Schneider Electric USA Inc: CS2200-NA {600V} outputs 2,200,000 W AC at 600 V, 3-phase (2117.0 A continuous, 2,650 A OCPD), ranking #792 of 2,343 CEC inverters at 97.18% efficiency with a 905-1,200 V MPPT window and 1,200 V DC limit. All figures reconcile directly against federal energy archives, state electrical licensing boards, California Energy Commission datasheets, and National Electrical Code engineering constants.
- AC Output (Paco)
- 2,200,000 W
- AC Voltage
- 600 V, 3-phase
- Min PV Breaker
- 2,650 A (parallel Cu feeders)
- CEC Efficiency
- 97.18%
How Does Schneider Electric USA Inc: CS2200-NA {600V} Compare Against Peer CEC Listings?
Breaker sizing (2,650 A), parallel Cu feeders wire rules, and DC input limits for Schneider Electric USA Inc: CS2200-NA {600V}.
Classified as a grid-tied PV inverter (listed since 2024-04-02), Schneider Electric USA Inc: CS2200-NA {600V} requires 2646.2 A design capacity -> 2,650 A breaker using parallel Cu feeders copper at 75 C terminals. Weighted efficiency sits at 97.18% (+0.36 pts vs overall CEC median) across 2,343 CEC models, while commercial 600 v, 3-phase switchgear interconnection uses 1,200a bus / 1,200a main (600v) or nec 705.11 supply-side tap.
Where Does Schneider Electric USA Inc: CS2200-NA {600V} Fall Across Listed CEC Models?
Output power comparison showing where Schneider Electric USA Inc: CS2200-NA {600V} sits among all 2,343 CEC-listed grid-support inverters.
What Dataset Percentiles Define Schneider Electric USA Inc: CS2200-NA {600V}?
Relative ranking of Schneider Electric USA Inc: CS2200-NA {600V} on continuous AC power, CEC weighted efficiency, and OCPD breaker current.
What Do the Dataset Ranks Show for Schneider Electric USA Inc: CS2200-NA {600V}?
Snapshot of Schneider Electric USA Inc: CS2200-NA {600V} efficiency rank (#792), OCPD breaker size, MPPT span, and busbar verdict.
97.18% CEC Weighted Efficiency
-1.10 pts vs the 98.28% 600 V median; overall power rank #94 (2,200,000 W, top 4.0%; higher than 96.0% of peers).
2,650 A Required Backfeed OCPD
125% x 2117.0 A = 2646.2 A -> 2,650 A standard OCPD using parallel Cu feeders (75 C).
905 V - 1,200 V (Max 1,200 V DC)
Tracking span of 295.0 V; listed since 2024-04-02 (grid-tied PV inverter).
Supply-Side Tap (705.11) / Dedicated Switchboard
Evaluated for 600 V, 3-phase switchgear (200A Bus / 200A Main (600V) to 1,200A Bus / 1,200A Main (600V)) under NEC 705.12 / 705.11.
NEC 705.12 Backfeed OCPD & 120% Busbar Formula
I_cont = 2200000.0W / 600 V 3-phase -> 2117.0 A | Breaker >= 1.25 * 2117.0 = 2646.2 A -> 2,650 A
CEC Inverters.csv for Schneider Electric USA Inc: CS2200-NA {600V}: Paco=2200000.0 W, Vac=600 V, Vdcmax=1200.0 V, Eff=97.18%.
Result: Min 2,650 A breaker & parallel Cu feeders (75 C); 1,200A Bus / 1,200A Main (600V): Supply-Side Tap (705.11) / Dedicated Switchboard.
What Are the Published CEC Specifications for Schneider Electric USA Inc: CS2200-NA {600V}?
Complete California Energy Commission grid-support inverter ratings and hybrid battery capabilities for Schneider Electric USA Inc: CS2200-NA {600V}.
| Parameter | Measured / Listed Value | Engineering Significance |
|---|---|---|
| Max Continuous AC Power (Paco) | 2,200,000 W | Determines required backfeed OCPD size via 125% continuous rule |
| Nominal AC Voltage (Vac) | 600 V, 3-phase | 240V split-phase residential vs. 208V/480V/MV commercial |
| Max DC Input Voltage (Vdcmax) | 1,200 V | Hard ceiling for cold-weather PV string Voc under NEC 690.7 |
| MPPT Operating Range | 905 V - 1,200 V | Optimal DC string Vmp window for full power harvest |
| Max Input DC Current (Idcmax) | 2147.75 A | Used to verify parallel string combiner limits |
| CEC Weighted Efficiency | 97.18% | Calculated AC/DC conversion ratio from CEC test protocol |
| CEC Listing Date & Hybrid | 2024-04-02 / Hybrid: No (Grid-Tied PV) | Utility interconnection approval metadata |
What Switchgear Limits Apply to Schneider Electric USA Inc: CS2200-NA {600V} (600 V, 3-phase)?
