Apparent Inc: SG424U CA 120VAC 60Hz {120V} outputs 250 W AC at 120 V (2.1 A continuous, 15 A OCPD), ranking #2,336 of 2,343 CEC inverters at 91.11% efficiency with a 31.2-48.9 V MPPT window and 48.9 V DC limit. All figures reconcile directly against federal energy archives, state electrical licensing boards, California Energy Commission datasheets, and National Electrical Code engineering constants.
- AC Output (Paco)
- 250 W
- AC Voltage
- 120 V
- Min PV Breaker
- 15 A (14 AWG Cu)
- CEC Efficiency
- 91.11%
How Does Apparent Inc: SG424U CA 120VAC 60Hz {120V} Compare Against Peer CEC Listings?
Breaker sizing (15 A), 14 AWG Cu wire rules, and DC input limits for Apparent Inc: SG424U CA 120VAC 60Hz {120V}.
Classified as a grid-tied PV inverter (listed since 2022-08-22), Apparent Inc: SG424U CA 120VAC 60Hz {120V} requires 2.6 A design capacity -> 15 A breaker using 14 AWG Cu copper at 75 C terminals. Weighted efficiency sits at 91.11% (-5.71 pts vs overall CEC median) across 2,343 CEC models, while module-level microinverter output eliminates high-voltage dc rooftop strings and connects via a 240v ac trunk circuit.
Where Does Apparent Inc: SG424U CA 120VAC 60Hz {120V} Fall Across Listed CEC Models?
Output power comparison showing where Apparent Inc: SG424U CA 120VAC 60Hz {120V} sits among all 2,343 CEC-listed grid-support inverters.
What Dataset Percentiles Define Apparent Inc: SG424U CA 120VAC 60Hz {120V}?
Relative ranking of Apparent Inc: SG424U CA 120VAC 60Hz {120V} on continuous AC power, CEC weighted efficiency, and OCPD breaker current.
What Do the Dataset Ranks Show for Apparent Inc: SG424U CA 120VAC 60Hz {120V}?
Snapshot of Apparent Inc: SG424U CA 120VAC 60Hz {120V} efficiency rank (#2,336), OCPD breaker size, MPPT span, and busbar verdict.
91.11% CEC Weighted Efficiency
-3.62 pts vs the 94.73% 120 V median; overall power rank #2,309 (250 W, below CEC median; higher than 1.5% of peers).
15 A Required Backfeed OCPD
125% x 2.1 A = 2.6 A -> 15 A standard OCPD using 14 AWG Cu (75 C).
31.2 V - 48.9 V (Max 48.9 V DC)
Tracking span of 17.7 V; listed since 2022-08-22 (grid-tied PV inverter).
120V AC Coupled / Dedicated Transformer
200A/200A panel allows 40A PV backfeed; 200A/175A derate allows 65A; 225A/200A allows 70A.
NEC 705.12 Backfeed OCPD & 120% Busbar Formula
I_cont = 250.0W / 120 V -> 2.1 A | Breaker >= 1.25 * 2.1 = 2.6 A -> 15 A
CEC Inverters.csv for Apparent Inc: SG424U CA 120VAC 60Hz {120V}: Paco=250.0 W, Vac=120 V, Vdcmax=48.9 V, Eff=91.11%.
Result: Min 15 A breaker & 14 AWG Cu (75 C); 200A Bus / 200A Main: 120V AC Coupled / Dedicated Transformer.
What Are the Published CEC Specifications for Apparent Inc: SG424U CA 120VAC 60Hz {120V}?
Complete California Energy Commission grid-support inverter ratings and hybrid battery capabilities for Apparent Inc: SG424U CA 120VAC 60Hz {120V}.
| Parameter | Measured / Listed Value | Engineering Significance |
|---|---|---|
| Max Continuous AC Power (Paco) | 250 W | Determines required backfeed OCPD size via 125% continuous rule |
| Nominal AC Voltage (Vac) | 120 V | 240V split-phase residential vs. 208V/480V/MV commercial |
| Max DC Input Voltage (Vdcmax) | 48.9 V | Hard ceiling for cold-weather PV string Voc under NEC 690.7 |
| MPPT Operating Range | 31.2 V - 48.9 V | Optimal DC string Vmp window for full power harvest |
| Max Input DC Current (Idcmax) | 7.53858 A | Used to verify parallel string combiner limits |
| CEC Weighted Efficiency | 91.11% | Calculated AC/DC conversion ratio from CEC test protocol |
| CEC Listing Date & Hybrid | 2022-08-22 / Hybrid: No (Grid-Tied PV) | Utility interconnection approval metadata |
Can a Residential Panel Meet 120% Busbar Limits for Apparent Inc: SG424U CA 120VAC 60Hz {120V}?
NEC 705.12(B)(3)(2) backfeed compliance table for Apparent Inc: SG424U CA 120VAC 60Hz {120V} at 120 V.
| Panel Configuration | 120% Max Backfeed | Required PV OCPD | Compliance Verdict |
|---|---|---|---|
| 100A Bus / 100A Main | 20 A | 15 A | 120V AC Coupled / Dedicated Transformer |
| 150A Bus / 150A Main | 30 A | 15 A | 120V AC Coupled / Dedicated Transformer |
| 200A Bus / 200A Main | 40 A | 15 A | 120V AC Coupled / Dedicated Transformer |
| 200A Bus / 175A Main | 65 A | 15 A | 120V AC Coupled / Dedicated Transformer |
| 225A Bus / 200A Main | 70 A | 15 A | 120V AC Coupled / Dedicated Transformer |
Which CEC PV Module Strings Pair With Apparent Inc: SG424U CA 120VAC 60Hz {120V}?
