Thornova Solar TS-BGT66(710)-G12 is a 710.0 W STC (675.2 W PTC) Mono-c-Si solar module ranking #135 of 21,677 CEC listings (top 0.8%; higher than 99.2% of peers). It delivers 23.05% efficiency, 49.0 V Voc at 25 C, and 52.88 V cold Voc at -10 C (11 panels max per 600 V string).
- STC Wattage
- 710.0 W
- PTC Wattage
- 675.2 W
- Voc @ 25C
- 49.0 V
- Efficiency
- 23.05%
How Does Thornova Solar TS-BGT66(710)-G12 Compare Against Peer CEC Listings?
How Thornova Solar Thornova Solar TS-BGT66(710)-G12 handles rooftop heat (675.2 W PTC), 8 kW sizing, and cold winter string voltage.
For NEC string engineering, Thornova Solar TS-BGT66(710)-G12 exhibits 18.4 A short-circuit current, requiring a 28.7 A (156%) conductor rating and 30 A OCPD under NEC 690.8. Ranked #135 of 21,677 (300.0 W above the 410.0 W Mono-c-Si median), this large-format commercial and ground-mount module covers 37.0 m2 for an 8 kW system (15 panels for 10 kW). Higher 49.0 V open-circuit voltage caps 600 V residential strings at 11 panels at 14 F (-10 C).
Where Does Thornova Solar TS-BGT66(710)-G12 Fall Across Listed CEC Models?
Where Thornova Solar TS-BGT66(710)-G12 (710.0 W) sits inside the 21,677-panel CEC STC wattage curve relative to the 385.0 W median.
What Dataset Percentiles Define Thornova Solar TS-BGT66(710)-G12?
Percentile placement of Thornova Solar TS-BGT66(710)-G12 across power density (230.5 W/m2), thermal retention, and nameplate STC wattage.
What Do the Dataset Ranks Show for Thornova Solar TS-BGT66(710)-G12?
Four critical engineering numbers homeowners and solar installers check first when reviewing Thornova Solar TS-BGT66(710)-G12 specifications.
Top 0.8% STC Output
710.0 W STC (+325.0 W vs all-CEC median) vs 410.0 W Mono-c-Si median.
23.05% Aperture Efficiency
Power density 230.5 W/m2 (3.14 percentage points above 19.91% CEC median). PTC/STC ratio: 95.1% (rank #713).
11 Panels Max @ -10 C (600 V)
Cold Voc reaches 52.88 V at -10 C (581.7 V string) and 53.98 V at -20 C (11 max).
12 Panels = 8,520 W STC
Occupies 37.0 m2 (398 sq ft) producing 8,102 W PTC; NEC 690.8 OCPD floor is 28.7 A (30 A breaker).
NEC 690.7(A) Cold-Temperature Voc & 690.8 OCPD Formula
Voc_cold = 49.0 * (1 + (-0.226/100) * (-10 - 25)) = 52.88 V | OCPD = 1.56 * 18.4 = 28.7 A
Inputs from CEC Modules.csv for Thornova Solar TS-BGT66(710)-G12: Voc=49.0 V, beta_Voc=-0.226%/C, Isc=18.4 A, STC=710.0 W, Area=3.08 m2.
Result: 11 panels max on 600 V (581.7 V); 12 panels for 8 kW (398 sq ft).
What Are the Published CEC Specifications for Thornova Solar TS-BGT66(710)-G12?
Verified electrical STC and PTC ratings, open-circuit voltage, short-circuit current, and physical area published for Thornova Solar TS-BGT66(710)-G12.
| Parameter | Measured / Listed Value | Engineering Significance |
|---|---|---|
| Nameplate Power (STC) | 710.0 W | Rated DC output under Standard Test Conditions (1000 W/m2, 25C cell) |
| Real-World Output (PTC) | 675.2 W (95.1% STC) | PVUSA Test Conditions rating used for utility interconnection |
| Open-Circuit Voltage (Voc) | 49.0 V | Primary cold-weather string sizing limit under NEC 690.7 |
| Short-Circuit Current (Isc) | 18.4 A | Determines 156% (1.25x1.25) OCPD fuse/breaker sizing under NEC 690.8 |
| Max Power Voltage / Current | 40.9 V / 17.36 A | Inverter MPPT operating window alignment |
| Voc Temp Coefficient (beta_Voc) | -0.226 %/C | Negative slope governing voltage rise below 25C |
| Module Efficiency & Area | 23.05% (3.08 m2) | Array roof footprint density |
| Cell Count & Technology | 66 cells (Mono-c-Si) | Bifacial glass-glass |
How Many Thornova Solar TS-BGT66(710)-G12 Panels Build a 6 kW, 8 kW, or 10 kW Array?
Compare 6 kW, 8 kW, and 10 kW array footprints and Year-1 utility savings using Thornova Solar TS-BGT66(710)-G12 (710.0 W).
| Target Array | Panels | Actual DC | Roof Area | US Avg ($/yr) | CA High ($/yr) |
|---|---|---|---|---|---|
| 6 kW Class | 9 | 6.39 kW | 298 sq ft | $1,599 | $2,704 |
| 8 kW Class | 12 | 8.52 kW | 398 sq ft | $2,132 | $3,606 |
| 10 kW Class | 15 | 10.65 kW | 497 sq ft | $2,666 | $4,507 |
How Many Thornova Solar TS-BGT66(710)-G12 Modules Fit in a Cold-Weather String?
