Yaskawa Solectria Solar: XGI 1500-166/166-UL-A {600V} outputs 166,000 W AC at 600 V, 3-phase (159.7 A continuous, 200 A OCPD), ranking #86 of 2,343 CEC inverters at 98.47% efficiency with a 860-1,250 V MPPT window and 1,250 V DC limit. All figures reconcile directly against federal energy archives, state electrical licensing boards, California Energy Commission datasheets, and National Electrical Code engineering constants.
- AC Output (Paco)
- 166,000 W
- AC Voltage
- 600 V, 3-phase
- Min PV Breaker
- 200 A (3/0 AWG Cu)
- CEC Efficiency
- 98.47%
How Does Yaskawa Solectria Solar: XGI 1500-166/166-UL-A {600V} Compare Against Peer CEC Listings?
CEC efficiency rank (#86), 860-1,250 V MPPT tracking, and panel fit for Yaskawa Solectria Solar: XGI 1500-166/166-UL-A {600V}.
Operating at 600 V, 3-phase, Yaskawa Solectria Solar: XGI 1500-166/166-UL-A {600V} converts DC array energy at 98.47% CEC weighted efficiency (top 4.1%; higher than 95.9% of peers) with a 1,250 V max DC input and 168.581 A max input current for NEC 690.7 string safety. Compare this 166,000 W grid-tied PV inverter directly with Ginlong Technologies Co Ltd: Solis-185K-EHV-5G-US-PLUS {600V} (172,987 W). Commercial 600 V, 3-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (600V) or NEC 705.11 supply-side tap.
Where Does Yaskawa Solectria Solar: XGI 1500-166/166-UL-A {600V} Fall Across Listed CEC Models?
CEC inverter wattage histogram highlighting Yaskawa Solectria Solar: XGI 1500-166/166-UL-A {600V} at 166,000 W continuous AC output.
What Dataset Percentiles Define Yaskawa Solectria Solar: XGI 1500-166/166-UL-A {600V}?
Dataset percentiles comparing Yaskawa Solectria Solar: XGI 1500-166/166-UL-A {600V} against 2,343 certified grid-support inverters nationwide. Compare thermal ratings, overcurrent protection caps, and continuous load headroom carefully before expanding an existing home service panel.
What Do the Dataset Ranks Show for Yaskawa Solectria Solar: XGI 1500-166/166-UL-A {600V}?
Engineering highlights for Yaskawa Solectria Solar: XGI 1500-166/166-UL-A {600V} covering efficiency, 3/0 AWG Cu feeder, and panel compatibility.
98.47% CEC Weighted Efficiency
+0.19 pts vs the 98.28% 600 V median; overall power rank #262 (166,000 W, top 11.3%; higher than 88.7% of peers).
200 A Required Backfeed OCPD
125% x 159.7 A = 199.6 A -> 200 A standard OCPD using 3/0 AWG Cu (75 C).
860 V - 1,250 V (Max 1,250 V DC)
Tracking span of 390.0 V; active in CEC directory (grid-tied PV inverter).
Supply-Side Tap (705.11) / Dedicated Switchboard
Evaluated for 600 V, 3-phase switchgear (200A Bus / 200A Main (600V) to 1,200A Bus / 1,200A Main (600V)) under NEC 705.12 / 705.11.
NEC 705.12 Backfeed OCPD & 120% Busbar Formula
I_cont = 166000.0W / 600 V 3-phase -> 159.7 A | Breaker >= 1.25 * 159.7 = 199.6 A -> 200 A
CEC Inverters.csv for Yaskawa Solectria Solar: XGI 1500-166/166-UL-A {600V}: Paco=166000.0 W, Vac=600 V, Vdcmax=1250.0 V, Eff=98.47%.
Result: Min 200 A breaker & 3/0 AWG Cu (75 C); 1,200A Bus / 1,200A Main (600V): PASS (120% Commercial Busbar).
What Are the Published CEC Specifications for Yaskawa Solectria Solar: XGI 1500-166/166-UL-A {600V}?
California Energy Commission Solar Equipment List parameters for Yaskawa Solectria Solar: XGI 1500-166/166-UL-A {600V} (grid-tied PV inverter) interconnection.
| Parameter | Measured / Listed Value | Engineering Significance |
|---|---|---|
| Max Continuous AC Power (Paco) | 166,000 W | Determines required backfeed OCPD size via 125% continuous rule |
| Nominal AC Voltage (Vac) | 600 V, 3-phase | 240V split-phase residential vs. 208V/480V/MV commercial |
| Max DC Input Voltage (Vdcmax) | 1,250 V | Hard ceiling for cold-weather PV string Voc under NEC 690.7 |
| MPPT Operating Range | 860 V - 1,250 V | Optimal DC string Vmp window for full power harvest |
| Max Input DC Current (Idcmax) | 168.581 A | Used to verify parallel string combiner limits |
| CEC Weighted Efficiency | 98.47% | Calculated AC/DC conversion ratio from CEC test protocol |
| Inverter Topology | Hybrid: No (Grid-Tied PV) | CEC Solar Equipment List grid-support certification |
What Switchgear Limits Apply to Yaskawa Solectria Solar: XGI 1500-166/166-UL-A {600V} (600 V, 3-phase)?
Panelboard and switchgear backfeed allowances for Yaskawa Solectria Solar: XGI 1500-166/166-UL-A {600V} (200 A OCPD). Always verify current state NEC adoption cycles, local utility interconnection tariffs, and panel busbar ratings before pulling project permits.
| Switchboard / Interconnect | 120% Max Backfeed | Required PV OCPD | Compliance Verdict |
|---|---|---|---|
| 200A Bus / 200A Main (600V) | 40 A | 200 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| 400A Bus / 400A Main (600V) | 80 A | 200 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| 600A Bus / 600A Main (600V) | 120 A | 200 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| 800A Bus / 800A Main (600V) | 160 A | 200 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| 1,200A Bus / 1,200A Main (600V) | 240 A | 200 A | PASS (120% Commercial Busbar) |
Which CEC PV Module Strings Pair With Yaskawa Solectria Solar: XGI 1500-166/166-UL-A {600V}?
