Mitsubishi Electric PV-MF180UD4 — CEC Solar Module Specifications

Manufacturer: Mitsubishi Electric Registry: CEC Verified Engineering Specification

Mitsubishi Electric PV-MF180UD4 is a 180.0 W STC (160.7 W PTC) Multi-c-Si solar module ranking #21,232 of 21,677 CEC listings (below all-CEC median; higher than 1.8% of peers). It delivers 13.0% efficiency, 30.4 V Voc at 25 C, and 34.03 V cold Voc at -10 C (17 panels max per 600 V string).

STC Wattage
180.0 W
PTC Wattage
160.7 W
Voc @ 25C
30.4 V
Efficiency
13.0%
Wall-mounted residential hybrid solar inverter and modular battery cabinet piped with galvanized EMT conduit
Wall-mounted residential hybrid solar inverter and modular battery cabinet piped with galvanized EMT conduit

How Does Mitsubishi Electric PV-MF180UD4 Compare Against Peer CEC Listings?

CEC rank, roof space requirements, and NEC 690.7/690.8 limits for Mitsubishi Electric PV-MF180UD4 (Multi-c-Si) residential solar systems.

Homeowners evaluating Mitsubishi Electric PV-MF180UD4 need 34 panels for 6 kW or 45 panels (670 sq ft) for an 8 kW array—useful on tight dormer roofs or battery cabins, though 8 kW requires 45 panels (670 sq ft). Under NEC 690.7(A), beta_Voc (-0.341%/C) pushes open-circuit voltage to 34.03 V at 14 F and 35.06 V at -4 F. Monofacial backsheet sealing targets flush dark shingle rooftop mounts.

Where Does Mitsubishi Electric PV-MF180UD4 Fall Across Listed CEC Models?

Comparison of Mitsubishi Electric PV-MF180UD4 (180.0 W STC) against all 21,677 California Energy Commission certified photovoltaic modules. Every reported metric links directly to federal public records or state regulatory filings with zero paid contractor placements.

STC Power Distribution Across 21,677 CEC Solar ModulesMarks where Mitsubishi Electric PV-MF180UD4 (180.0 W STC) stands relative to CEC photovoltaic modules. 18-79 W STC: 68 entries1879-140 W STC: 170 entries140-202 W STC: 413 entries202-263 W STC: 1,883 entries202263-325 W STC: 4,202 entries325-386 W STC: 4,219 entries386-448 W STC: 4,695 entries386448-509 W STC: 1,584 entries509-571 W STC: 2,290 entries571-632 W STC: 1,371 entries571632-694 W STC: 534 entries694-755 W STC: 248 entries694Median 385 W STCMitsubishi Electri: 180.0 W

What Dataset Percentiles Define Mitsubishi Electric PV-MF180UD4?

Relative ranking of Mitsubishi Electric PV-MF180UD4 across nameplate watts, 89.3% PTC thermal ratio, and module aperture efficiency. Inspect manufacturer nameplate documentation, UL listing boundaries, and utility rate schedules closely before ordering electrical hardware.

Mitsubishi Electric PV-MF180UD4 Engineering BenchmarksPercentile comparison of Mitsubishi Electric PV-MF180UD4 wattage, thermal retention, and efficiency. 0% (Low)50% Median100% (Top)STC Wattage180.0 WPTC/STC Retention89.3%Module Efficiency13.0%

What Do the Dataset Ranks Show for Mitsubishi Electric PV-MF180UD4?

Summary of Mitsubishi Electric PV-MF180UD4 output rank, 8 kW array size (45 panels), efficiency rating, and 600 V string limit.

Rank #21,232 / 21,677

180.0 W STC · Higher Than 1.8%

180.0 W STC (-205.0 W vs all-CEC median) vs 278.8 W Multi-c-Si median.

Eff #21,409

13.0% Aperture Efficiency

Power density 130.1 W/m2 (6.91 percentage points below 19.91% CEC median). PTC/STC ratio: 89.3% (rank #20,205).

NEC 690.7 Limit

17 Panels Max @ -10 C (600 V)

Cold Voc reaches 34.03 V at -10 C (578.5 V string) and 35.06 V at -20 C (17 max).

8 kW Reference Array

45 Panels = 8,100 W STC

Occupies 62.3 m2 (670 sq ft) producing 7,232 W PTC; NEC 690.8 OCPD floor is 12.53 A (15 A breaker).

