataset Percentiles Define SolarEdge Technologies Ltd: SE666KUS {480V}?
Percentile placement of SolarEdge Technologies Ltd: SE666KUS {480V} across AC power class, conversion efficiency, and backfeed breaker size.
What Do the Dataset Ranks Show for SolarEdge Technologies Ltd: SE666KUS {480V}?
Primary electrical sizing limits, efficiency ranks, and NEC 705.12 / 690.7 thresholds for SolarEdge Technologies Ltd: SE666KUS {480V}. Data intervals combine current 2025 federal utility and BLS wage releases with verified state electrical board rosters.
98.29% CEC Weighted Efficiency
+0.27 pts vs the 98.02% 480 V median; overall power rank #533 (33,300 W, top 22.9%; higher than 77.1% of peers).
60 A Required Backfeed OCPD
125% x 40.1 A = 50.1 A -> 60 A standard OCPD using 6 AWG Cu (75 C).
790 V - 950 V (Max 950 V DC)
Tracking span of 160.0 V; listed since 2023-02-01 (grid-tied PV inverter).
PASS (120% Commercial Busbar)
Evaluated for 480 V, 3-phase switchgear (200A Bus / 200A Main (480V) to 1,200A Bus / 1,200A Main (480V)) under NEC 705.12 / 705.11.
NEC 705.12 Backfeed OCPD & 120% Busbar Formula
I_cont = 33300.0W / 480 V 3-phase -> 40.1 A | Breaker >= 1.25 * 40.1 = 50.1 A -> 60 A
CEC Inverters.csv for SolarEdge Technologies Ltd: SE666KUS {480V}: Paco=33300.0 W, Vac=480 V, Vdcmax=950.0 V, Eff=98.29%.
Result: Min 60 A breaker & 6 AWG Cu (75 C); 1,200A Bus / 1,200A Main (480V): PASS (120% Commercial Busbar).
What Are the Published CEC Specifications for SolarEdge Technologies Ltd: SE666KUS {480V}?
Official California Energy Commission electrical test parameters, AC voltage, and DC limits for SolarEdge Technologies Ltd: SE666KUS {480V}.
| Parameter | Measured / Listed Value | Engineering Significance |
|---|---|---|
| Max Continuous AC Power (Paco) | 33,300 W | Determines required backfeed OCPD size via 125% continuous rule |
| Nominal AC Voltage (Vac) | 480 V, 3-phase | 240V split-phase residential vs. 208V/480V/MV commercial |
| Max DC Input Voltage (Vdcmax) | 950 V | Hard ceiling for cold-weather PV string Voc under NEC 690.7 |
| MPPT Operating Range | 790 V - 950 V | Optimal DC string Vmp window for full power harvest |
| Max Input DC Current (Idcmax) | 39.8575 A | Used to verify parallel string combiner limits |
| CEC Weighted Efficiency | 98.29% | Calculated AC/DC conversion ratio from CEC test protocol |
| CEC Listing Date & Hybrid | 2023-02-01 / Hybrid: No (Grid-Tied PV) | Utility interconnection approval metadata |
What Switchgear Limits Apply to SolarEdge Technologies Ltd: SE666KUS {480V} (480 V, 3-phase)?
Check whether SolarEdge Technologies Ltd: SE666KUS {480V} (60 A breaker) fits without main breaker derate or supply-side taps.
| Switchboard / Interconnect | 120% Max Backfeed | Required PV OCPD | Compliance Verdict |
|---|---|---|---|
| 200A Bus / 200A Main (480V) | 40 A | 60 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| 400A Bus / 400A Main (480V) | 80 A | 60 A | PASS (120% Commercial Busbar) |
| 600A Bus / 600A Main (480V) | 120 A | 60 A | PASS (120% Commercial Busbar) |
| 800A Bus / 800A Main (480V) | 160 A | 60 A | PASS (120% Commercial Busbar) |
| 1,200A Bus / 1,200A Main (480V) | 240 A | 60 A | PASS (120% Commercial Busbar) |
Which Competing Grid-Support Inverters Compare to SolarEdge Technologies Ltd: SE666KUS {480V}?