Maximum series module counts for Thornova Solar TS-BGT66(710)-G12 from 25 C down to -20 C (-4 F) under NEC 690.7.
| Ambient Min Temp | Cold Voc / Panel | Max Panels (600 V) | 600 V String Voc | Max Panels (1000 V) |
|---|---|---|---|---|
| -20 C (-4 F) | 53.98 V | 11 panels | 593.8 V | 18 panels |
| -10 C (14 F) | 52.88 V | 11 panels | 581.7 V | 18 panels |
| 0 C (32 F) | 51.77 V | 11 panels | 569.5 V | 19 panels |
| 25 C (77 F STC) | 49.0 V | 12 panels | 588.0 V | 20 panels |
Which Cross-Brand Solar Modules Compare Closest to Thornova Solar TS-BGT66(710)-G12?
Alternative CEC solar modules from competing brands near Thornova Solar TS-BGT66(710)-G12 (710.0 W), including Trina Solar CoLtd TSM-710NEG21C20.
| Alternative Module | STC (W) | Delta vs This | Voc (V) | Eff (%) | PTC/STC |
|---|---|---|---|---|---|
| Trina Solar CoLtd TSM-710NEG21C20 Trina Solar CoLtd |
710.0 W | Tie (0 W) | 49.0 V | 23.05% | 94.7% |
| Boviet Solar Technology Co Ltd BVM8611M-710-H-HC-BF Boviet Solar Technology Co Ltd |
710.0 W | Tie (0 W) | 48.93 V | 24.4% | 95.3% |
| Boviet Solar Technology Co Ltd BVM8611M-710-H-HC-BF-DG Boviet Solar Technology Co Ltd |
710.0 W | Tie (0 W) | 48.93 V | 24.4% | 95.4% |
| Vietnam Sunergy Joint Stock Company VSUN710N-132BMH-DG Vietnam Sunergy Joint Stock Company |
710.0 W | Tie (0 W) | 48.9 V | 22.86% | 94.4% |
What Are the Design Limits and Best-Fit Uses for Thornova Solar TS-BGT66(710)-G12?
Evaluate Thornova Solar TS-BGT66(710)-G12 (710.0 W STC, 49.0 V Voc) against your roof geometry, winter climate, and inverter voltage ceiling before finalizing bids.
- Winter overvoltage boundary: at -20 C (-4 F), Thornova Solar TS-BGT66(710)-G12 reaches 53.98 V per panel—exceeding 11 panels in series voids 600 V inverter warranties.
- Footprint constraint: 12 panels for an 8 kW build require 398 sq ft of unshaded roof plane — better matched to wide open ground racks or commercial flat roofs than tight residential roof hips.
- 2026 tax credit baseline: cash residential installs of Thornova Solar TS-BGT66(710)-G12 carry 0% federal 25D credit after 2025-12-31, making 18.54 c/kWh+ utility avoidance key.
Thornova Solar TS-BGT66(710)-G12 8 kW Residential Fit
Needs 12 modules (398 sq ft) with a 30 A string OCPD, offsetting ~$2,132/yr at US average tariffs.
Cold-Climate String Design (-10 C / -20 C)
Cap 600 V series strings at 11 panels (-10 C) or 11 panels (-20 C), or compare Trina Solar CoLtd TSM-710NEG21C20.
Bifacial / High-Heat Roof Check
Glass-glass bifacial cells capture rear albedo reflection over light ground gravel or white membranes. Real-world output tracks 675.2 W PTC.
Which Homeowner Electrical & Solar Questions Come Up Most Often?
Technical answers for Thornova Solar TS-BGT66(710)-G12 by Thornova Solar grounded in CEC test data and NEC 690.7/690.8 limits.
Why is Thornova Solar TS-BGT66(710)-G12 PTC wattage (675.2 W) lower than STC (710.0 W)?
Laboratory STC tests at 25 C cell temperature, whereas real rooftop heat lowers voltage to 675.2 W PTC (95.1% retention) across Thornova Solar TS-BGT66(710)-G12's 3.08 m2 aperture.
Who should skip Thornova Solar TS-BGT66(710)-G12 on a complex residential roof?
Homes with chopped dormers or heavy chimney shade should compare smaller modules or microinverters if 12 Thornova Solar TS-BGT66(710)-G12 panels (398 sq ft) leave unusable roof gaps vs. Trina Solar CoLtd TSM-710NEG21C20.
What is the 1,000 V commercial string limit for Thornova Solar TS-BGT66(710)-G12?
On 1,000 V commercial inverters at -10 C (52.88 V cold Voc), Thornova Solar TS-BGT66(710)-G12 fits up to 18 panels per series string.
Sources
- CEC Solar Equipment List — PV Modules (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
- NFPA 70 National Electrical Code (Section Numbers & Standard Engineering Tables Only) — National Fire Protection Association (NFPA), 2020 / 2023 / 2026 Editions (retrieved 2026-11-23)