JA Solar JAM72S10-390/PR — CEC Solar Module Specifications

Manufacturer: JA Solar Registry: CEC Verified Engineering Specification

JA Solar JAM72S10-390/PR is a 390.0 W STC (365.0 W PTC) Mono-c-Si solar module ranking #10,321 of 21,677 CEC listings (top 49.5%; higher than 50.5% of peers). It delivers 20.0% efficiency, 48.91 V Voc at 25 C, and 53.46 V cold Voc at -10 C (11 panels max per 600 V string).

STC Wattage
390.0 W
PTC Wattage
365.0 W
Voc @ 25C
48.91 V
Efficiency
20.0%
Wall-mounted residential hybrid solar inverter and modular battery cabinet piped with galvanized EMT conduit
Wall-mounted residential hybrid solar inverter and modular battery cabinet piped with galvanized EMT conduit

How Does JA Solar JAM72S10-390/PR Compare Against Peer CEC Listings?

Solar engineering breakdown for JA Solar JAM72S10-390/PR: PTC thermal retention, roof footprint, and cold Voc string bounds.

Measured at 390.0 W STC and 365.0 W PTC, JA Solar JAM72S10-390/PR sits +5.0 W vs all-CEC median (top 49.5%; higher than 50.5% of peers) among 21,677 listed modules. Power density reaches 200.0 W/m2 (0.09 percentage points above 19.91% CEC median). Higher 48.91 V open-circuit voltage caps 600 V residential strings at 11 panels at 14 F (-10 C), whereas 1,000 V commercial inverters handle up to 18 panels in series. Alternative peer CSI Solar Co Ltd CS3U-390MS rates 390.0 W.

Where Does JA Solar JAM72S10-390/PR Fall Across Listed CEC Models?

Distribution marker showing JA Solar JAM72S10-390/PR (390.0 W) relative to the 385.0 W all-CEC solar panel median.

STC Power Distribution Across 21,677 CEC Solar ModulesMarks where JA Solar JAM72S10-390/PR (390.0 W STC) stands relative to CEC photovoltaic modules. 18-79 W STC: 68 entries1879-140 W STC: 170 entries140-202 W STC: 413 entries202-263 W STC: 1,883 entries202263-325 W STC: 4,202 entries325-386 W STC: 4,219 entries386-448 W STC: 4,695 entries386448-509 W STC: 1,584 entries509-571 W STC: 2,290 entries571-632 W STC: 1,371 entries571632-694 W STC: 534 entries694-755 W STC: 248 entries694Median 385 W STCJA Solar JAM72S10-: 390.0 W

What Dataset Percentiles Define JA Solar JAM72S10-390/PR?

Dataset percentiles tracking JA Solar JAM72S10-390/PR power output, thermal retention ratio, and aperture efficiency against 21,677 models.

JA Solar JAM72S10-390/PR Engineering BenchmarksPercentile comparison of JA Solar JAM72S10-390/PR wattage, thermal retention, and efficiency. 0% (Low)50% Median100% (Top)STC Wattage390.0 WPTC/STC Retention93.6%Module Efficiency20.0%

What Do the Dataset Ranks Show for JA Solar JAM72S10-390/PR?

Benchmark highlights for JA Solar JAM72S10-390/PR covering STC output, efficiency, 8 kW footprint, and OCPD breaker size.

Rank #10,321 / 21,677

Top 49.5% STC Output

390.0 W STC (+5.0 W vs all-CEC median) vs 410.0 W Mono-c-Si median.

Eff #10,442

20.0% Aperture Efficiency

Power density 200.0 W/m2 (0.09 percentage points above 19.91% CEC median). PTC/STC ratio: 93.6% (rank #6,726).

NEC 690.7 Limit

11 Panels Max @ -10 C (600 V)

Cold Voc reaches 53.46 V at -10 C (588.1 V string) and 54.76 V at -20 C (10 max).

8 kW Reference Array

21 Panels = 8,190 W STC

Occupies 40.9 m2 (441 sq ft) producing 7,665 W PTC; NEC 690.8 OCPD floor is 15.85 A (20 A breaker).

