Hoymiles Power Electronics Inc: HAS-115LV-USG1 {240V} outputs 9,153 W AC at 240 V (38.1 A continuous, 50 A OCPD), ranking #2,313 of 2,343 CEC inverters at 94.14% efficiency with a 50-60 V MPPT window and 60 V DC limit. All figures reconcile directly against federal energy archives, state electrical licensing boards, California Energy Commission datasheets, and National Electrical Code engineering constants.
- AC Output (Paco)
- 9,153 W
- AC Voltage
- 240 V
- Min PV Breaker
- 50 A (8 AWG Cu)
- CEC Efficiency
- 94.14%
How Does Hoymiles Power Electronics Inc: HAS-115LV-USG1 {240V} Compare Against Peer CEC Listings?
NEC 705.12 breaker requirements, efficiency placement, and 240 V grid-support overview for Hoymiles Power Electronics Inc: HAS-115LV-USG1 {240V}.
Ranking #1,007 of 2,343 CEC inverters (top 43.0%; higher than 57.0% of peers), Hoymiles Power Electronics Inc: HAS-115LV-USG1 {240V} is a grid-tied PV inverter delivering 9,153 W continuous AC at 240 V (38.1 A continuous). Its 50 A backfeed breaker exceeds a 200A/200A panel's 40 A ceiling, requiring a 175 A main derate, 225 A busbar, or NEC 705.11 tap. Weighted CEC efficiency reaches 94.14% (-2.54 pts vs the 96.68% 240 V median) against peers like Base Power Inc: MIN 9000TL-XH-US {240V} (9,063 W).
Where Does Hoymiles Power Electronics Inc: HAS-115LV-USG1 {240V} Fall Across Listed CEC Models?
Marks Hoymiles Power Electronics Inc: HAS-115LV-USG1 {240V} (9,153 W AC) across the California Energy Commission inverter AC capacity distribution.
What Dataset Percentiles Define Hoymiles Power Electronics Inc: HAS-115LV-USG1 {240V}?
Benchmarks Hoymiles Power Electronics Inc: HAS-115LV-USG1 {240V} continuous AC output, 94.14% CEC weighted efficiency, and 50 A OCPD breaker demand.
What Do the Dataset Ranks Show for Hoymiles Power Electronics Inc: HAS-115LV-USG1 {240V}?
Four key NEC 705.12 and California Energy Commission metrics defining Hoymiles Power Electronics Inc: HAS-115LV-USG1 {240V} by Hoymiles Power Electronics Inc.
94.14% CEC Weighted Efficiency
-2.54 pts vs the 96.68% 240 V median; overall power rank #1,007 (9,153 W, top 43.0%; higher than 57.0% of peers).
50 A Required Backfeed OCPD
125% x 38.1 A = 47.6 A -> 50 A standard OCPD using 8 AWG Cu (75 C).
50 V - 60 V (Max 60 V DC)
Tracking span of 10.0 V; listed since 2024-08-12 (grid-tied PV inverter).
Needs Derate / Tap 705.11
200A/200A panel allows 40A PV backfeed; 200A/175A derate allows 65A; 225A/200A allows 70A.
NEC 705.12 Backfeed OCPD & 120% Busbar Formula
I_cont = 9153.0W / 240 V -> 38.1 A | Breaker >= 1.25 * 38.1 = 47.6 A -> 50 A
CEC Inverters.csv for Hoymiles Power Electronics Inc: HAS-115LV-USG1 {240V}: Paco=9153.0 W, Vac=240 V, Vdcmax=60.0 V, Eff=94.14%.
Result: Min 50 A breaker & 8 AWG Cu (75 C); 200A Bus / 200A Main: Needs Derate / Tap 705.11.
What Are the Published CEC Specifications for Hoymiles Power Electronics Inc: HAS-115LV-USG1 {240V}?
Official laboratory CEC ratings, MPPT operating window, and DC voltage bounds recorded for Hoymiles Power Electronics Inc: HAS-115LV-USG1 {240V}.
| Parameter | Measured / Listed Value | Engineering Significance |
|---|---|---|
| Max Continuous AC Power (Paco) | 9,153 W | Determines required backfeed OCPD size via 125% continuous rule |
| Nominal AC Voltage (Vac) | 240 V | 240V split-phase residential vs. 208V/480V/MV commercial |
| Max DC Input Voltage (Vdcmax) | 60 V | Hard ceiling for cold-weather PV string Voc under NEC 690.7 |
| MPPT Operating Range | 50 V - 60 V | Optimal DC string Vmp window for full power harvest |
| Max Input DC Current (Idcmax) | 176.771 A | Used to verify parallel string combiner limits |
| CEC Weighted Efficiency | 94.14% | Calculated AC/DC conversion ratio from CEC test protocol |
| CEC Listing Date & Hybrid | 2024-08-12 / Hybrid: No (Grid-Tied PV) | Utility interconnection approval metadata |
Can a Residential Panel Meet 120% Busbar Limits for Hoymiles Power Electronics Inc: HAS-115LV-USG1 {240V}?
