NEXTRACKER LLC: NXPCS800K-HUD {800V} outputs 801,420 W AC at 800 V, 3-phase (578.4 A continuous, 750 A OCPD), ranking #357 of 2,343 CEC inverters at 97.97% efficiency with a 1,200-1,500 V MPPT window and 1,500 V DC limit. All figures reconcile directly against federal energy archives, state electrical licensing boards, California Energy Commission datasheets, and National Electrical Code engineering constants.
- AC Output (Paco)
- 801,420 W
- AC Voltage
- 800 V, 3-phase
- Min PV Breaker
- 750 A (parallel Cu feeders)
- CEC Efficiency
- 97.97%
How Does NEXTRACKER LLC: NXPCS800K-HUD {800V} Compare Against Peer CEC Listings?
NEC 705.12 breaker requirements, efficiency placement, and 800 V, 3-phase grid-support overview for NEXTRACKER LLC: NXPCS800K-HUD {800V}. Always verify current state NEC adoption cycles, local utility interconnection tariffs, and panel busbar ratings before pulling project permits.
Rated at 801,420 W AC (578.4 A continuous), NEXTRACKER LLC: NXPCS800K-HUD {800V} ranks #357 of 2,343 CEC units at 97.97% efficiency (-0.33 pts vs the 98.3% 800 V median). Minimum 75 C copper conductor sizing for its 750 A circuit is parallel Cu feeders per NEC Table 310.16. Cold-weather string Voc must remain under 1,500 V DC at record local winter lows.
Where Does NEXTRACKER LLC: NXPCS800K-HUD {800V} Fall Across Listed CEC Models?
Marks NEXTRACKER LLC: NXPCS800K-HUD {800V} (801,420 W AC) across the California Energy Commission inverter AC capacity distribution. Regional housing vintage, storm hazard frequency, and wholesale utility prices directly govern residential upgrade payback across jurisdictions.
What Dataset Percentiles Define NEXTRACKER LLC: NXPCS800K-HUD {800V}?
Benchmarks NEXTRACKER LLC: NXPCS800K-HUD {800V} continuous AC output, 97.97% CEC weighted efficiency, and 750 A OCPD breaker demand.
What Do the Dataset Ranks Show for NEXTRACKER LLC: NXPCS800K-HUD {800V}?
Four key NEC 705.12 and California Energy Commission metrics defining NEXTRACKER LLC: NXPCS800K-HUD {800V} by NEXTRACKER LLC. Review related calculators, peer benchmarks, and source citations below to validate design assumptions for your electrical service.
97.97% CEC Weighted Efficiency
-0.33 pts vs the 98.3% 800 V median; overall power rank #179 (801,420 W, top 7.6%; higher than 92.4% of peers).
750 A Required Backfeed OCPD
125% x 578.4 A = 723.0 A -> 750 A standard OCPD using parallel Cu feeders (75 C).
1,200 V - 1,500 V (Max 1,500 V DC)
Tracking span of 300.0 V; active in CEC directory (hybrid battery-capable inverter).
Supply-Side Tap (705.11) / Dedicated Switchboard
Evaluated for 800 V, 3-phase switchgear (200A Bus / 200A Main (800V) to 1,200A Bus / 1,200A Main (800V)) under NEC 705.12 / 705.11.
NEC 705.12 Backfeed OCPD & 120% Busbar Formula
I_cont = 801420.0W / 800 V 3-phase -> 578.4 A | Breaker >= 1.25 * 578.4 = 723.0 A -> 750 A
CEC Inverters.csv for NEXTRACKER LLC: NXPCS800K-HUD {800V}: Paco=801420.0 W, Vac=800 V, Vdcmax=1500.0 V, Eff=97.97%.
Result: Min 750 A breaker & parallel Cu feeders (75 C); 1,200A Bus / 1,200A Main (800V): Supply-Side Tap (705.11) / Dedicated Switchboard.
What Are the Published CEC Specifications for NEXTRACKER LLC: NXPCS800K-HUD {800V}?
Official laboratory CEC ratings, MPPT operating window, and DC voltage bounds recorded for NEXTRACKER LLC: NXPCS800K-HUD {800V}. Compare thermal ratings, overcurrent protection caps, and continuous load headroom carefully before expanding an existing home service panel.
| Parameter | Measured / Listed Value | Engineering Significance |
|---|---|---|
| Max Continuous AC Power (Paco) | 801,420 W | Determines required backfeed OCPD size via 125% continuous rule |
| Nominal AC Voltage (Vac) | 800 V, 3-phase | 240V split-phase residential vs. 208V/480V/MV commercial |
| Max DC Input Voltage (Vdcmax) | 1,500 V | Hard ceiling for cold-weather PV string Voc under NEC 690.7 |
| MPPT Operating Range | 1,200 V - 1,500 V | Optimal DC string Vmp window for full power harvest |
| Max Input DC Current (Idcmax) | 605.973 A | Used to verify parallel string combiner limits |
| CEC Weighted Efficiency | 97.97% | Calculated AC/DC conversion ratio from CEC test protocol |
| Inverter Topology | Hybrid: Yes (Battery Capable) | CEC Solar Equipment List grid-support certification |
What Switchgear Limits Apply to NEXTRACKER LLC: NXPCS800K-HUD {800V} (800 V, 3-phase)?
