Hyperian Energy Inc: ST2-114i {240V} outputs 11,371 W AC at 240 V (47.4 A continuous, 60 A OCPD), ranking #906 of 2,343 CEC inverters at 97.08% efficiency with a 300-440 V MPPT window and 440 V DC limit. All figures reconcile directly against federal energy archives, state electrical licensing boards, California Energy Commission datasheets, and National Electrical Code engineering constants.
- AC Output (Paco)
- 11,371 W
- AC Voltage
- 240 V
- Min PV Breaker
- 60 A (6 AWG Cu)
- CEC Efficiency
- 97.08%
How Does Hyperian Energy Inc: ST2-114i {240V} Compare Against Peer CEC Listings?
How Hyperian Energy Inc Hyperian Energy Inc: ST2-114i {240V} compares on 97.08% efficiency, MPPT span, and 120% busbar interconnection.
Hyperian Energy Inc certifies Hyperian Energy Inc: ST2-114i {240V} (hybrid battery-capable inverter, active in CEC directory) at 11,371 W AC (5,595 W above the 5,776 W 240 V median). Its 440 V DC ceiling pairs with an MPPT window of 300-440 V (span 140.0 V). Under NEC 690.8/705.12, 125% sizing demands 6 AWG Cu conductors on a 60 A OCPD.
Where Does Hyperian Energy Inc: ST2-114i {240V} Fall Across Listed CEC Models?
Position of Hyperian Energy Inc: ST2-114i {240V} (11,371 W AC) relative to the 7,680 W CEC median inverter.
What Dataset Percentiles Define Hyperian Energy Inc: ST2-114i {240V}?
Percentile placement of Hyperian Energy Inc: ST2-114i {240V} across AC power class, conversion efficiency, and backfeed breaker size.
What Do the Dataset Ranks Show for Hyperian Energy Inc: ST2-114i {240V}?
Primary electrical sizing limits, efficiency ranks, and NEC 705.12 / 690.7 thresholds for Hyperian Energy Inc: ST2-114i {240V}. Every reported metric links directly to federal public records or state regulatory filings with zero paid contractor placements.
97.08% CEC Weighted Efficiency
+0.40 pts vs the 96.68% 240 V median; overall power rank #792 (11,371 W, top 33.8%; higher than 66.2% of peers).
60 A Required Backfeed OCPD
125% x 47.4 A = 59.2 A -> 60 A standard OCPD using 6 AWG Cu (75 C).
300 V - 440 V (Max 440 V DC)
Tracking span of 140.0 V; active in CEC directory (hybrid battery-capable inverter).
Needs Derate / Tap 705.11
200A/200A panel allows 40A PV backfeed; 200A/175A derate allows 65A; 225A/200A allows 70A.
NEC 705.12 Backfeed OCPD & 120% Busbar Formula
I_cont = 11371.0W / 240 V -> 47.4 A | Breaker >= 1.25 * 47.4 = 59.2 A -> 60 A
CEC Inverters.csv for Hyperian Energy Inc: ST2-114i {240V}: Paco=11371.0 W, Vac=240 V, Vdcmax=440.0 V, Eff=97.08%.
Result: Min 60 A breaker & 6 AWG Cu (75 C); 200A Bus / 200A Main: Needs Derate / Tap 705.11.
What Are the Published CEC Specifications for Hyperian Energy Inc: ST2-114i {240V}?
Official California Energy Commission electrical test parameters, AC voltage, and DC limits for Hyperian Energy Inc: ST2-114i {240V}.
| Parameter | Measured / Listed Value | Engineering Significance |
|---|---|---|
| Max Continuous AC Power (Paco) | 11,371 W | Determines required backfeed OCPD size via 125% continuous rule |
| Nominal AC Voltage (Vac) | 240 V | 240V split-phase residential vs. 208V/480V/MV commercial |
| Max DC Input Voltage (Vdcmax) | 440 V | Hard ceiling for cold-weather PV string Voc under NEC 690.7 |
| MPPT Operating Range | 300 V - 440 V | Optimal DC string Vmp window for full power harvest |
| Max Input DC Current (Idcmax) | 31.657 A | Used to verify parallel string combiner limits |
| CEC Weighted Efficiency | 97.08% | Calculated AC/DC conversion ratio from CEC test protocol |
| Inverter Topology | Hybrid: Yes (Battery Capable) | CEC Solar Equipment List grid-support certification |
Can a Residential Panel Meet 120% Busbar Limits for Hyperian Energy Inc: ST2-114i {240V}?