Evaluates Hoymiles Power Electronics Inc: HAS-115LV-USG1 {240V} (50 A OCPD) across standard 100 A to 225 A busbars or commercial switchboards.
| Panel Configuration | 120% Max Backfeed | Required PV OCPD | Compliance Verdict |
|---|---|---|---|
| 100A Bus / 100A Main | 20 A | 50 A | Needs Derate / Tap 705.11 |
| 150A Bus / 150A Main | 30 A | 50 A | Needs Derate / Tap 705.11 |
| 200A Bus / 200A Main | 40 A | 50 A | Needs Derate / Tap 705.11 |
| 200A Bus / 175A Main | 65 A | 50 A | PASS (120% Rule) |
| 225A Bus / 200A Main | 70 A | 50 A | PASS (120% Rule) |
Which CEC PV Module Strings Pair With Hoymiles Power Electronics Inc: HAS-115LV-USG1 {240V}?
Sample PV string lengths aligned within 50-60 V MPPT and 60 V DC max at -10 C. Inspect manufacturer nameplate documentation, UL listing boundaries, and utility rate schedules closely before ordering electrical hardware.
| CEC Module | STC (W) | -10 C Voc | Valid String Range | Max String DC |
|---|---|---|---|---|
| AXITEC AC-590TGB/144TS | 590.0 W | 56.24 V | 1 panel (micro/module) | 0.59 kW |
| Aptos Solar Technology LLC DNA-108-MFN10-440W | 440.0 W | 42.15 V | 1 panel (micro/module) | 0.44 kW |
| Boviet Solar Technology Co Ltd BVM7610M-425-H-HC-BF | 425.0 W | 44.75 V | 1 panel (micro/module) | 0.42 kW |
| CSI Solar Co Ltd CS6P-200P | 200.0 W | 40.6 V | 1 panel (micro/module) | 0.2 kW |
Which Competing Grid-Support Inverters Compare to Hoymiles Power Electronics Inc: HAS-115LV-USG1 {240V}?
Competing CEC grid-support inverters near 9,153 W AC and 240 V, led by Base Power Inc: MIN 9000TL-XH-US {240V}.
| Alternative Inverter | AC Output | Delta | Vac | Max DC | CEC Eff |
|---|---|---|---|---|---|
| Base Power Inc: MIN 9000TL-XH-US {240V} Base Power Inc |
9,063 W | -90 W | 240.0 V | 480.0 V | 97.69% |
| Chint Power Systems America: CPS ECH96KTL/US {240V} Chint Power Systems America |
9,540 W | +387 W | 240.0 V | 480.0 V | 96.61% |
| Afore New Energy Technology (Shanghai) Co Ltd: AF96K-DH {240V} Afore New Energy Technology (Shanghai) Co Ltd |
9,592 W | +439 W | 240.0 V | 480.0 V | 97.87% |
| AIMS Power Inc: PIHY9600 {240V} AIMS Power Inc |
9,592 W | +439 W | 240.0 V | 480.0 V | 97.87% |
What Are the Interconnection Limits and Best-Fit Uses for Hoymiles Power Electronics Inc: HAS-115LV-USG1 {240V}?
Check Hoymiles Power Electronics Inc: HAS-115LV-USG1 {240V} (9,153 W AC, 50 A OCPD) against your main panel busbar, winter string Voc, and IEEE 1547 outage rules.
- Anti-islanding shutdown: grid-tied inverters shut off within 2 seconds during blackouts under IEEE 1547 unless paired with a battery microgrid interconnect.
- Busbar 120% limit: Its 50 A backfeed breaker exceeds a 200A/200A panel's 40 A ceiling, requiring a 175 A main derate, 225 A busbar, or NEC 705.11 tap.
- Cold Voc hard ceiling: never allow winter open-circuit PV string voltage to exceed 60 V DC on Hoymiles Power Electronics Inc: HAS-115LV-USG1 {240V}.
Hoymiles Power Electronics Inc: HAS-115LV-USG1 {240V} Panel & Wire Spec
Size 75 C copper conductors at 8 AWG Cu on a 50 A OCPD breaker (38.1 A continuous).
Alternative Inverter Comparison
Compare efficiency (94.14%) and MPPT window (50-60 V) directly against Base Power Inc: MIN 9000TL-XH-US {240V} (9,063 W).
Which Homeowner Electrical & Solar Questions Come Up Most Often?
Answers for Hoymiles Power Electronics Inc: HAS-115LV-USG1 {240V} by Hoymiles Power Electronics Inc covering breaker sizing, MPPT limits, and 240 V interconnection.
What breaker and wire size does Hoymiles Power Electronics Inc: HAS-115LV-USG1 {240V} require?
At 9,153 W continuous AC (240 V), continuous current is 38.1 A; 125% NEC 690.8/705.12 sizing requires a 50 A breaker and 8 AWG Cu (75 C) wire.
Does Hoymiles Power Electronics Inc: HAS-115LV-USG1 {240V} fit a 200 A main panel under the 120% busbar rule?
A 200 A busbar with a 200 A main allows 40 A of solar backfeed. Requiring 50 A at 240 V means Needs Derate / Tap 705.11.
How does Hoymiles Power Electronics Inc: HAS-115LV-USG1 {240V} compare to Base Power Inc: MIN 9000TL-XH-US {240V}?
Hoymiles Power Electronics Inc: HAS-115LV-USG1 {240V} delivers 9,153 W AC at 94.14% CEC efficiency with a 60 V DC ceiling, while Base Power Inc: MIN 9000TL-XH-US {240V} outputs 9,063 W at 240 V.
Sources
- CEC Solar Equipment List — Grid-Support Inverters (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
- CEC Solar Equipment List — PV Modules (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
- NFPA 70 National Electrical Code (Section Numbers & Standard Engineering Tables Only) — National Fire Protection Association (NFPA), 2020 / 2023 / 2026 Editions (retrieved 2026-11-23)