JA Solar JAM60S10-335/PR — CEC Solar Module Specifications

Manufacturer: JA Solar Registry: CEC Verified Engineering Specification

JA Solar JAM60S10-335/PR is a 335.0 W STC (313.8 W PTC) Mono-c-Si solar module ranking #13,844 of 21,677 CEC listings (below all-CEC median; higher than 34.7% of peers). It delivers 20.55% efficiency, 41.12 V Voc at 25 C, and 44.95 V cold Voc at -10 C (13 panels max per 600 V string).

STC Wattage
335.0 W
PTC Wattage
313.8 W
Voc @ 25C
41.12 V
Efficiency
20.55%
Wall-mounted residential hybrid solar inverter and modular battery cabinet piped with galvanized EMT conduit
Wall-mounted residential hybrid solar inverter and modular battery cabinet piped with galvanized EMT conduit

How Does JA Solar JAM60S10-335/PR Compare Against Peer CEC Listings?

Solar engineering breakdown for JA Solar JAM60S10-335/PR: PTC thermal retention, roof footprint, and cold Voc string bounds.

Across 5,889 Mono-c-Si listings from JA Solar and peers, JA Solar JAM60S10-335/PR stands 75.0 W below the 410.0 W Mono-c-Si median and strong 93.7% PTC-to-STC heat retention (#6,162 of 21,677). Sizing 6 kW (18 panels) to 10 kW (30 panels) yields $1,509-$2,515/yr in baseline US bill offset. Mid-range 41.12 V open-circuit voltage allows up to 13 panels per 600 V string at 14 F.

Where Does JA Solar JAM60S10-335/PR Fall Across Listed CEC Models?

Distribution marker showing JA Solar JAM60S10-335/PR (335.0 W) relative to the 385.0 W all-CEC solar panel median.

STC Power Distribution Across 21,677 CEC Solar ModulesMarks where JA Solar JAM60S10-335/PR (335.0 W STC) stands relative to CEC photovoltaic modules. 18-79 W STC: 68 entries1879-140 W STC: 170 entries140-202 W STC: 413 entries202-263 W STC: 1,883 entries202263-325 W STC: 4,202 entries325-386 W STC: 4,219 entries386-448 W STC: 4,695 entries386448-509 W STC: 1,584 entries509-571 W STC: 2,290 entries571-632 W STC: 1,371 entries571632-694 W STC: 534 entries694-755 W STC: 248 entries694Median 385 W STCJA Solar JAM60S10-: 335.0 W

What Dataset Percentiles Define JA Solar JAM60S10-335/PR?

Dataset percentiles tracking JA Solar JAM60S10-335/PR power output, thermal retention ratio, and aperture efficiency against 21,677 models.

JA Solar JAM60S10-335/PR Engineering BenchmarksPercentile comparison of JA Solar JAM60S10-335/PR wattage, thermal retention, and efficiency. 0% (Low)50% Median100% (Top)STC Wattage335.0 WPTC/STC Retention93.7%Module Efficiency20.55%

What Do the Dataset Ranks Show for JA Solar JAM60S10-335/PR?

Benchmark highlights for JA Solar JAM60S10-335/PR covering STC output, efficiency, 8 kW footprint, and OCPD breaker size.

Rank #13,844 / 21,677

335.0 W STC · Higher Than 34.7%

335.0 W STC (-50.0 W vs all-CEC median) vs 410.0 W Mono-c-Si median.

Eff #8,330

20.55% Aperture Efficiency

Power density 205.5 W/m2 (0.64 percentage points above 19.91% CEC median). PTC/STC ratio: 93.7% (rank #6,162).

NEC 690.7 Limit

13 Panels Max @ -10 C (600 V)

Cold Voc reaches 44.95 V at -10 C (584.4 V string) and 46.04 V at -20 C (13 max).

8 kW Reference Array

24 Panels = 8,040 W STC

Occupies 39.1 m2 (421 sq ft) producing 7,531 W PTC; NEC 690.8 OCPD floor is 16.19 A (20 A breaker).

NEC 690.7(A) Cold-Temperature Voc & 690.8 OCPD Formula

Voc_cold = 41.12 * (1 + (-0.266/100) * (-10 - 25)) = 44.95 V | OCPD = 1.56 * 10.38 = 16.19 A

Inputs from CEC Modules.csv for JA Solar JAM60S10-335/PR: Voc=41.12 V, beta_Voc=-0.266%/C, Isc=10.38 A, STC=335.0 W, Area=1.63 m2.

