SolarEdge Technologies Ltd: SE6000x {240V} outputs 5,990 W AC at 240 V (25.0 A continuous, 35 A OCPD), ranking #1,044 of 2,343 CEC inverters at 96.98% efficiency with a 370-500 V MPPT window and 500 V DC limit. All figures reconcile directly against federal energy archives, state electrical licensing boards, California Energy Commission datasheets, and National Electrical Code engineering constants.
- AC Output (Paco)
- 5,990 W
- AC Voltage
- 240 V
- Min PV Breaker
- 35 A (8 AWG Cu)
- CEC Efficiency
- 96.98%
How Does SolarEdge Technologies Ltd: SE6000x {240V} Compare Against Peer CEC Listings?
NEC 705.12 breaker requirements, efficiency placement, and 240 V grid-support overview for SolarEdge Technologies Ltd: SE6000x {240V}. All figures trace directly to published federal energy filings, state electrical boards, CEC datasheets, and NFPA 70 NEC tables.
Rated at 5,990 W AC (25.0 A continuous), SolarEdge Technologies Ltd: SE6000x {240V} ranks #1,044 of 2,343 CEC units at 96.98% efficiency (+0.30 pts vs the 96.68% 240 V median). Minimum 75 C copper conductor sizing for its 35 A circuit is 8 AWG Cu per NEC Table 310.16. Cold-weather string Voc must remain under 500 V DC at record local winter lows.
Where Does SolarEdge Technologies Ltd: SE6000x {240V} Fall Across Listed CEC Models?
Marks SolarEdge Technologies Ltd: SE6000x {240V} (5,990 W AC) across the California Energy Commission inverter AC capacity distribution.
What Dataset Percentiles Define SolarEdge Technologies Ltd: SE6000x {240V}?
Benchmarks SolarEdge Technologies Ltd: SE6000x {240V} continuous AC output, 96.98% CEC weighted efficiency, and 35 A OCPD breaker demand.
What Do the Dataset Ranks Show for SolarEdge Technologies Ltd: SE6000x {240V}?
Four key NEC 705.12 and California Energy Commission metrics defining SolarEdge Technologies Ltd: SE6000x {240V} by SolarEdge Technologies Ltd.
96.98% CEC Weighted Efficiency
+0.30 pts vs the 96.68% 240 V median; overall power rank #1,426 (5,990 W, below CEC median; higher than 39.1% of peers).
35 A Required Backfeed OCPD
125% x 25.0 A = 31.2 A -> 35 A standard OCPD using 8 AWG Cu (75 C).
370 V - 500 V (Max 500 V DC)
Tracking span of 130.0 V; listed since 2018-10-15 (grid-tied PV inverter).
PASS (120% Rule)
200A/200A panel allows 40A PV backfeed; 200A/175A derate allows 65A; 225A/200A allows 70A.
NEC 705.12 Backfeed OCPD & 120% Busbar Formula
I_cont = 5990.0W / 240 V -> 25.0 A | Breaker >= 1.25 * 25.0 = 31.2 A -> 35 A
CEC Inverters.csv for SolarEdge Technologies Ltd: SE6000x {240V}: Paco=5990.0 W, Vac=240 V, Vdcmax=500.0 V, Eff=96.98%.
Result: Min 35 A breaker & 8 AWG Cu (75 C); 200A Bus / 200A Main: PASS (120% Rule).
What Are the Published CEC Specifications for SolarEdge Technologies Ltd: SE6000x {240V}?
Official laboratory CEC ratings, MPPT operating window, and DC voltage bounds recorded for SolarEdge Technologies Ltd: SE6000x {240V}.
| Parameter | Measured / Listed Value | Engineering Significance |
|---|---|---|
| Max Continuous AC Power (Paco) | 5,990 W | Determines required backfeed OCPD size via 125% continuous rule |
| Nominal AC Voltage (Vac) | 240 V | 240V split-phase residential vs. 208V/480V/MV commercial |
| Max DC Input Voltage (Vdcmax) | 500 V | Hard ceiling for cold-weather PV string Voc under NEC 690.7 |
| MPPT Operating Range | 370 V - 500 V | Optimal DC string Vmp window for full power harvest |
| Max Input DC Current (Idcmax) | 14.1994 A | Used to verify parallel string combiner limits |
| CEC Weighted Efficiency | 96.98% | Calculated AC/DC conversion ratio from CEC test protocol |
| CEC Listing Date & Hybrid | 2018-10-15 / Hybrid: No (Grid-Tied PV) | Utility interconnection approval metadata |
Can a Residential Panel Meet 120% Busbar Limits for SolarEdge Technologies Ltd: SE6000x {240V}?
