Manufacturer: Altenergy Power System Inc Registry: CEC Verified Engineering Specification

Altenergy Power System Inc: QS2 {208V} outputs 1,923 W AC at 208 V, commercial single-phase (9.2 A continuous, 15 A OCPD), ranking #2,272 of 2,343 CEC inverters at 94.73% efficiency with a 30-45 V MPPT window and 45 V DC limit. All figures reconcile directly against federal energy archives, state electrical licensing boards, California Energy Commission datasheets, and National Electrical Code engineering constants.

AC Output (Paco)
1,923 W
AC Voltage
208 V, commercial single-phase
Min PV Breaker
15 A (14 AWG Cu)
CEC Efficiency
94.73%
Wall-mounted residential hybrid solar inverter and modular battery cabinet piped with galvanized EMT conduit
Wall-mounted residential hybrid solar inverter and modular battery cabinet piped with galvanized EMT conduit

How Does Altenergy Power System Inc: QS2 {208V} Compare Against Peer CEC Listings?

Breaker sizing (15 A), 14 AWG Cu wire rules, and DC input limits for Altenergy Power System Inc: QS2 {208V}.

Classified as a grid-tied PV inverter (active in CEC directory), Altenergy Power System Inc: QS2 {208V} requires 11.5 A design capacity -> 15 A breaker using 14 AWG Cu copper at 75 C terminals. Weighted efficiency sits at 94.73% (-2.09 pts vs overall CEC median) across 2,343 CEC models, while commercial 208 v, commercial single-phase switchgear interconnection uses 1,200a bus / 1,200a main (208v) or nec 705.11 supply-side tap.

Where Does Altenergy Power System Inc: QS2 {208V} Fall Across Listed CEC Models?

Output power comparison showing where Altenergy Power System Inc: QS2 {208V} sits among all 2,343 CEC-listed grid-support inverters.

AC Power Distribution Across Listed CEC Inverters (up to 25 kW)Shows where Altenergy Power System Inc: QS2 {208V} (1,923 W AC) sits across CEC inverters. 190-2258 W AC: 584 entries1902258-4325 W AC: 158 entries4325-6392 W AC: 259 entries6392-8460 W AC: 270 entries63928460-10528 W AC: 258 entries10528-12595 W AC: 116 entries12595-14662 W AC: 17 entries1259514662-16730 W AC: 37 entries16730-18798 W AC: 7 entries18798-20865 W AC: 11 entries1879820865-22932 W AC: 5 entries22932-25000 W AC: 26 entries22932Median 7,680 W ACAltenergy Power Sy: 1,923 W

What Dataset Percentiles Define Altenergy Power System Inc: QS2 {208V}?

Relative ranking of Altenergy Power System Inc: QS2 {208V} on continuous AC power, CEC weighted efficiency, and OCPD breaker current.

Altenergy Power System Inc: QS2 {208V} Technical ThresholdsPercentile comparison for Altenergy Power System Inc: QS2 {208V} AC output, weighted CEC efficiency, and OCPD sizing. 0% (Low)50% Median100% (Top)Rated AC Output1,923 WCEC Efficiency94.73%Backfeed Breaker15 A

What Do the Dataset Ranks Show for Altenergy Power System Inc: QS2 {208V}?

Snapshot of Altenergy Power System Inc: QS2 {208V} efficiency rank (#2,272), OCPD breaker size, MPPT span, and busbar verdict.

Eff #2,272 / 2,343

94.73% CEC Weighted Efficiency

-1.68 pts vs the 96.41% 208 V median; overall power rank #1,764 (1,923 W, below CEC median; higher than 24.7% of peers).

NEC 705.12 Check

15 A Required Backfeed OCPD

125% x 9.2 A = 11.5 A -> 15 A standard OCPD using 14 AWG Cu (75 C).

MPPT Window

30 V - 45 V (Max 45 V DC)

Tracking span of 15.0 V; active in CEC directory (grid-tied PV inverter).