Alternative CEC inverters comparable to SolarEdge Technologies Ltd: SE666KUS {480V}, including CSI Solar Co Ltd: CSI-33K-T480GL03-U {480V} (32,865 W) at 480 V, 3-phase.
| Alternative Inverter | AC Output | Delta | Vac | Max DC | CEC Eff |
|---|---|---|---|---|---|
| CSI Solar Co Ltd: CSI-33K-T480GL03-U {480V} CSI Solar Co Ltd |
32,865 W | -435 W | 480.0 V | 850.0 V | 98.36% |
| CSI Solar Co Ltd: CSI-36K-T480GL03-U {480V} CSI Solar Co Ltd |
35,866 W | +2566 W | 480.0 V | 850.0 V | 98.21% |
| Delta Electronics: M28U_120 {480V} Delta Electronics |
30,709 W | -2591 W | 480.0 V | 830.0 V | 98.14% |
| Delta Electronics: M28U_121 {480V} Delta Electronics |
30,709 W | -2591 W | 480.0 V | 830.0 V | 98.14% |
What Are the Interconnection Limits and Best-Fit Uses for SolarEdge Technologies Ltd: SE666KUS {480V}?
Check SolarEdge Technologies Ltd: SE666KUS {480V} (33,300 W AC, 60 A OCPD) against your main panel busbar, winter string Voc, and IEEE 1547 outage rules.
- Anti-islanding shutdown: grid-tied inverters shut off within 2 seconds during blackouts under IEEE 1547 unless paired with a battery microgrid interconnect.
- Busbar 120% limit: Commercial 480 V, 3-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (480V) or NEC 705.11 supply-side tap.
- Cold Voc hard ceiling: never allow winter open-circuit PV string voltage to exceed 950 V DC on SolarEdge Technologies Ltd: SE666KUS {480V}.
SolarEdge Technologies Ltd: SE666KUS {480V} Panel & Wire Spec
Size 75 C copper conductors at 6 AWG Cu on a 60 A OCPD breaker (40.1 A continuous).
Alternative Inverter Comparison
Compare efficiency (98.29%) and MPPT window (790-950 V) directly against CSI Solar Co Ltd: CSI-33K-T480GL03-U {480V} (32,865 W).
Which Homeowner Electrical & Solar Questions Come Up Most Often?
Answers for SolarEdge Technologies Ltd: SE666KUS {480V} by SolarEdge Technologies Ltd covering breaker sizing, MPPT limits, and 480 V, 3-phase interconnection.
What breaker and wire size does SolarEdge Technologies Ltd: SE666KUS {480V} require?
At 33,300 W continuous AC (480 V, 3-phase), continuous current is 40.1 A; 125% NEC 690.8/705.12 sizing requires a 60 A breaker and 6 AWG Cu (75 C) wire.
What commercial switchgear or feeder sizing does SolarEdge Technologies Ltd: SE666KUS {480V} require?
At 33,300 W AC and 480 V, 3-phase, continuous line current is 40.1 A, requiring a 60 A OCPD and 1,200A Bus / 1,200A Main (480V) or NEC 705.11 interconnection.
How does SolarEdge Technologies Ltd: SE666KUS {480V} compare to CSI Solar Co Ltd: CSI-33K-T480GL03-U {480V}?
SolarEdge Technologies Ltd: SE666KUS {480V} delivers 33,300 W AC at 98.29% CEC efficiency with a 950 V DC ceiling, while CSI Solar Co Ltd: CSI-33K-T480GL03-U {480V} outputs 32,865 W at 480 V, 3-phase.
Sources
- CEC Solar Equipment List — Grid-Support Inverters (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
- CEC Solar Equipment List — PV Modules (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
- NFPA 70 National Electrical Code (Section Numbers & Standard Engineering Tables Only) — National Fire Protection Association (NFPA), 2020 / 2023 / 2026 Editions (retrieved 2026-11-23)