SolarEdge Technologies Ltd: SE3800H-US {208V} outputs 3,255 W AC at 208 V, commercial single-phase (15.6 A continuous, 20 A OCPD), ranking #41 of 2,343 CEC inverters at 98.67% efficiency with a 360-480 V MPPT window and 480 V DC limit. All figures reconcile directly against federal energy archives, state electrical licensing boards, California Energy Commission datasheets, and National Electrical Code engineering constants.
- AC Output (Paco)
- 3,255 W
- AC Voltage
- 208 V, commercial single-phase
- Min PV Breaker
- 20 A (12 AWG Cu)
- CEC Efficiency
- 98.67%
How Does SolarEdge Technologies Ltd: SE3800H-US {208V} Compare Against Peer CEC Listings?
Breaker sizing (20 A), 12 AWG Cu wire rules, and DC input limits for SolarEdge Technologies Ltd: SE3800H-US {208V}.
For NEC 705.12 solar interconnection, SolarEdge Technologies Ltd: SE3800H-US {208V} outputs 15.6 A continuous AC at 208 V, commercial single-phase and needs a 20 A backfeed breaker on 12 AWG Cu (75 C). Commercial 208 V, commercial single-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (208V) or NEC 705.11 supply-side tap. Conversion efficiency scores 98.67% (#41 of 2,343, +1.85 pts vs overall CEC median).
Where Does SolarEdge Technologies Ltd: SE3800H-US {208V} Fall Across Listed CEC Models?
Output power comparison showing where SolarEdge Technologies Ltd: SE3800H-US {208V} sits among all 2,343 CEC-listed grid-support inverters. Cross-check local Authority Having Jurisdiction amendments and serving utility net-metering terms before finalizing project sizing.
What Dataset Percentiles Define SolarEdge Technologies Ltd: SE3800H-US {208V}?
Relative ranking of SolarEdge Technologies Ltd: SE3800H-US {208V} on continuous AC power, CEC weighted efficiency, and OCPD breaker current.
What Do the Dataset Ranks Show for SolarEdge Technologies Ltd: SE3800H-US {208V}?
Snapshot of SolarEdge Technologies Ltd: SE3800H-US {208V} efficiency rank (#41), OCPD breaker size, MPPT span, and busbar verdict.
98.67% CEC Weighted Efficiency
+2.26 pts vs the 96.41% 208 V median; overall power rank #1,721 (3,255 W, below CEC median; higher than 26.5% of peers).
20 A Required Backfeed OCPD
125% x 15.6 A = 19.5 A -> 20 A standard OCPD using 12 AWG Cu (75 C).
360 V - 480 V (Max 480 V DC)
Tracking span of 120.0 V; listed since 2025-08-01 (hybrid battery-capable inverter).
PASS (120% Commercial Busbar)
Evaluated for 208 V, commercial single-phase switchgear (200A Bus / 200A Main (208V) to 1,200A Bus / 1,200A Main (208V)) under NEC 705.12 / 705.11.
NEC 705.12 Backfeed OCPD & 120% Busbar Formula
I_cont = 3255.0W / 208 V -> 15.6 A | Breaker >= 1.25 * 15.6 = 19.5 A -> 20 A
CEC Inverters.csv for SolarEdge Technologies Ltd: SE3800H-US {208V}: Paco=3255.0 W, Vac=208 V, Vdcmax=480.0 V, Eff=98.67%.
Result: Min 20 A breaker & 12 AWG Cu (75 C); 1,200A Bus / 1,200A Main (208V): PASS (120% Commercial Busbar).
What Are the Published CEC Specifications for SolarEdge Technologies Ltd: SE3800H-US {208V}?
Complete California Energy Commission grid-support inverter ratings and hybrid battery capabilities for SolarEdge Technologies Ltd: SE3800H-US {208V}. All figures trace directly to published federal energy filings, state electrical boards, CEC datasheets, and NFPA 70 NEC tables.
| Parameter | Measured / Listed Value | Engineering Significance |
|---|---|---|
| Max Continuous AC Power (Paco) | 3,255 W | Determines required backfeed OCPD size via 125% continuous rule |
| Nominal AC Voltage (Vac) | 208 V, commercial single-phase | 240V split-phase residential vs. 208V/480V/MV commercial |
| Max DC Input Voltage (Vdcmax) | 480 V | Hard ceiling for cold-weather PV string Voc under NEC 690.7 |
| MPPT Operating Range | 360 V - 480 V | Optimal DC string Vmp window for full power harvest |
| Max Input DC Current (Idcmax) | 8.3513 A | Used to verify parallel string combiner limits |
| CEC Weighted Efficiency | 98.67% | Calculated AC/DC conversion ratio from CEC test protocol |
| CEC Listing Date & Hybrid | 2025-08-01 / Hybrid: Yes (Battery Capable) | Utility interconnection approval metadata |
What Switchgear Limits Apply to SolarEdge Technologies Ltd: SE3800H-US {208V} (208 V, commercial single-phase)?
