Altenergy Power System Inc: ELS-96 {208V} outputs 8,308 W AC at 208 V, commercial single-phase (39.9 A continuous, 50 A OCPD), ranking #2,323 of 2,343 CEC inverters at 93.5% efficiency with a 51-60 V MPPT window and 60 V DC limit. All figures reconcile directly against federal energy archives, state electrical licensing boards, California Energy Commission datasheets, and National Electrical Code engineering constants.
- AC Output (Paco)
- 8,308 W
- AC Voltage
- 208 V, commercial single-phase
- Min PV Breaker
- 50 A (8 AWG Cu)
- CEC Efficiency
- 93.5%
How Does Altenergy Power System Inc: ELS-96 {208V} Compare Against Peer CEC Listings?
NEC 705.12 breaker requirements, efficiency placement, and 208 V, commercial single-phase grid-support overview for Altenergy Power System Inc: ELS-96 {208V}.
Ranking #1,082 of 2,343 CEC inverters (top 46.2%; higher than 53.8% of peers), Altenergy Power System Inc: ELS-96 {208V} is a grid-tied PV inverter delivering 8,308 W continuous AC at 208 V, commercial single-phase (39.9 A continuous). Commercial 208 V, commercial single-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (208V) or NEC 705.11 supply-side tap. Weighted CEC efficiency reaches 93.5% (-2.91 pts vs the 96.41% 208 V median) against peers like Delta Electronics: E10-TL-US(AC) {208V} (8,327 W).
Where Does Altenergy Power System Inc: ELS-96 {208V} Fall Across Listed CEC Models?
Marks Altenergy Power System Inc: ELS-96 {208V} (8,308 W AC) across the California Energy Commission inverter AC capacity distribution.
What Dataset Percentiles Define Altenergy Power System Inc: ELS-96 {208V}?
Benchmarks Altenergy Power System Inc: ELS-96 {208V} continuous AC output, 93.5% CEC weighted efficiency, and 50 A OCPD breaker demand.
What Do the Dataset Ranks Show for Altenergy Power System Inc: ELS-96 {208V}?
Four key NEC 705.12 and California Energy Commission metrics defining Altenergy Power System Inc: ELS-96 {208V} by Altenergy Power System Inc.
93.5% CEC Weighted Efficiency
-2.91 pts vs the 96.41% 208 V median; overall power rank #1,082 (8,308 W, top 46.2%; higher than 53.8% of peers).
50 A Required Backfeed OCPD
125% x 39.9 A = 49.9 A -> 50 A standard OCPD using 8 AWG Cu (75 C).
51 V - 60 V (Max 60 V DC)
Tracking span of 9.0 V; listed since 2025-01-13 (grid-tied PV inverter).
PASS (120% Commercial Busbar)
Evaluated for 208 V, commercial single-phase switchgear (200A Bus / 200A Main (208V) to 1,200A Bus / 1,200A Main (208V)) under NEC 705.12 / 705.11.
NEC 705.12 Backfeed OCPD & 120% Busbar Formula
I_cont = 8308.0W / 208 V -> 39.9 A | Breaker >= 1.25 * 39.9 = 49.9 A -> 50 A
CEC Inverters.csv for Altenergy Power System Inc: ELS-96 {208V}: Paco=8308.0 W, Vac=208 V, Vdcmax=60.0 V, Eff=93.5%.
Result: Min 50 A breaker & 8 AWG Cu (75 C); 1,200A Bus / 1,200A Main (208V): PASS (120% Commercial Busbar).
What Are the Published CEC Specifications for Altenergy Power System Inc: ELS-96 {208V}?
Official laboratory CEC ratings, MPPT operating window, and DC voltage bounds recorded for Altenergy Power System Inc: ELS-96 {208V}.
| Parameter | Measured / Listed Value | Engineering Significance |
|---|---|---|
| Max Continuous AC Power (Paco) | 8,308 W | Determines required backfeed OCPD size via 125% continuous rule |
| Nominal AC Voltage (Vac) | 208 V, commercial single-phase | 240V split-phase residential vs. 208V/480V/MV commercial |
| Max DC Input Voltage (Vdcmax) | 60 V | Hard ceiling for cold-weather PV string Voc under NEC 690.7 |
| MPPT Operating Range | 51 V - 60 V | Optimal DC string Vmp window for full power harvest |
| Max Input DC Current (Idcmax) | 158.678 A | Used to verify parallel string combiner limits |
| CEC Weighted Efficiency | 93.5% | Calculated AC/DC conversion ratio from CEC test protocol |
| CEC Listing Date & Hybrid | 2025-01-13 / Hybrid: No (Grid-Tied PV) | Utility interconnection approval metadata |
What Switchgear Limits Apply to Altenergy Power System Inc: ELS-96 {208V} (208 V, commercial single-phase)?
