Yaskawa Solectria Solar: XGI 1500-150/166-UL {600V} — CEC Inverter Specifications

Manufacturer: Yaskawa Solectria Solar Registry: CEC Verified Engineering Specification

Yaskawa Solectria Solar: XGI 1500-150/166-UL {600V} outputs 150,000 W AC at 600 V, 3-phase (144.3 A continuous, 200 A OCPD), ranking #81 of 2,343 CEC inverters at 98.48% efficiency with a 860-1,250 V MPPT window and 1,250 V DC limit. All figures reconcile directly against federal energy archives, state electrical licensing boards, California Energy Commission datasheets, and National Electrical Code engineering constants.

AC Output (Paco)
150,000 W
AC Voltage
600 V, 3-phase
Min PV Breaker
200 A (3/0 AWG Cu)
CEC Efficiency
98.48%
Wall-mounted residential hybrid solar inverter and modular battery cabinet piped with galvanized EMT conduit
Wall-mounted residential hybrid solar inverter and modular battery cabinet piped with galvanized EMT conduit

How Does Yaskawa Solectria Solar: XGI 1500-150/166-UL {600V} Compare Against Peer CEC Listings?

Breaker sizing (200 A), 3/0 AWG Cu wire rules, and DC input limits for Yaskawa Solectria Solar: XGI 1500-150/166-UL {600V}.

Classified as a grid-tied PV inverter (active in CEC directory), Yaskawa Solectria Solar: XGI 1500-150/166-UL {600V} requires 180.4 A design capacity -> 200 A breaker using 3/0 AWG Cu copper at 75 C terminals. Weighted efficiency sits at 98.48% (+1.66 pts vs overall CEC median) across 2,343 CEC models, while commercial 600 v, 3-phase switchgear interconnection uses 1,200a bus / 1,200a main (600v) or nec 705.11 supply-side tap.

Where Does Yaskawa Solectria Solar: XGI 1500-150/166-UL {600V} Fall Across Listed CEC Models?

Output power comparison showing where Yaskawa Solectria Solar: XGI 1500-150/166-UL {600V} sits among all 2,343 CEC-listed grid-support inverters.

AC Power Distribution Across Listed CEC Inverters (up to 25 kW)Shows where Yaskawa Solectria Solar: XGI 1500-150/166-UL {600V} (150,000 W AC) sits across CEC inverters. 190-2258 W AC: 584 entries1902258-4325 W AC: 158 entries4325-6392 W AC: 259 entries6392-8460 W AC: 270 entries63928460-10528 W AC: 258 entries10528-12595 W AC: 116 entries12595-14662 W AC: 17 entries1259514662-16730 W AC: 37 entries16730-18798 W AC: 7 entries18798-20865 W AC: 11 entries1879820865-22932 W AC: 5 entries22932-25000 W AC: 26 entries22932Median 7,680 W ACYaskawa Solectria : 150,000 W

What Dataset Percentiles Define Yaskawa Solectria Solar: XGI 1500-150/166-UL {600V}?

Relative ranking of Yaskawa Solectria Solar: XGI 1500-150/166-UL {600V} on continuous AC power, CEC weighted efficiency, and OCPD breaker current.

Yaskawa Solectria Solar: XGI 1500-150/166-UL {600V} Technical ThresholdsPercentile comparison for Yaskawa Solectria Solar: XGI 1500-150/166-UL {600V} AC output, weighted CEC efficiency, and OCPD sizing. 0% (Low)50% Median100% (Top)Rated AC Output150,000 WCEC Efficiency98.48%Backfeed Breaker200 A

What Do the Dataset Ranks Show for Yaskawa Solectria Solar: XGI 1500-150/166-UL {600V}?

Snapshot of Yaskawa Solectria Solar: XGI 1500-150/166-UL {600V} efficiency rank (#81), OCPD breaker size, MPPT span, and busbar verdict.

Eff #81 / 2,343

98.48% CEC Weighted Efficiency

+0.20 pts vs the 98.28% 600 V median; overall power rank #273 (150,000 W, top 11.8%; higher than 88.2% of peers).

NEC 705.12 Check

200 A Required Backfeed OCPD

125% x 144.3 A = 180.4 A -> 200 A standard OCPD using 3/0 AWG Cu (75 C).