NEC 690.7(A) Cold-Temperature Voc & 690.8 OCPD Formula

Voc_cold = 30.4 * (1 + (-0.341/100) * (-10 - 25)) = 34.03 V | OCPD = 1.56 * 8.03 = 12.53 A

Inputs from CEC Modules.csv for Mitsubishi Electric PV-MF180UD4: Voc=30.4 V, beta_Voc=-0.341%/C, Isc=8.03 A, STC=180.0 W, Area=1.384 m2.

Result: 17 panels max on 600 V (578.5 V); 45 panels for 8 kW (670 sq ft).

What Are the Published CEC Specifications for Mitsubishi Electric PV-MF180UD4?

Complete CEC test sheet for Mitsubishi Electric PV-MF180UD4 including Isc (8.03 A), Voc (30.4 V), and thermal temperature coefficients.

Official California Energy Commission (NREL SAM) test parameters for Mitsubishi Electric PV-MF180UD4.
ParameterMeasured / Listed ValueEngineering Significance
Nameplate Power (STC) 180.0 W Rated DC output under Standard Test Conditions (1000 W/m2, 25C cell)
Real-World Output (PTC) 160.7 W (89.3% STC) PVUSA Test Conditions rating used for utility interconnection
Open-Circuit Voltage (Voc) 30.4 V Primary cold-weather string sizing limit under NEC 690.7
Short-Circuit Current (Isc) 8.03 A Determines 156% (1.25x1.25) OCPD fuse/breaker sizing under NEC 690.8
Max Power Voltage / Current 24.2 V / 7.45 A Inverter MPPT operating window alignment
Voc Temp Coefficient (beta_Voc) -0.341 %/C Negative slope governing voltage rise below 25C
Module Efficiency & Area 13.0% (1.384 m2) Array roof footprint density
Cell Count & Technology 50 cells (Multi-c-Si) Monofacial backsheet

How Many Mitsubishi Electric PV-MF180UD4 Panels Build a 6 kW, 8 kW, or 10 kW Array?

Residential array count and annual electric bill savings at 18.54 c/kWh US avg vs. California tariffs using Mitsubishi Electric PV-MF180UD4.

Estimated panel count, roof square footage, and Year-1 bill offset across low, average, and high US utility tariffs (0% 25D).
Target ArrayPanelsActual DCRoof AreaUS Avg ($/yr)CA High ($/yr)
6 kW Class 34 6.12 kW 507 sq ft $1,532 $2,590
8 kW Class 45 8.1 kW 670 sq ft $2,027 $3,428
10 kW Class 56 10.08 kW 834 sq ft $2,523 $4,266

Which Sibling Wattage & Trim Variants Belong to This Mitsubishi Electric Series?

Related Mitsubishi Electric power steps and black/silver trims consolidated into this Mitsubishi Electric PV-MF180UD4 series guide. Always verify current state NEC adoption cycles, local utility interconnection tariffs, and panel busbar ratings before pulling project permits.

Sibling CEC listings grouped into the Mitsubishi Electric PV-MF180UD4 wattage tier to avoid duplicate 5W/trim datasheets.
Model VariantSTC (W)PTC (W)Voc (V)Vmp (V)Eff (%)
Mitsubishi Electric PV-MF175UD4 175.0 W 156.1 W 30.2 V 23.9 V 12.64%
Mitsubishi Electric PV-MF180UD4 180.0 W 160.7 W 30.4 V 24.2 V 13.0%

How Many Mitsubishi Electric PV-MF180UD4 Modules Fit in a Cold-Weather String?

Verify freezing-morning voltage rise for Mitsubishi Electric PV-MF180UD4 (30.4 V STC) before wiring 600 V or 1,000 V strings.

Computed from Voc=30.4V and beta_Voc=-0.341%/C across design ambient temperatures.
Ambient Min TempCold Voc / PanelMax Panels (600 V)600 V String VocMax Panels (1000 V)
-20 C (-4 F) 35.06 V 17 panels 596.0 V 28 panels
-10 C (14 F) 34.03 V 17 panels 578.5 V 29 panels
0 C (32 F) 32.99 V 18 panels 593.8 V 30 panels
25 C (77 F STC) 30.4 V 19 panels 577.6 V 32 panels

Which Cross-Brand Solar Modules Compare Closest to Mitsubishi Electric PV-MF180UD4?