NEC 705.12(B)(3)(2) backfeed compliance table for Schneider Electric USA Inc: CS2200-NA {600V} at 600 V, 3-phase.
| Switchboard / Interconnect | 120% Max Backfeed | Required PV OCPD | Compliance Verdict |
|---|---|---|---|
| 200A Bus / 200A Main (600V) | 40 A | 2,650 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| 400A Bus / 400A Main (600V) | 80 A | 2,650 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| 600A Bus / 600A Main (600V) | 120 A | 2,650 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| 800A Bus / 800A Main (600V) | 160 A | 2,650 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| 1,200A Bus / 1,200A Main (600V) | 240 A | 2,650 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
Which CEC PV Module Strings Pair With Schneider Electric USA Inc: CS2200-NA {600V}?
Minimum and maximum series solar module strings fitting Schneider Electric USA Inc: CS2200-NA {600V} MPPT and 1,200 V limits.
| CEC Module | STC (W) | -10 C Voc | Valid String Range | Max String DC |
|---|---|---|---|---|
| Aptos Solar Technology LLC DNA-108-MFN10-440W | 440.0 W | 42.15 V | 28 panels (fixed) | 12.32 kW |
| G-Star Pte Ltd GSN8K66T(H)740WT | 740.0 W | 54.38 V | 22 panels (fixed) | 16.28 kW |
Which Competing Grid-Support Inverters Compare to Schneider Electric USA Inc: CS2200-NA {600V}?
Peer 600 V, 3-phase CEC inverters near 2,200,000 W AC output such as Power Electronics: FS2125K {600V}. All figures trace directly to published federal energy filings, state electrical boards, CEC datasheets, and NFPA 70 NEC tables.
| Alternative Inverter | AC Output | Delta | Vac | Max DC | CEC Eff |
|---|---|---|---|---|---|
| Power Electronics: FS2125K {600V} Power Electronics |
2,201,520 W | +1520 W | 600.0 V | 1200.0 V | 97.98% |
| Power Electronics: FS2000K {600V} Power Electronics |
2,103,416 W | -96584 W | 600.0 V | 1200.0 V | 97.83% |
| Delta Electronics: PCS2328S-XXX-US {600V} Delta Electronics |
2,327,940 W | +127940 W | 600.0 V | 1500.0 V | 97.96% |
| Power Electronics: FS1850CU15 {600V} Power Electronics |
2,020,960 W | -179040 W | 600.0 V | 1200.0 V | 97.74% |
What Are the Interconnection Limits and Best-Fit Uses for Schneider Electric USA Inc: CS2200-NA {600V}?
Check Schneider Electric USA Inc: CS2200-NA {600V} (2,200,000 W AC, 2,650 A OCPD) against your main panel busbar, winter string Voc, and IEEE 1547 outage rules.
- Anti-islanding shutdown: grid-tied inverters shut off within 2 seconds during blackouts under IEEE 1547 unless paired with a battery microgrid interconnect.
- Busbar 120% limit: Commercial 600 V, 3-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (600V) or NEC 705.11 supply-side tap.
- Cold Voc hard ceiling: never allow winter open-circuit PV string voltage to exceed 1,200 V DC on Schneider Electric USA Inc: CS2200-NA {600V}.
Schneider Electric USA Inc: CS2200-NA {600V} Panel & Wire Spec
Size 75 C copper conductors at parallel Cu feeders on a 2,650 A OCPD breaker (2117.0 A continuous).
Alternative Inverter Comparison
Compare efficiency (97.18%) and MPPT window (905-1,200 V) directly against Power Electronics: FS2125K {600V} (2,201,520 W).
Which Homeowner Electrical & Solar Questions Come Up Most Often?
Answers for Schneider Electric USA Inc: CS2200-NA {600V} by Schneider Electric USA Inc covering breaker sizing, MPPT limits, and 600 V, 3-phase interconnection.
What breaker and wire size does Schneider Electric USA Inc: CS2200-NA {600V} require?
At 2,200,000 W continuous AC (600 V, 3-phase), continuous current is 2117.0 A; 125% NEC 690.8/705.12 sizing requires a 2,650 A breaker and parallel Cu feeders (75 C) wire.
What commercial switchgear or feeder sizing does Schneider Electric USA Inc: CS2200-NA {600V} require?
At 2,200,000 W AC and 600 V, 3-phase, continuous line current is 2117.0 A, requiring a 2,650 A OCPD and 1,200A Bus / 1,200A Main (600V) or NEC 705.11 interconnection.
How does Schneider Electric USA Inc: CS2200-NA {600V} compare to Power Electronics: FS2125K {600V}?
Schneider Electric USA Inc: CS2200-NA {600V} delivers 2,200,000 W AC at 97.18% CEC efficiency with a 1,200 V DC ceiling, while Power Electronics: FS2125K {600V} outputs 2,201,520 W at 600 V, 3-phase.
Sources
- CEC Solar Equipment List — Grid-Support Inverters (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
- CEC Solar Equipment List — PV Modules (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
- NFPA 70 National Electrical Code (Section Numbers & Standard Engineering Tables Only) — National Fire Protection Association (NFPA), 2020 / 2023 / 2026 Editions (retrieved 2026-11-23)