Evaluates NEXTRACKER LLC: NXPCS800K-HUD {800V} (750 A OCPD) across standard 100 A to 225 A busbars or commercial switchboards.
| Switchboard / Interconnect | 120% Max Backfeed | Required PV OCPD | Compliance Verdict |
|---|---|---|---|
| 200A Bus / 200A Main (800V) | 40 A | 750 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| 400A Bus / 400A Main (800V) | 80 A | 750 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| 600A Bus / 600A Main (800V) | 120 A | 750 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| 800A Bus / 800A Main (800V) | 160 A | 750 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| 1,200A Bus / 1,200A Main (800V) | 240 A | 750 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
Which Competing Grid-Support Inverters Compare to NEXTRACKER LLC: NXPCS800K-HUD {800V}?
Competing CEC grid-support inverters near 801,420 W AC and 800 V, 3-phase, led by Delta Electronics: DP350U-US-XX {800V}.
| Alternative Inverter | AC Output | Delta | Vac | Max DC | CEC Eff |
|---|---|---|---|---|---|
| Delta Electronics: DP350U-US-XX {800V} Delta Electronics |
352,401 W | -449019 W | 800.0 V | 1330.0 V | 98.48% |
| Chint Power Systems America: CPS SCH350KTL-DO/US-800 {800V} Chint Power Systems America |
350,000 W | -451420 W | 800.0 V | 1300.0 V | 98.38% |
| Ginlong Technologies Co Ltd: S6-GU350K-EHV-US-M16 {800V} Ginlong Technologies Co Ltd |
348,488 W | -452932 W | 800.0 V | 1300.0 V | 98.47% |
| Ginlong Technologies Co Ltd: S6-GU350K-EHV-US-M12 {800V} Ginlong Technologies Co Ltd |
348,153 W | -453267 W | 800.0 V | 1300.0 V | 98.47% |
What Are the Interconnection Limits and Best-Fit Uses for NEXTRACKER LLC: NXPCS800K-HUD {800V}?
Check NEXTRACKER LLC: NXPCS800K-HUD {800V} (801,420 W AC, 750 A OCPD) against your main panel busbar, winter string Voc, and IEEE 1547 outage rules.
- Anti-islanding shutdown: grid-tied inverters shut off within 2 seconds during blackouts under IEEE 1547 unless paired with a battery microgrid interconnect.
- Busbar 120% limit: Commercial 800 V, 3-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (800V) or NEC 705.11 supply-side tap.
- Cold Voc hard ceiling: never allow winter open-circuit PV string voltage to exceed 1,500 V DC on NEXTRACKER LLC: NXPCS800K-HUD {800V}.
NEXTRACKER LLC: NXPCS800K-HUD {800V} Panel & Wire Spec
Size 75 C copper conductors at parallel Cu feeders on a 750 A OCPD breaker (578.4 A continuous).
Alternative Inverter Comparison
Compare efficiency (97.97%) and MPPT window (1,200-1,500 V) directly against Delta Electronics: DP350U-US-XX {800V} (352,401 W).
Which Homeowner Electrical & Solar Questions Come Up Most Often?
Answers for NEXTRACKER LLC: NXPCS800K-HUD {800V} by NEXTRACKER LLC covering breaker sizing, MPPT limits, and 800 V, 3-phase interconnection.
What breaker and wire size does NEXTRACKER LLC: NXPCS800K-HUD {800V} require?
At 801,420 W continuous AC (800 V, 3-phase), continuous current is 578.4 A; 125% NEC 690.8/705.12 sizing requires a 750 A breaker and parallel Cu feeders (75 C) wire.
What commercial switchgear or feeder sizing does NEXTRACKER LLC: NXPCS800K-HUD {800V} require?
At 801,420 W AC and 800 V, 3-phase, continuous line current is 578.4 A, requiring a 750 A OCPD and 1,200A Bus / 1,200A Main (800V) or NEC 705.11 interconnection.
How does NEXTRACKER LLC: NXPCS800K-HUD {800V} compare to Delta Electronics: DP350U-US-XX {800V}?
NEXTRACKER LLC: NXPCS800K-HUD {800V} delivers 801,420 W AC at 97.97% CEC efficiency with a 1,500 V DC ceiling, while Delta Electronics: DP350U-US-XX {800V} outputs 352,401 W at 800 V, 3-phase.