Result: 13 panels max on 600 V (584.4 V); 24 panels for 8 kW (421 sq ft).

What Are the Published CEC Specifications for JA Solar JAM60S10-335/PR?

Official CEC datasheet figures for JA Solar JAM60S10-335/PR (Mono-c-Si) used in utility interconnection and permit reviews. Review related calculators, peer benchmarks, and source citations below to validate design assumptions for your electrical service.

Official California Energy Commission (NREL SAM) test parameters for JA Solar JAM60S10-335/PR.
ParameterMeasured / Listed ValueEngineering Significance
Nameplate Power (STC) 335.0 W Rated DC output under Standard Test Conditions (1000 W/m2, 25C cell)
Real-World Output (PTC) 313.8 W (93.7% STC) PVUSA Test Conditions rating used for utility interconnection
Open-Circuit Voltage (Voc) 41.12 V Primary cold-weather string sizing limit under NEC 690.7
Short-Circuit Current (Isc) 10.38 A Determines 156% (1.25x1.25) OCPD fuse/breaker sizing under NEC 690.8
Max Power Voltage / Current 34.36 V / 9.75 A Inverter MPPT operating window alignment
Voc Temp Coefficient (beta_Voc) -0.266 %/C Negative slope governing voltage rise below 25C
Module Efficiency & Area 20.55% (1.63 m2) Array roof footprint density
Cell Count & Technology 60 cells (Mono-c-Si) Monofacial backsheet

How Many JA Solar JAM60S10-335/PR Panels Build a 6 kW, 8 kW, or 10 kW Array?

How many JA Solar JAM60S10-335/PR modules and square feet are required for 6 kW, 8 kW, and 10 kW home solar arrays.

Estimated panel count, roof square footage, and Year-1 bill offset across low, average, and high US utility tariffs (0% 25D).
Target ArrayPanelsActual DCRoof AreaUS Avg ($/yr)CA High ($/yr)
6 kW Class 18 6.03 kW 316 sq ft $1,509 $2,552
8 kW Class 24 8.04 kW 421 sq ft $2,012 $3,403
10 kW Class 30 10.05 kW 526 sq ft $2,515 $4,253

Which Sibling Wattage & Trim Variants Belong to This JA Solar Series?

Consolidated JA Solar wattage variants sharing the JA Solar JAM60S10-335/PR mechanical and cell layout. All figures trace directly to published federal energy filings, state electrical boards, CEC datasheets, and NFPA 70 NEC tables.

Sibling CEC listings grouped into the JA Solar JAM60S10-335/PR wattage tier to avoid duplicate 5W/trim datasheets.
Model VariantSTC (W)PTC (W)Voc (V)Vmp (V)Eff (%)
JA Solar JAM60S10-325/PR 325.0 W 304.2 W 40.56 V 33.87 V 19.94%
JA Solar JAM60S10-330/PR 330.0 W 309.0 W 40.84 V 34.13 V 20.25%
JA Solar JAM60S10-335/PR 335.0 W 313.8 W 41.12 V 34.36 V 20.55%
JA Solar JAM60S10-340/PR 340.0 W 318.6 W 41.36 V 34.63 V 20.86%

How Many JA Solar JAM60S10-335/PR Modules Fit in a Cold-Weather String?

NEC 690.7(A) winter string table preventing overvoltage trips on JA Solar JAM60S10-335/PR (44.95 V at 14 F).

Computed from Voc=41.12V and beta_Voc=-0.266%/C across design ambient temperatures.
Ambient Min TempCold Voc / PanelMax Panels (600 V)600 V String VocMax Panels (1000 V)
-20 C (-4 F) 46.04 V 13 panels 598.5 V 21 panels
-10 C (14 F) 44.95 V 13 panels 584.4 V 22 panels
0 C (32 F) 43.85 V 13 panels 570.1 V 22 panels
25 C (77 F STC) 41.12 V 14 panels 575.7 V 24 panels

Which Cross-Brand Solar Modules Compare Closest to JA Solar JAM60S10-335/PR?

Competing CEC solar panels closest to JA Solar JAM60S10-335/PR in nameplate wattage and Voc, starting with Dehui Solar Power (Vietnam) CoLtd DH-M860F 335W.