NEC 705.12(B)(3)(2) backfeed compliance table for SolarEdge Technologies Ltd: SE3800H-US {208V} at 208 V, commercial single-phase.
| Switchboard / Interconnect | 120% Max Backfeed | Required PV OCPD | Compliance Verdict |
|---|---|---|---|
| 200A Bus / 200A Main (208V) | 40 A | 20 A | PASS (120% Commercial Busbar) |
| 400A Bus / 400A Main (208V) | 80 A | 20 A | PASS (120% Commercial Busbar) |
| 600A Bus / 600A Main (208V) | 120 A | 20 A | PASS (120% Commercial Busbar) |
| 800A Bus / 800A Main (208V) | 160 A | 20 A | PASS (120% Commercial Busbar) |
| 1,200A Bus / 1,200A Main (208V) | 240 A | 20 A | PASS (120% Commercial Busbar) |
Which CEC PV Module Strings Pair With SolarEdge Technologies Ltd: SE3800H-US {208V}?
Minimum and maximum series solar module strings fitting SolarEdge Technologies Ltd: SE3800H-US {208V} MPPT and 480 V limits.
| CEC Module | STC (W) | -10 C Voc | Valid String Range | Max String DC |
|---|---|---|---|---|
| Aptos Solar Technology LLC DNA-108-MFN10-440W | 440.0 W | 42.15 V | 11 panels (fixed) | 4.84 kW |
Which Competing Grid-Support Inverters Compare to SolarEdge Technologies Ltd: SE3800H-US {208V}?
Peer 208 V, commercial single-phase CEC inverters near 3,255 W AC output such as ABB: UNO-DM-38-TL-PLUS-US-SB-RA {208V}. Regional housing vintage, storm hazard frequency, and wholesale utility prices directly govern residential upgrade payback across jurisdictions.
| Alternative Inverter | AC Output | Delta | Vac | Max DC | CEC Eff |
|---|---|---|---|---|---|
| ABB: UNO-DM-38-TL-PLUS-US-SB-RA {208V} ABB |
3,300 W | +45 W | 208.0 V | 480.0 V | 95.88% |
| ABB: UNO-DM-38-TL-PLUS-US-SB-RA-Q {208V} ABB |
3,300 W | +45 W | 208.0 V | 480.0 V | 95.88% |
| ABB: UNO-DM-38-TL-PLUS-US-SE-RA {208V} ABB |
3,300 W | +45 W | 208.0 V | 480.0 V | 95.88% |
| ABB: UNO-DM-38-TL-PLUS-US-SZ-RA {208V} ABB |
3,300 W | +45 W | 208.0 V | 480.0 V | 95.88% |
What Are the Interconnection Limits and Best-Fit Uses for SolarEdge Technologies Ltd: SE3800H-US {208V}?
Check SolarEdge Technologies Ltd: SE3800H-US {208V} (3,255 W AC, 20 A OCPD) against your main panel busbar, winter string Voc, and IEEE 1547 outage rules.
- Anti-islanding shutdown: grid-tied inverters shut off within 2 seconds during blackouts under IEEE 1547 unless paired with a battery microgrid interconnect.
- Busbar 120% limit: Commercial 208 V, commercial single-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (208V) or NEC 705.11 supply-side tap.
- Cold Voc hard ceiling: never allow winter open-circuit PV string voltage to exceed 480 V DC on SolarEdge Technologies Ltd: SE3800H-US {208V}.
SolarEdge Technologies Ltd: SE3800H-US {208V} Panel & Wire Spec
Size 75 C copper conductors at 12 AWG Cu on a 20 A OCPD breaker (15.6 A continuous).
Alternative Inverter Comparison
Compare efficiency (98.67%) and MPPT window (360-480 V) directly against ABB: UNO-DM-38-TL-PLUS-US-SB-RA {208V} (3,300 W).
Which Homeowner Electrical & Solar Questions Come Up Most Often?
Answers for SolarEdge Technologies Ltd: SE3800H-US {208V} by SolarEdge Technologies Ltd covering breaker sizing, MPPT limits, and 208 V, commercial single-phase interconnection.
What breaker and wire size does SolarEdge Technologies Ltd: SE3800H-US {208V} require?
At 3,255 W continuous AC (208 V, commercial single-phase), continuous current is 15.6 A; 125% NEC 690.8/705.12 sizing requires a 20 A breaker and 12 AWG Cu (75 C) wire.
What commercial switchgear or feeder sizing does SolarEdge Technologies Ltd: SE3800H-US {208V} require?
At 3,255 W AC and 208 V, commercial single-phase, continuous line current is 15.6 A, requiring a 20 A OCPD and 1,200A Bus / 1,200A Main (208V) or NEC 705.11 interconnection.
How does SolarEdge Technologies Ltd: SE3800H-US {208V} compare to ABB: UNO-DM-38-TL-PLUS-US-SB-RA {208V}?
SolarEdge Technologies Ltd: SE3800H-US {208V} delivers 3,255 W AC at 98.67% CEC efficiency with a 480 V DC ceiling, while ABB: UNO-DM-38-TL-PLUS-US-SB-RA {208V} outputs 3,300 W at 208 V, commercial single-phase.
Sources
- CEC Solar Equipment List — Grid-Support Inverters (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
- CEC Solar Equipment List — PV Modules (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
- NFPA 70 National Electrical Code (Section Numbers & Standard Engineering Tables Only) — National Fire Protection Association (NFPA), 2020 / 2023 / 2026 Editions (retrieved 2026-11-23)