Tesla Inc T430S — CEC Solar Module Specifications

Manufacturer: Tesla Inc Registry: CEC Verified Engineering Specification

Tesla Inc T430S is a 430.0 W STC (401.8 W PTC) Mono-c-Si solar module ranking #7,266 of 21,677 CEC listings (top 35.2%; higher than 64.8% of peers). It delivers 20.37% efficiency, 48.8 V Voc at 25 C, and 53.24 V cold Voc at -10 C (11 panels max per 600 V string).

STC Wattage
430.0 W
PTC Wattage
401.8 W
Voc @ 25C
48.8 V
Efficiency
20.37%
Wall-mounted residential hybrid solar inverter and modular battery cabinet piped with galvanized EMT conduit
Wall-mounted residential hybrid solar inverter and modular battery cabinet piped with galvanized EMT conduit

How Does Tesla Inc T430S Compare Against Peer CEC Listings?

Solar engineering breakdown for Tesla Inc T430S: PTC thermal retention, roof footprint, and cold Voc string bounds. Cross-check local Authority Having Jurisdiction amendments and serving utility net-metering terms before finalizing project sizing.

Measured at 430.0 W STC and 401.8 W PTC, Tesla Inc T430S sits +45.0 W vs all-CEC median (top 35.2%; higher than 64.8% of peers) among 21,677 listed modules. Power density reaches 203.7 W/m2 (0.46 percentage points above 19.91% CEC median). Higher 48.8 V open-circuit voltage caps 600 V residential strings at 11 panels at 14 F (-10 C), whereas 1,000 V commercial inverters handle up to 18 panels in series. Alternative peer Caterpillar Inc PVC435MP03H rates 435.0 W.

Where Does Tesla Inc T430S Fall Across Listed CEC Models?

Distribution marker showing Tesla Inc T430S (430.0 W) relative to the 385.0 W all-CEC solar panel median. All figures trace directly to published federal energy filings, state electrical boards, CEC datasheets, and NFPA 70 NEC tables.

STC Power Distribution Across 21,677 CEC Solar ModulesMarks where Tesla Inc T430S (430.0 W STC) stands relative to CEC photovoltaic modules. 18-79 W STC: 68 entries1879-140 W STC: 170 entries140-202 W STC: 413 entries202-263 W STC: 1,883 entries202263-325 W STC: 4,202 entries325-386 W STC: 4,219 entries386-448 W STC: 4,695 entries386448-509 W STC: 1,584 entries509-571 W STC: 2,290 entries571-632 W STC: 1,371 entries571632-694 W STC: 534 entries694-755 W STC: 248 entries694Median 385 W STCTesla Inc T430S: 430.0 W

What Dataset Percentiles Define Tesla Inc T430S?

Dataset percentiles tracking Tesla Inc T430S power output, thermal retention ratio, and aperture efficiency against 21,677 models. Compare thermal ratings, overcurrent protection caps, and continuous load headroom carefully before expanding an existing home service panel.

Tesla Inc T430S Engineering BenchmarksPercentile comparison of Tesla Inc T430S wattage, thermal retention, and efficiency. 0% (Low)50% Median100% (Top)STC Wattage430.0 WPTC/STC Retention93.4%Module Efficiency20.37%

What Do the Dataset Ranks Show for Tesla Inc T430S?

Benchmark highlights for Tesla Inc T430S covering STC output, efficiency, 8 kW footprint, and OCPD breaker size. Always verify current state NEC adoption cycles, local utility interconnection tariffs, and panel busbar ratings before pulling project permits.

Rank #7,266 / 21,677

Top 35.2% STC Output

430.0 W STC (+45.0 W vs all-CEC median) vs 410.0 W Mono-c-Si median.

Eff #9,017

20.37% Aperture Efficiency

Power density 203.7 W/m2 (0.46 percentage points above 19.91% CEC median). PTC/STC ratio: 93.4% (rank #7,716).

NEC 690.7 Limit

11 Panels Max @ -10 C (600 V)

Cold Voc reaches 53.24 V at -10 C (585.6 V string) and 54.51 V at -20 C (11 max).