Evaluates Altenergy Power System Inc: ELS-96 {208V} (50 A OCPD) across standard 100 A to 225 A busbars or commercial switchboards.
| Switchboard / Interconnect | 120% Max Backfeed | Required PV OCPD | Compliance Verdict |
|---|---|---|---|
| 200A Bus / 200A Main (208V) | 40 A | 50 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| 400A Bus / 400A Main (208V) | 80 A | 50 A | PASS (120% Commercial Busbar) |
| 600A Bus / 600A Main (208V) | 120 A | 50 A | PASS (120% Commercial Busbar) |
| 800A Bus / 800A Main (208V) | 160 A | 50 A | PASS (120% Commercial Busbar) |
| 1,200A Bus / 1,200A Main (208V) | 240 A | 50 A | PASS (120% Commercial Busbar) |
Which CEC PV Module Strings Pair With Altenergy Power System Inc: ELS-96 {208V}?
Sample PV string lengths aligned within 51-60 V MPPT and 60 V DC max at -10 C. Always verify current state NEC adoption cycles, local utility interconnection tariffs, and panel busbar ratings before pulling project permits.
| CEC Module | STC (W) | -10 C Voc | Valid String Range | Max String DC |
|---|---|---|---|---|
| AXITEC AC-590TGB/144TS | 590.0 W | 56.24 V | 1 panel (micro/module) | 0.59 kW |
| Aptos Solar Technology LLC DNA-108-MFN10-440W | 440.0 W | 42.15 V | 1 panel (micro/module) | 0.44 kW |
| Boviet Solar Technology Co Ltd BVM7610M-425-H-HC-BF | 425.0 W | 44.75 V | 1 panel (micro/module) | 0.42 kW |
| CSI Solar Co Ltd CS6P-200P | 200.0 W | 40.6 V | 1 panel (micro/module) | 0.2 kW |
Which Competing Grid-Support Inverters Compare to Altenergy Power System Inc: ELS-96 {208V}?
Competing CEC grid-support inverters near 8,308 W AC and 208 V, commercial single-phase, led by Delta Electronics: E10-TL-US(AC) {208V}.
| Alternative Inverter | AC Output | Delta | Vac | Max DC | CEC Eff |
|---|---|---|---|---|---|
| Delta Electronics: E10-TL-US(AC) {208V} Delta Electronics |
8,327 W | +19 W | 208.0 V | 480.0 V | 97.45% |
| Delta Electronics: M10-TL-US {208V} Delta Electronics |
8,360 W | +52 W | 208.0 V | 480.0 V | 96.83% |
| Delta Electronics: M10-4-TL-US {208V} Delta Electronics |
8,385 W | +77 W | 208.0 V | 480.0 V | 96.94% |
| Delta Electronics: E10_BDI {208V} Delta Electronics |
8,400 W | +92 W | 208.0 V | 480.0 V | 96.86% |
What Are the Interconnection Limits and Best-Fit Uses for Altenergy Power System Inc: ELS-96 {208V}?
Check Altenergy Power System Inc: ELS-96 {208V} (8,308 W AC, 50 A OCPD) against your main panel busbar, winter string Voc, and IEEE 1547 outage rules.
- Anti-islanding shutdown: grid-tied inverters shut off within 2 seconds during blackouts under IEEE 1547 unless paired with a battery microgrid interconnect.
- Busbar 120% limit: Commercial 208 V, commercial single-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (208V) or NEC 705.11 supply-side tap.
- Cold Voc hard ceiling: never allow winter open-circuit PV string voltage to exceed 60 V DC on Altenergy Power System Inc: ELS-96 {208V}.
Altenergy Power System Inc: ELS-96 {208V} Panel & Wire Spec
Size 75 C copper conductors at 8 AWG Cu on a 50 A OCPD breaker (39.9 A continuous).
Alternative Inverter Comparison
Compare efficiency (93.5%) and MPPT window (51-60 V) directly against Delta Electronics: E10-TL-US(AC) {208V} (8,327 W).
Which Homeowner Electrical & Solar Questions Come Up Most Often?
Answers for Altenergy Power System Inc: ELS-96 {208V} by Altenergy Power System Inc covering breaker sizing, MPPT limits, and 208 V, commercial single-phase interconnection.
What breaker and wire size does Altenergy Power System Inc: ELS-96 {208V} require?
At 8,308 W continuous AC (208 V, commercial single-phase), continuous current is 39.9 A; 125% NEC 690.8/705.12 sizing requires a 50 A breaker and 8 AWG Cu (75 C) wire.
What commercial switchgear or feeder sizing does Altenergy Power System Inc: ELS-96 {208V} require?
At 8,308 W AC and 208 V, commercial single-phase, continuous line current is 39.9 A, requiring a 50 A OCPD and 1,200A Bus / 1,200A Main (208V) or NEC 705.11 interconnection.
How does Altenergy Power System Inc: ELS-96 {208V} compare to Delta Electronics: E10-TL-US(AC) {208V}?
Altenergy Power System Inc: ELS-96 {208V} delivers 8,308 W AC at 93.5% CEC efficiency with a 60 V DC ceiling, while Delta Electronics: E10-TL-US(AC) {208V} outputs 8,327 W at 208 V, commercial single-phase.
Sources
- CEC Solar Equipment List — Grid-Support Inverters (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
- CEC Solar Equipment List — PV Modules (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
- NFPA 70 National Electrical Code (Section Numbers & Standard Engineering Tables Only) — National Fire Protection Association (NFPA), 2020 / 2023 / 2026 Editions (retrieved 2026-11-23)