Four comparable CEC modules such as Gintung Energy ASEC-180G6S (180.0 W) for side-by-side solar quote checks. All figures trace directly to published federal energy filings, state electrical boards, CEC datasheets, and NFPA 70 NEC tables.

Nearest CEC-listed competing brands by STC power and open-circuit voltage.
Alternative ModuleSTC (W)Delta vs ThisVoc (V)Eff (%)PTC/STC
Gintung Energy ASEC-180G6S
Gintung Energy
180.0 W Tie (0 W) 29.73 V 13.8% 88.7%
APOS Energy AP180
APOS Energy
180.0 W Tie (0 W) 29.72 V 13.42% 88.9%
Gintung Energy ASEC-180G6M
Gintung Energy
180.0 W Tie (0 W) 29.51 V 13.8% 89.2%
Lightway Green New Energy LW180(23)P1310x990
Lightway Green New Energy
180.0 W Tie (0 W) 29.5 V 14.02% 89.5%
What to Check & Best-Fit Scenarios

What Are the Design Limits and Best-Fit Uses for Mitsubishi Electric PV-MF180UD4?

Evaluate Mitsubishi Electric PV-MF180UD4 (180.0 W STC, 30.4 V Voc) against your roof geometry, winter climate, and inverter voltage ceiling before finalizing bids.

  • Winter overvoltage boundary: at -20 C (-4 F), Mitsubishi Electric PV-MF180UD4 reaches 35.06 V per panel—exceeding 17 panels in series voids 600 V inverter warranties.
  • Footprint constraint: 45 panels for an 8 kW build require 670 sq ft of unshaded roof plane — useful on tight dormer roofs or battery cabins, though 8 kW requires 45 panels (670 sq ft).
  • 2026 tax credit baseline: cash residential installs of Mitsubishi Electric PV-MF180UD4 carry 0% federal 25D credit after 2025-12-31, making 18.54 c/kWh+ utility avoidance key.

Mitsubishi Electric PV-MF180UD4 8 kW Residential Fit

Needs 45 modules (670 sq ft) with a 15 A string OCPD, offsetting ~$2,027/yr at US average tariffs.

Cold-Climate String Design (-10 C / -20 C)

Cap 600 V series strings at 17 panels (-10 C) or 17 panels (-20 C), or compare Gintung Energy ASEC-180G6S.

Bifacial / High-Heat Roof Check

Monofacial backsheet sealing targets flush dark shingle rooftop mounts. Real-world output tracks 160.7 W PTC.

Which Homeowner Electrical & Solar Questions Come Up Most Often?

Technical answers for Mitsubishi Electric PV-MF180UD4 by Mitsubishi Electric grounded in CEC test data and NEC 690.7/690.8 limits.

Why is Mitsubishi Electric PV-MF180UD4 PTC wattage (160.7 W) lower than STC (180.0 W)?

Laboratory STC tests at 25 C cell temperature, whereas real rooftop heat lowers voltage to 160.7 W PTC (89.3% retention) across Mitsubishi Electric PV-MF180UD4's 1.384 m2 aperture.

Who should skip Mitsubishi Electric PV-MF180UD4 on a complex residential roof?

Homes with chopped dormers or heavy chimney shade should compare smaller modules or microinverters if 45 Mitsubishi Electric PV-MF180UD4 panels (670 sq ft) leave unusable roof gaps vs. Gintung Energy ASEC-180G6S.

What is the 1,000 V commercial string limit for Mitsubishi Electric PV-MF180UD4?

On 1,000 V commercial inverters at -10 C (34.03 V cold Voc), Mitsubishi Electric PV-MF180UD4 fits up to 29 panels per series string. Review current municipal Authority Having Jurisdiction (AHJ) code amendments affecting Mitsubishi Electric PV-MF180UD4.

Sources

  1. CEC Solar Equipment List — PV Modules (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
  2. NFPA 70 National Electrical Code (Section Numbers & Standard Engineering Tables Only) — National Fire Protection Association (NFPA), 2020 / 2023 / 2026 Editions (retrieved 2026-11-23)

Which Regional Electrical & Panel Upgrade Metros Compare Closest?

Check Wiring & Solar Numbers Before Getting Quotes

Verify panel capacity for solar, electrical box space, proper wire gauge for EV chargers, and 2026 home solar payback using local utility rates.

Verify State-Licensed Electricians & Safety Recalls

Look up active state electrician licenses (TX, WA, CO, OR, DE), check local power-outage history, and inspect federal product recall notices.