8 kW Reference Array

19 Panels = 8,170 W STC

Occupies 40.1 m2 (432 sq ft) producing 7,634 W PTC; NEC 690.8 OCPD floor is 17.66 A (20 A breaker).

NEC 690.7(A) Cold-Temperature Voc & 690.8 OCPD Formula

Voc_cold = 48.8 * (1 + (-0.26/100) * (-10 - 25)) = 53.24 V | OCPD = 1.56 * 11.32 = 17.66 A

Inputs from CEC Modules.csv for Tesla Inc T430S: Voc=48.8 V, beta_Voc=-0.26%/C, Isc=11.32 A, STC=430.0 W, Area=2.111 m2.

Result: 11 panels max on 600 V (585.6 V); 19 panels for 8 kW (432 sq ft).

What Are the Published CEC Specifications for Tesla Inc T430S?

Official CEC datasheet figures for Tesla Inc T430S (Mono-c-Si) used in utility interconnection and permit reviews. Review related calculators, peer benchmarks, and source citations below to validate design assumptions for your electrical service.

Official California Energy Commission (NREL SAM) test parameters for Tesla Inc T430S.
ParameterMeasured / Listed ValueEngineering Significance
Nameplate Power (STC) 430.0 W Rated DC output under Standard Test Conditions (1000 W/m2, 25C cell)
Real-World Output (PTC) 401.8 W (93.4% STC) PVUSA Test Conditions rating used for utility interconnection
Open-Circuit Voltage (Voc) 48.8 V Primary cold-weather string sizing limit under NEC 690.7
Short-Circuit Current (Isc) 11.32 A Determines 156% (1.25x1.25) OCPD fuse/breaker sizing under NEC 690.8
Max Power Voltage / Current 41.2 V / 10.44 A Inverter MPPT operating window alignment
Voc Temp Coefficient (beta_Voc) -0.26 %/C Negative slope governing voltage rise below 25C
Module Efficiency & Area 20.37% (2.111 m2) Array roof footprint density
Cell Count & Technology 24 cells (Mono-c-Si) Monofacial backsheet

How Many Tesla Inc T430S Panels Build a 6 kW, 8 kW, or 10 kW Array?

How many Tesla Inc T430S modules and square feet are required for 6 kW, 8 kW, and 10 kW home solar arrays.

Estimated panel count, roof square footage, and Year-1 bill offset across low, average, and high US utility tariffs (0% 25D).
Target ArrayPanelsActual DCRoof AreaUS Avg ($/yr)CA High ($/yr)
6 kW Class 14 6.02 kW 318 sq ft $1,507 $2,548
8 kW Class 19 8.17 kW 432 sq ft $2,045 $3,458
10 kW Class 24 10.32 kW 545 sq ft $2,583 $4,368

Which Sibling Wattage & Trim Variants Belong to This Tesla Inc Series?

Consolidated Tesla Inc wattage variants sharing the Tesla Inc T430S mechanical and cell layout. Use these verified dataset benchmarks alongside a licensed electrician load calculation to compare residential upgrade bids with confidence.

Sibling CEC listings grouped into the Tesla Inc T430S wattage tier to avoid duplicate 5W/trim datasheets.
Model VariantSTC (W)PTC (W)Voc (V)Vmp (V)Eff (%)
Tesla Inc T425S 425.0 W 397.0 W 48.65 V 41.05 V 20.13%
Tesla Inc T430S 430.0 W 401.8 W 48.8 V 41.2 V 20.37%

How Many Tesla Inc T430S Modules Fit in a Cold-Weather String?

NEC 690.7(A) winter string table preventing overvoltage trips on Tesla Inc T430S (53.24 V at 14 F).

Computed from Voc=48.8V and beta_Voc=-0.26%/C across design ambient temperatures.
Ambient Min TempCold Voc / PanelMax Panels (600 V)600 V String VocMax Panels (1000 V)
-20 C (-4 F) 54.51 V 11 panels 599.6 V 18 panels
-10 C (14 F) 53.24 V 11 panels 585.6 V 18 panels
0 C (32 F) 51.97 V 11 panels 571.7 V 19 panels
25 C (77 F STC) 48.8 V 12 panels 585.6 V 20 panels

Which Cross-Brand Solar Modules Compare Closest to Tesla Inc T430S?