Nearest CEC-listed competing brands by STC power and open-circuit voltage.
Alternative ModuleSTC (W)Delta vs ThisVoc (V)Eff (%)PTC/STC
Dehui Solar Power (Vietnam) CoLtd DH-M860F 335W
Dehui Solar Power (Vietnam) CoLtd
335.0 W Tie (0 W) 40.8 V 20.81% 93.0%
Auxin Solar AXNG1M335B
Auxin Solar
335.0 W Tie (0 W) 40.75 V 20.43% 93.2%
Dehui Solar Power (Vietnam) CoLtd DH-M860W 335W
Dehui Solar Power (Vietnam) CoLtd
335.0 W Tie (0 W) 40.7 V 21.07% 92.6%
Aptos Solar Technology LLC DNA-120-MF23-335W {Blk}
Aptos Solar Technology LLC
335.0 W Tie (0 W) 40.44 V 19.85% 90.8%
What to Check & Best-Fit Scenarios

What Are the Design Limits and Best-Fit Uses for JA Solar JAM60S10-335/PR?

Evaluate JA Solar JAM60S10-335/PR (335.0 W STC, 41.12 V Voc) against your roof geometry, winter climate, and inverter voltage ceiling before finalizing bids.

  • Winter overvoltage boundary: at -20 C (-4 F), JA Solar JAM60S10-335/PR reaches 46.04 V per panel—exceeding 13 panels in series voids 600 V inverter warranties.
  • Footprint constraint: 24 panels for an 8 kW build require 421 sq ft of unshaded roof plane — useful on tight dormer roofs or battery cabins, though 8 kW requires 24 panels (421 sq ft).
  • 2026 tax credit baseline: cash residential installs of JA Solar JAM60S10-335/PR carry 0% federal 25D credit after 2025-12-31, making 18.54 c/kWh+ utility avoidance key.

JA Solar JAM60S10-335/PR 8 kW Residential Fit

Needs 24 modules (421 sq ft) with a 20 A string OCPD, offsetting ~$2,012/yr at US average tariffs.

Cold-Climate String Design (-10 C / -20 C)

Cap 600 V series strings at 13 panels (-10 C) or 13 panels (-20 C), or compare Dehui Solar Power (Vietnam) CoLtd DH-M860F 335W.

Bifacial / High-Heat Roof Check

Monofacial backsheet sealing targets flush dark shingle rooftop mounts. Real-world output tracks 313.8 W PTC.

Which Homeowner Electrical & Solar Questions Come Up Most Often?

Technical answers for JA Solar JAM60S10-335/PR by JA Solar grounded in CEC test data and NEC 690.7/690.8 limits.

What fuse or breaker size does NEC 690.8 require for JA Solar JAM60S10-335/PR?

Multiplying JA Solar JAM60S10-335/PR's 10.38 A short-circuit current by 1.56 equals 16.19 A minimum ampacity, requiring at least a 20 A overcurrent fuse or breaker.

Can JA Solar JAM60S10-335/PR pair with microinverters instead of a 600 V string inverter?

Yes—if the microinverter DC input ceiling exceeds 44.95 V cold Voc at 14 F and handles 10.38 A Isc; string inverters cap JA Solar JAM60S10-335/PR at 13 panels on 600 V.

Is JA Solar JAM60S10-335/PR eligible for the 30% federal 25D solar credit in 2026?

No. Federal Section 25D expired December 31, 2025 under Public Law 119-21, so 2026 cash installs of JA Solar JAM60S10-335/PR rely on utility bill offset (~$2,012/yr at 8 kW) rather than 25D.

Sources

  1. CEC Solar Equipment List — PV Modules (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
  2. NFPA 70 National Electrical Code (Section Numbers & Standard Engineering Tables Only) — National Fire Protection Association (NFPA), 2020 / 2023 / 2026 Editions (retrieved 2026-11-23)

Which Regional Electrical & Panel Upgrade Metros Compare Closest?

Check Wiring & Solar Numbers Before Getting Quotes

Verify panel capacity for solar, electrical box space, proper wire gauge for EV chargers, and 2026 home solar payback using local utility rates.

Verify State-Licensed Electricians & Safety Recalls

Look up active state electrician licenses (TX, WA, CO, OR, DE), check local power-outage history, and inspect federal product recall notices.