Check whether Hyperian Energy Inc: ST2-114i {240V} (60 A breaker) fits without main breaker derate or supply-side taps.
| Panel Configuration | 120% Max Backfeed | Required PV OCPD | Compliance Verdict |
|---|---|---|---|
| 100A Bus / 100A Main | 20 A | 60 A | Needs Derate / Tap 705.11 |
| 150A Bus / 150A Main | 30 A | 60 A | Needs Derate / Tap 705.11 |
| 200A Bus / 200A Main | 40 A | 60 A | Needs Derate / Tap 705.11 |
| 200A Bus / 175A Main | 65 A | 60 A | PASS (120% Rule) |
| 225A Bus / 200A Main | 70 A | 60 A | PASS (120% Rule) |
Which CEC PV Module Strings Pair With Hyperian Energy Inc: ST2-114i {240V}?
Verified cold-weather (-10 C) series module counts matched to Hyperian Energy Inc: ST2-114i {240V}'s 440 V DC ceiling.
| CEC Module | STC (W) | -10 C Voc | Valid String Range | Max String DC |
|---|---|---|---|---|
| AXITEC AC-590TGB/144TS | 590.0 W | 56.24 V | 7 panels (fixed) | 4.13 kW |
| Aptos Solar Technology LLC DNA-108-MFN10-440W | 440.0 W | 42.15 V | 9 to 10 panels | 4.4 kW |
| Boviet Solar Technology Co Ltd BVM7610M-425-H-HC-BF | 425.0 W | 44.75 V | 9 panels (fixed) | 3.83 kW |
| Chint New Energy Technology Co Ltd CHSM72M(DG)/F-BH-515 | 515.0 W | 53.76 V | 8 panels (fixed) | 4.12 kW |
Which Competing Grid-Support Inverters Compare to Hyperian Energy Inc: ST2-114i {240V}?
Alternative CEC inverters comparable to Hyperian Energy Inc: ST2-114i {240V}, including Chint Power Systems America: CPS ECH114KTL/US {240V} (11,360 W) at 240 V.
| Alternative Inverter | AC Output | Delta | Vac | Max DC | CEC Eff |
|---|---|---|---|---|---|
| Chint Power Systems America: CPS ECH114KTL/US {240V} Chint Power Systems America |
11,360 W | -11 W | 240.0 V | 480.0 V | 96.53% |
| Altenergy Power System Inc: ELS-114 {240V} Altenergy Power System Inc |
11,415 W | +44 W | 240.0 V | 60.0 V | 93.08% |
| Dyness Digital Energy Technology Co LTD: TX114K-HM {240V} Dyness Digital Energy Technology Co LTD |
11,498 W | +127 W | 240.0 V | 500.0 V | 96.41% |
| Dyness Digital Energy Technology Co LTD: TX114K-AM {240V} Dyness Digital Energy Technology Co LTD |
11,519 W | +148 W | 240.0 V | 490.0 V | 96.21% |
What Are the Interconnection Limits and Best-Fit Uses for Hyperian Energy Inc: ST2-114i {240V}?
Check Hyperian Energy Inc: ST2-114i {240V} (11,371 W AC, 60 A OCPD) against your main panel busbar, winter string Voc, and IEEE 1547 outage rules.
- Anti-islanding shutdown: grid-tied inverters shut off within 2 seconds during blackouts under IEEE 1547 unless paired with a battery microgrid interconnect.
- Busbar 120% limit: Its 60 A backfeed breaker exceeds a 200A/200A panel's 40 A ceiling, requiring a 175 A main derate, 225 A busbar, or NEC 705.11 tap.
- Cold Voc hard ceiling: never allow winter open-circuit PV string voltage to exceed 440 V DC on Hyperian Energy Inc: ST2-114i {240V}.
Hyperian Energy Inc: ST2-114i {240V} Panel & Wire Spec
Size 75 C copper conductors at 6 AWG Cu on a 60 A OCPD breaker (47.4 A continuous).
Alternative Inverter Comparison
Compare efficiency (97.08%) and MPPT window (300-440 V) directly against Chint Power Systems America: CPS ECH114KTL/US {240V} (11,360 W).
Which Homeowner Electrical & Solar Questions Come Up Most Often?
Answers for Hyperian Energy Inc: ST2-114i {240V} by Hyperian Energy Inc covering breaker sizing, MPPT limits, and 240 V interconnection.
What breaker and wire size does Hyperian Energy Inc: ST2-114i {240V} require?
At 11,371 W continuous AC (240 V), continuous current is 47.4 A; 125% NEC 690.8/705.12 sizing requires a 60 A breaker and 6 AWG Cu (75 C) wire.
Does Hyperian Energy Inc: ST2-114i {240V} fit a 200 A main panel under the 120% busbar rule?
A 200 A busbar with a 200 A main allows 40 A of solar backfeed. Requiring 60 A at 240 V means Needs Derate / Tap 705.11.
How does Hyperian Energy Inc: ST2-114i {240V} compare to Chint Power Systems America: CPS ECH114KTL/US {240V}?
Hyperian Energy Inc: ST2-114i {240V} delivers 11,371 W AC at 97.08% CEC efficiency with a 440 V DC ceiling, while Chint Power Systems America: CPS ECH114KTL/US {240V} outputs 11,360 W at 240 V.