NEC 690.7(A) Cold-Temperature Voc & 690.8 OCPD Formula

Voc_cold = 48.91 * (1 + (-0.266/100) * (-10 - 25)) = 53.46 V | OCPD = 1.56 * 10.16 = 15.85 A

Inputs from CEC Modules.csv for JA Solar JAM72S10-390/PR: Voc=48.91 V, beta_Voc=-0.266%/C, Isc=10.16 A, STC=390.0 W, Area=1.95 m2.

Result: 11 panels max on 600 V (588.1 V); 21 panels for 8 kW (441 sq ft).

What Are the Published CEC Specifications for JA Solar JAM72S10-390/PR?

Official CEC datasheet figures for JA Solar JAM72S10-390/PR (Mono-c-Si) used in utility interconnection and permit reviews. Data intervals combine current 2025 federal utility and BLS wage releases with verified state electrical board rosters.

Official California Energy Commission (NREL SAM) test parameters for JA Solar JAM72S10-390/PR.
ParameterMeasured / Listed ValueEngineering Significance
Nameplate Power (STC) 390.0 W Rated DC output under Standard Test Conditions (1000 W/m2, 25C cell)
Real-World Output (PTC) 365.0 W (93.6% STC) PVUSA Test Conditions rating used for utility interconnection
Open-Circuit Voltage (Voc) 48.91 V Primary cold-weather string sizing limit under NEC 690.7
Short-Circuit Current (Isc) 10.16 A Determines 156% (1.25x1.25) OCPD fuse/breaker sizing under NEC 690.8
Max Power Voltage / Current 40.55 V / 9.62 A Inverter MPPT operating window alignment
Voc Temp Coefficient (beta_Voc) -0.266 %/C Negative slope governing voltage rise below 25C
Module Efficiency & Area 20.0% (1.95 m2) Array roof footprint density
Cell Count & Technology 72 cells (Mono-c-Si) Monofacial backsheet

How Many JA Solar JAM72S10-390/PR Panels Build a 6 kW, 8 kW, or 10 kW Array?

How many JA Solar JAM72S10-390/PR modules and square feet are required for 6 kW, 8 kW, and 10 kW home solar arrays.

Estimated panel count, roof square footage, and Year-1 bill offset across low, average, and high US utility tariffs (0% 25D).
Target ArrayPanelsActual DCRoof AreaUS Avg ($/yr)CA High ($/yr)
6 kW Class 16 6.24 kW 336 sq ft $1,562 $2,641
8 kW Class 21 8.19 kW 441 sq ft $2,050 $3,466
10 kW Class 26 10.14 kW 546 sq ft $2,538 $4,292

Which Sibling Wattage & Trim Variants Belong to This JA Solar Series?

Consolidated JA Solar wattage variants sharing the JA Solar JAM72S10-390/PR mechanical and cell layout. Regional housing vintage, storm hazard frequency, and wholesale utility prices directly govern residential upgrade payback across jurisdictions.

Sibling CEC listings grouped into the JA Solar JAM72S10-390/PR wattage tier to avoid duplicate 5W/trim datasheets.
Model VariantSTC (W)PTC (W)Voc (V)Vmp (V)Eff (%)
JA Solar JAM72S10-385/PR 385.0 W 360.2 W 48.62 V 40.24 V 19.74%
JA Solar JAM72S10-390/PR 390.0 W 365.0 W 48.91 V 40.55 V 20.0%
JA Solar JAM72S10-395/PR 395.0 W 369.8 W 49.21 V 40.85 V 20.26%

How Many JA Solar JAM72S10-390/PR Modules Fit in a Cold-Weather String?

NEC 690.7(A) winter string table preventing overvoltage trips on JA Solar JAM72S10-390/PR (53.46 V at 14 F).

Computed from Voc=48.91V and beta_Voc=-0.266%/C across design ambient temperatures.
Ambient Min TempCold Voc / PanelMax Panels (600 V)600 V String VocMax Panels (1000 V)
-20 C (-4 F) 54.76 V 10 panels 547.6 V 18 panels
-10 C (14 F) 53.46 V 11 panels 588.1 V 18 panels
0 C (32 F) 52.16 V 11 panels 573.8 V 19 panels
25 C (77 F STC) 48.91 V 12 panels 586.9 V 20 panels

Which Cross-Brand Solar Modules Compare Closest to JA Solar JAM72S10-390/PR?