MPPT Window

860 V - 1,250 V (Max 1,250 V DC)

Tracking span of 390.0 V; active in CEC directory (grid-tied PV inverter).

Commercial / 3-Phase Fit

Supply-Side Tap (705.11) / Dedicated Switchboard

Evaluated for 600 V, 3-phase switchgear (200A Bus / 200A Main (600V) to 1,200A Bus / 1,200A Main (600V)) under NEC 705.12 / 705.11.

NEC 705.12 Backfeed OCPD & 120% Busbar Formula

I_cont = 150000.0W / 600 V 3-phase -> 144.3 A | Breaker >= 1.25 * 144.3 = 180.4 A -> 200 A

CEC Inverters.csv for Yaskawa Solectria Solar: XGI 1500-150/166-UL {600V}: Paco=150000.0 W, Vac=600 V, Vdcmax=1250.0 V, Eff=98.48%.

Result: Min 200 A breaker & 3/0 AWG Cu (75 C); 1,200A Bus / 1,200A Main (600V): PASS (120% Commercial Busbar).

What Are the Published CEC Specifications for Yaskawa Solectria Solar: XGI 1500-150/166-UL {600V}?

Complete California Energy Commission grid-support inverter ratings and hybrid battery capabilities for Yaskawa Solectria Solar: XGI 1500-150/166-UL {600V}.

Official California Energy Commission (NREL SAM) test parameters for Yaskawa Solectria Solar: XGI 1500-150/166-UL {600V}.
ParameterMeasured / Listed ValueEngineering Significance
Max Continuous AC Power (Paco) 150,000 W Determines required backfeed OCPD size via 125% continuous rule
Nominal AC Voltage (Vac) 600 V, 3-phase 240V split-phase residential vs. 208V/480V/MV commercial
Max DC Input Voltage (Vdcmax) 1,250 V Hard ceiling for cold-weather PV string Voc under NEC 690.7
MPPT Operating Range 860 V - 1,250 V Optimal DC string Vmp window for full power harvest
Max Input DC Current (Idcmax) 152.321 A Used to verify parallel string combiner limits
CEC Weighted Efficiency 98.48% Calculated AC/DC conversion ratio from CEC test protocol
Inverter Topology Hybrid: No (Grid-Tied PV) CEC Solar Equipment List grid-support certification

What Switchgear Limits Apply to Yaskawa Solectria Solar: XGI 1500-150/166-UL {600V} (600 V, 3-phase)?

NEC 705.12(B)(3)(2) backfeed compliance table for Yaskawa Solectria Solar: XGI 1500-150/166-UL {600V} at 600 V, 3-phase.

Evaluates Yaskawa Solectria Solar: XGI 1500-150/166-UL {600V} (200 A required OCPD at 600 V, 3-phase) across standard distribution busbars.
Switchboard / Interconnect120% Max BackfeedRequired PV OCPDCompliance Verdict
200A Bus / 200A Main (600V) 40 A 200 A Supply-Side Tap (705.11) / Dedicated Switchboard
400A Bus / 400A Main (600V) 80 A 200 A Supply-Side Tap (705.11) / Dedicated Switchboard
600A Bus / 600A Main (600V) 120 A 200 A Supply-Side Tap (705.11) / Dedicated Switchboard
800A Bus / 800A Main (600V) 160 A 200 A Supply-Side Tap (705.11) / Dedicated Switchboard
1,200A Bus / 1,200A Main (600V) 240 A 200 A PASS (120% Commercial Busbar)

Which CEC PV Module Strings Pair With Yaskawa Solectria Solar: XGI 1500-150/166-UL {600V}?

Minimum and maximum series solar module strings fitting Yaskawa Solectria Solar: XGI 1500-150/166-UL {600V} MPPT and 1,250 V limits.