Commercial / 3-Phase Fit

PASS (120% Commercial Busbar)

Evaluated for 208 V, commercial single-phase switchgear (200A Bus / 200A Main (208V) to 1,200A Bus / 1,200A Main (208V)) under NEC 705.12 / 705.11.

NEC 705.12 Backfeed OCPD & 120% Busbar Formula

I_cont = 1922.6W / 208 V -> 9.2 A | Breaker >= 1.25 * 9.2 = 11.5 A -> 15 A

CEC Inverters.csv for Altenergy Power System Inc: QS2 {208V}: Paco=1922.6 W, Vac=208 V, Vdcmax=45.0 V, Eff=94.73%.

Result: Min 15 A breaker & 14 AWG Cu (75 C); 1,200A Bus / 1,200A Main (208V): PASS (120% Commercial Busbar).

What Are the Published CEC Specifications for Altenergy Power System Inc: QS2 {208V}?

Complete California Energy Commission grid-support inverter ratings and hybrid battery capabilities for Altenergy Power System Inc: QS2 {208V}.

Official California Energy Commission (NREL SAM) test parameters for Altenergy Power System Inc: QS2 {208V}.
ParameterMeasured / Listed ValueEngineering Significance
Max Continuous AC Power (Paco) 1,923 W Determines required backfeed OCPD size via 125% continuous rule
Nominal AC Voltage (Vac) 208 V, commercial single-phase 240V split-phase residential vs. 208V/480V/MV commercial
Max DC Input Voltage (Vdcmax) 45 V Hard ceiling for cold-weather PV string Voc under NEC 690.7
MPPT Operating Range 30 V - 45 V Optimal DC string Vmp window for full power harvest
Max Input DC Current (Idcmax) 53.4116 A Used to verify parallel string combiner limits
CEC Weighted Efficiency 94.73% Calculated AC/DC conversion ratio from CEC test protocol
Inverter Topology Hybrid: No (Grid-Tied PV) CEC Solar Equipment List grid-support certification

What Switchgear Limits Apply to Altenergy Power System Inc: QS2 {208V} (208 V, commercial single-phase)?

NEC 705.12(B)(3)(2) backfeed compliance table for Altenergy Power System Inc: QS2 {208V} at 208 V, commercial single-phase.

Evaluates Altenergy Power System Inc: QS2 {208V} (15 A required OCPD at 208 V, commercial single-phase) across standard distribution busbars.
Switchboard / Interconnect120% Max BackfeedRequired PV OCPDCompliance Verdict
200A Bus / 200A Main (208V) 40 A 15 A PASS (120% Commercial Busbar)
400A Bus / 400A Main (208V) 80 A 15 A PASS (120% Commercial Busbar)
600A Bus / 600A Main (208V) 120 A 15 A PASS (120% Commercial Busbar)
800A Bus / 800A Main (208V) 160 A 15 A PASS (120% Commercial Busbar)
1,200A Bus / 1,200A Main (208V) 240 A 15 A PASS (120% Commercial Busbar)

Which CEC PV Module Strings Pair With Altenergy Power System Inc: QS2 {208V}?

Minimum and maximum series solar module strings fitting Altenergy Power System Inc: QS2 {208V} MPPT and 45 V limits.

Sampled CEC PV modules aligned within 30.0-45.0 V MPPT and 45.0 V max DC at -10 C.
CEC ModuleSTC (W)-10 C VocValid String RangeMax String DC
Aptos Solar Technology LLC DNA-108-MFN10-440W 440.0 W 42.15 V 1 panel (micro/module) 0.44 kW
Boviet Solar Technology Co Ltd BVM7610M-425-H-HC-BF 425.0 W 44.75 V 1 panel (micro/module) 0.42 kW
CSI Solar Co Ltd CS6P-200P 200.0 W 40.6 V 1 panel (micro/module) 0.2 kW
Hanwha Qcells (Qidong) Co Ltd HSL60P6-PB-0-270TW 270.0 W 42.56 V 1 panel (micro/module) 0.27 kW

Which Competing Grid-Support Inverters Compare to Altenergy Power System Inc: QS2 {208V}?