Minimum and maximum series solar module strings fitting Apparent Inc: SG424U CA 120VAC 60Hz {120V} MPPT and 48.9 V limits.
| CEC Module | STC (W) | -10 C Voc | Valid String Range | Max String DC |
|---|---|---|---|---|
| Aptos Solar Technology LLC DNA-108-MFN10-440W | 440.0 W | 42.15 V | 1 panel (micro/module) | 0.44 kW |
| Boviet Solar Technology Co Ltd BVM7610M-425-H-HC-BF | 425.0 W | 44.75 V | 1 panel (micro/module) | 0.42 kW |
| CSI Solar Co Ltd CS6P-200P | 200.0 W | 40.6 V | 1 panel (micro/module) | 0.2 kW |
| Hanwha Qcells (Qidong) Co Ltd HSL60P6-PB-0-270TW | 270.0 W | 42.56 V | 1 panel (micro/module) | 0.27 kW |
Which Competing Grid-Support Inverters Compare to Apparent Inc: SG424U CA 120VAC 60Hz {120V}?
Peer 120 V CEC inverters near 250 W AC output such as Altenergy Power System Inc: DS3-LV {120V}.
| Alternative Inverter | AC Output | Delta | Vac | Max DC | CEC Eff |
|---|---|---|---|---|---|
| Altenergy Power System Inc: DS3-LV {120V} Altenergy Power System Inc |
915 W | +665 W | 120.0 V | 45.0 V | 94.08% |
| Altenergy Power System Inc: EZ1-LV {120V} Altenergy Power System Inc |
915 W | +665 W | 120.0 V | 45.0 V | 94.08% |
| Northern Electric & Power Co Ltd: BDM-1200-LV {120V} Northern Electric & Power Co Ltd |
1,194 W | +944 W | 120.0 V | 55.0 V | 96.23% |
| Northern Electric & Power Co Ltd: BDM-1600-LV {120V} Northern Electric & Power Co Ltd |
1,597 W | +1347 W | 120.0 V | 55.0 V | 96.31% |
What Are the Interconnection Limits and Best-Fit Uses for Apparent Inc: SG424U CA 120VAC 60Hz {120V}?
Check Apparent Inc: SG424U CA 120VAC 60Hz {120V} (250 W AC, 15 A OCPD) against your main panel busbar, winter string Voc, and IEEE 1547 outage rules.
- Anti-islanding shutdown: grid-tied inverters shut off within 2 seconds during blackouts under IEEE 1547 unless paired with a battery microgrid interconnect.
- Busbar 120% limit: Module-level microinverter output eliminates high-voltage DC rooftop strings and connects via a 240V AC trunk circuit.
- Cold Voc hard ceiling: never allow winter open-circuit PV string voltage to exceed 48.9 V DC on Apparent Inc: SG424U CA 120VAC 60Hz {120V}.
Apparent Inc: SG424U CA 120VAC 60Hz {120V} Panel & Wire Spec
Size 75 C copper conductors at 14 AWG Cu on a 15 A OCPD breaker (2.1 A continuous).
Alternative Inverter Comparison
Compare efficiency (91.11%) and MPPT window (31.2-48.9 V) directly against Altenergy Power System Inc: DS3-LV {120V} (915 W).
Which Homeowner Electrical & Solar Questions Come Up Most Often?
Answers for Apparent Inc: SG424U CA 120VAC 60Hz {120V} by Apparent Inc covering breaker sizing, MPPT limits, and 120 V interconnection.
What breaker and wire size does Apparent Inc: SG424U CA 120VAC 60Hz {120V} require?
At 250 W continuous AC (120 V), continuous current is 2.1 A; 125% NEC 690.8/705.12 sizing requires a 15 A breaker and 14 AWG Cu (75 C) wire.
Does Apparent Inc: SG424U CA 120VAC 60Hz {120V} fit a 200 A main panel under the 120% busbar rule?
A 200 A busbar with a 200 A main allows 40 A of solar backfeed. Requiring 15 A at 120 V means 120V AC Coupled / Dedicated Transformer.
How does Apparent Inc: SG424U CA 120VAC 60Hz {120V} compare to Altenergy Power System Inc: DS3-LV {120V}?
Apparent Inc: SG424U CA 120VAC 60Hz {120V} delivers 250 W AC at 91.11% CEC efficiency with a 48.9 V DC ceiling, while Altenergy Power System Inc: DS3-LV {120V} outputs 915 W at 120 V.
Sources
- CEC Solar Equipment List — Grid-Support Inverters (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
- CEC Solar Equipment List — PV Modules (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
- NFPA 70 National Electrical Code (Section Numbers & Standard Engineering Tables Only) — National Fire Protection Association (NFPA), 2020 / 2023 / 2026 Editions (retrieved 2026-11-23)