Competing CEC solar panels closest to JA Solar JAM72S10-390/PR in nameplate wattage and Voc, starting with CSI Solar Co Ltd CS3U-390MS.

Nearest CEC-listed competing brands by STC power and open-circuit voltage.
Alternative ModuleSTC (W)Delta vs ThisVoc (V)Eff (%)PTC/STC
CSI Solar Co Ltd CS3U-390MS
CSI Solar Co Ltd
390.0 W Tie (0 W) 48.2 V 20.31% 93.2%
EMMVEE Photovoltaic Power Private Limited E385M72
EMMVEE Photovoltaic Power Private Limited
385.0 W -5.0 W 48.9 V 19.32% 92.0%
Amerisolar-Worldwide Energy and Manufacturing USA Co Ltd AS-6M-BHC-395W
Amerisolar-Worldwide Energy and Manufacturing USA Co Ltd
395.0 W +5.0 W 48.7 V 20.26% 92.9%
Amerisolar-Worldwide Energy and Manufacturing USA Co Ltd AS-6M-HC-395W
Amerisolar-Worldwide Energy and Manufacturing USA Co Ltd
395.0 W +5.0 W 48.7 V 20.68% 92.5%
What to Check & Best-Fit Scenarios

What Are the Design Limits and Best-Fit Uses for JA Solar JAM72S10-390/PR?

Evaluate JA Solar JAM72S10-390/PR (390.0 W STC, 48.91 V Voc) against your roof geometry, winter climate, and inverter voltage ceiling before finalizing bids.

  • Winter overvoltage boundary: at -20 C (-4 F), JA Solar JAM72S10-390/PR reaches 54.76 V per panel—exceeding 10 panels in series voids 600 V inverter warranties.
  • Footprint constraint: 21 panels for an 8 kW build require 441 sq ft of unshaded roof plane — well-proportioned for residential pitched roofs needing 21 panels (441 sq ft) for an 8 kW array.
  • 2026 tax credit baseline: cash residential installs of JA Solar JAM72S10-390/PR carry 0% federal 25D credit after 2025-12-31, making 18.54 c/kWh+ utility avoidance key.

JA Solar JAM72S10-390/PR 8 kW Residential Fit

Needs 21 modules (441 sq ft) with a 20 A string OCPD, offsetting ~$2,050/yr at US average tariffs.

Cold-Climate String Design (-10 C / -20 C)

Cap 600 V series strings at 11 panels (-10 C) or 10 panels (-20 C), or compare CSI Solar Co Ltd CS3U-390MS.

Bifacial / High-Heat Roof Check

Monofacial backsheet sealing targets flush dark shingle rooftop mounts. Real-world output tracks 365.0 W PTC.

Which Homeowner Electrical & Solar Questions Come Up Most Often?

Technical answers for JA Solar JAM72S10-390/PR by JA Solar grounded in CEC test data and NEC 690.7/690.8 limits.

How many JA Solar JAM72S10-390/PR panels fit on a 600 V winter solar string?

At -10 C (14 F), JA Solar JAM72S10-390/PR cold Voc rises from 48.91 V to 53.46 V (beta_Voc -0.266%/C), capping a 600 V string at 11 panels (588.1 V).

How much roof area does an 8 kW array of JA Solar JAM72S10-390/PR need?

An 8 kW DC system uses 21 JA Solar JAM72S10-390/PR modules (8,190 W STC / 7,665 W PTC), covering roughly 441 sq ft and saving ~$2,050/yr at 18.54 c/kWh.

How does JA Solar JAM72S10-390/PR compare against CSI Solar Co Ltd CS3U-390MS?

JA Solar JAM72S10-390/PR outputs 390.0 W STC (48.91 V Voc, rank #10,321 of 21,677), while CSI Solar Co Ltd CS3U-390MS delivers 390.0 W STC; both comply with 2026 NEC 690.7 string sizing rules.

Sources

  1. CEC Solar Equipment List — PV Modules (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
  2. NFPA 70 National Electrical Code (Section Numbers & Standard Engineering Tables Only) — National Fire Protection Association (NFPA), 2020 / 2023 / 2026 Editions (retrieved 2026-11-23)

Which Regional Electrical & Panel Upgrade Metros Compare Closest?