Peer 208 V, commercial single-phase CEC inverters near 1,923 W AC output such as Cherry Solution Co Ltd: CMI-1000S-SA {208V}.

Alternative CEC inverters at comparable AC output power and voltage class.
Alternative InverterAC OutputDeltaVacMax DCCEC Eff
Cherry Solution Co Ltd: CMI-1000S-SA {208V}
Cherry Solution Co Ltd
994 W -929 W 208.0 V 50.0 V 96.35%
Cherry Solution Co Ltd: CMI-1000S-WA {208V}
Cherry Solution Co Ltd
994 W -929 W 208.0 V 50.0 V 96.35%
ABB: PVI-30-OUTD-S-US-A {208V}
ABB
3,000 W +1077 W 208.0 V 480.0 V 95.47%
ABB: PVI-30-OUTD-S-US-Z-A {208V}
ABB
3,000 W +1077 W 208.0 V 480.0 V 95.47%
What to Check & Best-Fit Scenarios

What Are the Interconnection Limits and Best-Fit Uses for Altenergy Power System Inc: QS2 {208V}?

Check Altenergy Power System Inc: QS2 {208V} (1,923 W AC, 15 A OCPD) against your main panel busbar, winter string Voc, and IEEE 1547 outage rules.

  • Anti-islanding shutdown: grid-tied inverters shut off within 2 seconds during blackouts under IEEE 1547 unless paired with a battery microgrid interconnect.
  • Busbar 120% limit: Commercial 208 V, commercial single-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (208V) or NEC 705.11 supply-side tap.
  • Cold Voc hard ceiling: never allow winter open-circuit PV string voltage to exceed 45 V DC on Altenergy Power System Inc: QS2 {208V}.

Altenergy Power System Inc: QS2 {208V} Panel & Wire Spec

Size 75 C copper conductors at 14 AWG Cu on a 15 A OCPD breaker (9.2 A continuous).

Alternative Inverter Comparison

Compare efficiency (94.73%) and MPPT window (30-45 V) directly against Cherry Solution Co Ltd: CMI-1000S-SA {208V} (994 W).

Which Homeowner Electrical & Solar Questions Come Up Most Often?

Answers for Altenergy Power System Inc: QS2 {208V} by Altenergy Power System Inc covering breaker sizing, MPPT limits, and 208 V, commercial single-phase interconnection.

What breaker and wire size does Altenergy Power System Inc: QS2 {208V} require?

At 1,923 W continuous AC (208 V, commercial single-phase), continuous current is 9.2 A; 125% NEC 690.8/705.12 sizing requires a 15 A breaker and 14 AWG Cu (75 C) wire.

What commercial switchgear or feeder sizing does Altenergy Power System Inc: QS2 {208V} require?

At 1,923 W AC and 208 V, commercial single-phase, continuous line current is 9.2 A, requiring a 15 A OCPD and 1,200A Bus / 1,200A Main (208V) or NEC 705.11 interconnection.

How does Altenergy Power System Inc: QS2 {208V} compare to Cherry Solution Co Ltd: CMI-1000S-SA {208V}?

Altenergy Power System Inc: QS2 {208V} delivers 1,923 W AC at 94.73% CEC efficiency with a 45 V DC ceiling, while Cherry Solution Co Ltd: CMI-1000S-SA {208V} outputs 994 W at 208 V, commercial single-phase.

Sources

  1. CEC Solar Equipment List — Grid-Support Inverters (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
  2. CEC Solar Equipment List — PV Modules (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
  3. NFPA 70 National Electrical Code (Section Numbers & Standard Engineering Tables Only) — National Fire Protection Association (NFPA), 2020 / 2023 / 2026 Editions (retrieved 2026-11-23)

Which Regional Electrical & Panel Upgrade Metros Compare Closest?

Check Wiring & Solar Numbers Before Getting Quotes

Verify panel capacity for solar, electrical box space, proper wire gauge for EV chargers, and 2026 home solar payback using local utility rates.

Verify State-Licensed Electricians & Safety Recalls

Look up active state electrician licenses (TX, WA, CO, OR, DE), check local power-outage history, and inspect federal product recall notices.