Representative PV panel pairings verified under NEC 690.7 cold Voc for Yaskawa Solectria Solar: XGI 1500-166/166-UL-A {600V}.
| CEC Module | STC (W) | -10 C Voc | Valid String Range | Max String DC |
|---|---|---|---|---|
| AXITEC AC-590TGB/144TS | 590.0 W | 56.24 V | 21 to 22 panels | 12.98 kW |
| Aptos Solar Technology LLC DNA-108-MFN10-440W | 440.0 W | 42.15 V | 26 to 29 panels | 12.76 kW |
| Boviet Solar Technology Co Ltd BVM7610M-425-H-HC-BF | 425.0 W | 44.75 V | 25 to 27 panels | 11.47 kW |
| CSI Solar Co Ltd CS6P-200P | 200.0 W | 40.6 V | 30 panels (fixed) | 6.0 kW |
Which Competing Grid-Support Inverters Compare to Yaskawa Solectria Solar: XGI 1500-166/166-UL-A {600V}?
Four alternative CEC inverters matched to Yaskawa Solectria Solar: XGI 1500-166/166-UL-A {600V} (166,000 W AC), led by Ginlong Technologies Co Ltd: Solis-185K-EHV-5G-US-PLUS {600V}.
| Alternative Inverter | AC Output | Delta | Vac | Max DC | CEC Eff |
|---|---|---|---|---|---|
| Ginlong Technologies Co Ltd: Solis-185K-EHV-5G-US-PLUS {600V} Ginlong Technologies Co Ltd |
172,987 W | +6987 W | 600.0 V | 1300.0 V | 98.07% |
| Xiamen Kehua Digital Energy Tech Co Ltd: BCS175K-B-HM-US X2 {600V} Xiamen Kehua Digital Energy Tech Co Ltd |
175,017 W | +9017 W | 600.0 V | 1450.0 V | 98.34% |
| SMA America: SHP FLEX-US-21 {600V} SMA America |
150,079 W | -15921 W | 600.0 V | 1200.0 V | 98.52% |
| Xiamen Kehua Digital Energy Tech Co Ltd: BCS150K-B-HM-US X2 {600V} Xiamen Kehua Digital Energy Tech Co Ltd |
150,015 W | -15985 W | 600.0 V | 1450.0 V | 98.35% |
What Are the Interconnection Limits and Best-Fit Uses for Yaskawa Solectria Solar: XGI 1500-166/166-UL-A {600V}?
Check Yaskawa Solectria Solar: XGI 1500-166/166-UL-A {600V} (166,000 W AC, 200 A OCPD) against your main panel busbar, winter string Voc, and IEEE 1547 outage rules.
- Anti-islanding shutdown: grid-tied inverters shut off within 2 seconds during blackouts under IEEE 1547 unless paired with a battery microgrid interconnect.
- Busbar 120% limit: Commercial 600 V, 3-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (600V) or NEC 705.11 supply-side tap.
- Cold Voc hard ceiling: never allow winter open-circuit PV string voltage to exceed 1,250 V DC on Yaskawa Solectria Solar: XGI 1500-166/166-UL-A {600V}.
Yaskawa Solectria Solar: XGI 1500-166/166-UL-A {600V} Panel & Wire Spec
Size 75 C copper conductors at 3/0 AWG Cu on a 200 A OCPD breaker (159.7 A continuous).
Alternative Inverter Comparison
Compare efficiency (98.47%) and MPPT window (860-1,250 V) directly against Ginlong Technologies Co Ltd: Solis-185K-EHV-5G-US-PLUS {600V} (172,987 W).
Which Homeowner Electrical & Solar Questions Come Up Most Often?
Answers for Yaskawa Solectria Solar: XGI 1500-166/166-UL-A {600V} by Yaskawa Solectria Solar covering breaker sizing, MPPT limits, and 600 V, 3-phase interconnection.
What breaker and wire size does Yaskawa Solectria Solar: XGI 1500-166/166-UL-A {600V} require?
At 166,000 W continuous AC (600 V, 3-phase), continuous current is 159.7 A; 125% NEC 690.8/705.12 sizing requires a 200 A breaker and 3/0 AWG Cu (75 C) wire.
What commercial switchgear or feeder sizing does Yaskawa Solectria Solar: XGI 1500-166/166-UL-A {600V} require?
At 166,000 W AC and 600 V, 3-phase, continuous line current is 159.7 A, requiring a 200 A OCPD and 1,200A Bus / 1,200A Main (600V) or NEC 705.11 interconnection.
How does Yaskawa Solectria Solar: XGI 1500-166/166-UL-A {600V} compare to Ginlong Technologies Co Ltd: Solis-185K-EHV-5G-US-PLUS {600V}?
Yaskawa Solectria Solar: XGI 1500-166/166-UL-A {600V} delivers 166,000 W AC at 98.47% CEC efficiency with a 1,250 V DC ceiling, while Ginlong Technologies Co Ltd: Solis-185K-EHV-5G-US-PLUS {600V} outputs 172,987 W at 600 V, 3-phase.
Sources
- CEC Solar Equipment List — Grid-Support Inverters (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
- CEC Solar Equipment List — PV Modules (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
- NFPA 70 National Electrical Code (Section Numbers & Standard Engineering Tables Only) — National Fire Protection Association (NFPA), 2020 / 2023 / 2026 Editions (retrieved 2026-11-23)