Competing CEC solar panels closest to Tesla Inc T430S in nameplate wattage and Voc, starting with Caterpillar Inc PVC435MP03H.

Nearest CEC-listed competing brands by STC power and open-circuit voltage.
Alternative ModuleSTC (W)Delta vs ThisVoc (V)Eff (%)PTC/STC
Caterpillar Inc PVC435MP03H
Caterpillar Inc
435.0 W +5.0 W 48.7 V 20.52% 93.6%
CSI Solar Co Ltd CS3W-435P
CSI Solar Co Ltd
435.0 W +5.0 W 48.6 V 20.33% 92.4%
AXITEC AC-435MB/144V
AXITEC
435.0 W +5.0 W 49.1 V 20.33% 92.6%
Dehui Solar Power (Vietnam) CoLtd DH-M772F 435W
Dehui Solar Power (Vietnam) CoLtd
435.0 W +5.0 W 49.1 V 20.33% 92.6%
What to Check & Best-Fit Scenarios

What Are the Design Limits and Best-Fit Uses for Tesla Inc T430S?

Evaluate Tesla Inc T430S (430.0 W STC, 48.8 V Voc) against your roof geometry, winter climate, and inverter voltage ceiling before finalizing bids.

  • Winter overvoltage boundary: at -20 C (-4 F), Tesla Inc T430S reaches 54.51 V per panel—exceeding 11 panels in series voids 600 V inverter warranties.
  • Footprint constraint: 19 panels for an 8 kW build require 432 sq ft of unshaded roof plane — well-proportioned for residential pitched roofs needing 19 panels (432 sq ft) for an 8 kW array.
  • 2026 tax credit baseline: cash residential installs of Tesla Inc T430S carry 0% federal 25D credit after 2025-12-31, making 18.54 c/kWh+ utility avoidance key.

Tesla Inc T430S 8 kW Residential Fit

Needs 19 modules (432 sq ft) with a 20 A string OCPD, offsetting ~$2,045/yr at US average tariffs.

Cold-Climate String Design (-10 C / -20 C)

Cap 600 V series strings at 11 panels (-10 C) or 11 panels (-20 C), or compare Caterpillar Inc PVC435MP03H.

Bifacial / High-Heat Roof Check

Monofacial backsheet sealing targets flush dark shingle rooftop mounts. Real-world output tracks 401.8 W PTC.

Which Homeowner Electrical & Solar Questions Come Up Most Often?

Technical answers for Tesla Inc T430S by Tesla Inc grounded in CEC test data and NEC 690.7/690.8 limits.

How many Tesla Inc T430S panels fit on a 600 V winter solar string?

At -10 C (14 F), Tesla Inc T430S cold Voc rises from 48.8 V to 53.24 V (beta_Voc -0.26%/C), capping a 600 V string at 11 panels (585.6 V).

How much roof area does an 8 kW array of Tesla Inc T430S need?

An 8 kW DC system uses 19 Tesla Inc T430S modules (8,170 W STC / 7,634 W PTC), covering roughly 432 sq ft and saving ~$2,045/yr at 18.54 c/kWh.

How does Tesla Inc T430S compare against Caterpillar Inc PVC435MP03H?

Tesla Inc T430S outputs 430.0 W STC (48.8 V Voc, rank #7,266 of 21,677), while Caterpillar Inc PVC435MP03H delivers 435.0 W STC; both comply with 2026 NEC 690.7 string sizing rules.

Sources

  1. CEC Solar Equipment List — PV Modules (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
  2. NFPA 70 National Electrical Code (Section Numbers & Standard Engineering Tables Only) — National Fire Protection Association (NFPA), 2020 / 2023 / 2026 Editions (retrieved 2026-11-23)

Which Regional Electrical & Panel Upgrade Metros Compare Closest?

Check Wiring & Solar Numbers Before Getting Quotes

Verify panel capacity for solar, electrical box space, proper wire gauge for EV chargers, and 2026 home solar payback using local utility rates.

Verify State-Licensed Electricians & Safety Recalls

Look up active state electrician licenses (TX, WA, CO, OR, DE), check local power-outage history, and inspect federal product recall notices.