Evaluates SolarEdge Technologies Ltd: SE6000x {240V} (35 A OCPD) across standard 100 A to 225 A busbars or commercial switchboards.
| Panel Configuration | 120% Max Backfeed | Required PV OCPD | Compliance Verdict |
|---|---|---|---|
| 100A Bus / 100A Main | 20 A | 35 A | Needs Derate / Tap 705.11 |
| 150A Bus / 150A Main | 30 A | 35 A | Needs Derate / Tap 705.11 |
| 200A Bus / 200A Main | 40 A | 35 A | PASS (120% Rule) |
| 200A Bus / 175A Main | 65 A | 35 A | PASS (120% Rule) |
| 225A Bus / 200A Main | 70 A | 35 A | PASS (120% Rule) |
Which CEC PV Module Strings Pair With SolarEdge Technologies Ltd: SE6000x {240V}?
Sample PV string lengths aligned within 370-500 V MPPT and 500 V DC max at -10 C. Homeowners and permit reviewers can filter tables below to benchmark specific ratings, wiring ages, and code allowances side by side.
| CEC Module | STC (W) | -10 C Voc | Valid String Range | Max String DC |
|---|---|---|---|---|
| Boviet Solar Technology Co Ltd BVM7610M-425-H-HC-BF | 425.0 W | 44.75 V | 11 panels (fixed) | 4.67 kW |
| G-Star Pte Ltd GSN8K66T(H)740WT | 740.0 W | 54.38 V | 9 panels (fixed) | 6.66 kW |
| Hansol Technics Co Ltd HA650-AE-NNEA0 | 650.0 W | 61.2 V | 8 panels (fixed) | 5.2 kW |
| Heliene 72M-410 G1 | 410.0 W | 54.77 V | 9 panels (fixed) | 3.69 kW |
Which Competing Grid-Support Inverters Compare to SolarEdge Technologies Ltd: SE6000x {240V}?
Competing CEC grid-support inverters near 5,990 W AC and 240 V, led by Afore New Energy Technology (Shanghai) Co Ltd: AF6K-DH {240V}.
| Alternative Inverter | AC Output | Delta | Vac | Max DC | CEC Eff |
|---|---|---|---|---|---|
| Afore New Energy Technology (Shanghai) Co Ltd: AF6K-DH {240V} Afore New Energy Technology (Shanghai) Co Ltd |
5,995 W | +5 W | 240.0 V | 480.0 V | 97.6% |
| ABB: PVI-6000-OUTD-US-A {240V} ABB |
6,000 W | +10 W | 240.0 V | 480.0 V | 96.21% |
| ABB: PVI-6000-OUTD-US-Z-A {240V} ABB |
6,000 W | +10 W | 240.0 V | 480.0 V | 96.21% |
| ABB: PVI-6000-OUTD-US-Z-M-A {240V} ABB |
6,000 W | +10 W | 240.0 V | 480.0 V | 96.21% |
What Are the Interconnection Limits and Best-Fit Uses for SolarEdge Technologies Ltd: SE6000x {240V}?
Check SolarEdge Technologies Ltd: SE6000x {240V} (5,990 W AC, 35 A OCPD) against your main panel busbar, winter string Voc, and IEEE 1547 outage rules.
- Anti-islanding shutdown: grid-tied inverters shut off within 2 seconds during blackouts under IEEE 1547 unless paired with a battery microgrid interconnect.
- Busbar 120% limit: Requires a 35 A breaker, passing directly inside a standard 200 A main / 200 A busbar panel (40 A limit).
- Cold Voc hard ceiling: never allow winter open-circuit PV string voltage to exceed 500 V DC on SolarEdge Technologies Ltd: SE6000x {240V}.
SolarEdge Technologies Ltd: SE6000x {240V} Panel & Wire Spec
Size 75 C copper conductors at 8 AWG Cu on a 35 A OCPD breaker (25.0 A continuous).
Alternative Inverter Comparison
Compare efficiency (96.98%) and MPPT window (370-500 V) directly against Afore New Energy Technology (Shanghai) Co Ltd: AF6K-DH {240V} (5,995 W).
Which Homeowner Electrical & Solar Questions Come Up Most Often?
Answers for SolarEdge Technologies Ltd: SE6000x {240V} by SolarEdge Technologies Ltd covering breaker sizing, MPPT limits, and 240 V interconnection.
What breaker and wire size does SolarEdge Technologies Ltd: SE6000x {240V} require?
At 5,990 W continuous AC (240 V), continuous current is 25.0 A; 125% NEC 690.8/705.12 sizing requires a 35 A breaker and 8 AWG Cu (75 C) wire.
Does SolarEdge Technologies Ltd: SE6000x {240V} fit a 200 A main panel under the 120% busbar rule?
A 200 A busbar with a 200 A main allows 40 A of solar backfeed. Requiring 35 A at 240 V means PASS (120% Rule).
How does SolarEdge Technologies Ltd: SE6000x {240V} compare to Afore New Energy Technology (Shanghai) Co Ltd: AF6K-DH {240V}?
SolarEdge Technologies Ltd: SE6000x {240V} delivers 5,990 W AC at 96.98% CEC efficiency with a 500 V DC ceiling, while Afore New Energy Technology (Shanghai) Co Ltd: AF6K-DH {240V} outputs 5,995 W at 240 V.