Sampled CEC PV modules aligned within 860.0-1250.0 V MPPT and 1250.0 V max DC at -10 C.
CEC ModuleSTC (W)-10 C VocValid String RangeMax String DC
AXITEC AC-590TGB/144TS 590.0 W 56.24 V 21 to 22 panels 12.98 kW
Aptos Solar Technology LLC DNA-108-MFN10-440W 440.0 W 42.15 V 26 to 29 panels 12.76 kW
Boviet Solar Technology Co Ltd BVM7610M-425-H-HC-BF 425.0 W 44.75 V 25 to 27 panels 11.47 kW
CSI Solar Co Ltd CS6P-200P 200.0 W 40.6 V 30 panels (fixed) 6.0 kW

Which Competing Grid-Support Inverters Compare to Yaskawa Solectria Solar: XGI 1500-150/166-UL {600V}?

Peer 600 V, 3-phase CEC inverters near 150,000 W AC output such as SMA America: SHP 150-US-20 {600V}.

Alternative CEC inverters at comparable AC output power and voltage class.
Alternative InverterAC OutputDeltaVacMax DCCEC Eff
SMA America: SHP 150-US-20 {600V}
SMA America
150,000 W Tie (0 W) 600.0 V 1200.0 V 98.52%
SMA America: SHP 150-US-21 {600V}
SMA America
150,000 W Tie (0 W) 600.0 V 1200.0 V 98.52%
Xiamen Kehua Digital Energy Tech Co Ltd: BCS150K-B-HM-US X2 {600V}
Xiamen Kehua Digital Energy Tech Co Ltd
150,015 W +15 W 600.0 V 1450.0 V 98.35%
SMA America: SHP FLEX-US-21 {600V}
SMA America
150,079 W +79 W 600.0 V 1200.0 V 98.52%
What to Check & Best-Fit Scenarios

What Are the Interconnection Limits and Best-Fit Uses for Yaskawa Solectria Solar: XGI 1500-150/166-UL {600V}?

Check Yaskawa Solectria Solar: XGI 1500-150/166-UL {600V} (150,000 W AC, 200 A OCPD) against your main panel busbar, winter string Voc, and IEEE 1547 outage rules.

  • Anti-islanding shutdown: grid-tied inverters shut off within 2 seconds during blackouts under IEEE 1547 unless paired with a battery microgrid interconnect.
  • Busbar 120% limit: Commercial 600 V, 3-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (600V) or NEC 705.11 supply-side tap.
  • Cold Voc hard ceiling: never allow winter open-circuit PV string voltage to exceed 1,250 V DC on Yaskawa Solectria Solar: XGI 1500-150/166-UL {600V}.

Yaskawa Solectria Solar: XGI 1500-150/166-UL {600V} Panel & Wire Spec

Size 75 C copper conductors at 3/0 AWG Cu on a 200 A OCPD breaker (144.3 A continuous).

Alternative Inverter Comparison

Compare efficiency (98.48%) and MPPT window (860-1,250 V) directly against SMA America: SHP 150-US-20 {600V} (150,000 W).

Which Homeowner Electrical & Solar Questions Come Up Most Often?

Answers for Yaskawa Solectria Solar: XGI 1500-150/166-UL {600V} by Yaskawa Solectria Solar covering breaker sizing, MPPT limits, and 600 V, 3-phase interconnection.

What breaker and wire size does Yaskawa Solectria Solar: XGI 1500-150/166-UL {600V} require?

At 150,000 W continuous AC (600 V, 3-phase), continuous current is 144.3 A; 125% NEC 690.8/705.12 sizing requires a 200 A breaker and 3/0 AWG Cu (75 C) wire.

What commercial switchgear or feeder sizing does Yaskawa Solectria Solar: XGI 1500-150/166-UL {600V} require?

At 150,000 W AC and 600 V, 3-phase, continuous line current is 144.3 A, requiring a 200 A OCPD and 1,200A Bus / 1,200A Main (600V) or NEC 705.11 interconnection.

How does Yaskawa Solectria Solar: XGI 1500-150/166-UL {600V} compare to SMA America: SHP 150-US-20 {600V}?

Yaskawa Solectria Solar: XGI 1500-150/166-UL {600V} delivers 150,000 W AC at 98.48% CEC efficiency with a 1,250 V DC ceiling, while SMA America: SHP 150-US-20 {600V} outputs 150,000 W at 600 V, 3-phase.

Sources

  1. CEC Solar Equipment List — Grid-Support Inverters (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
  2. CEC Solar Equipment List — PV Modules (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
  3. NFPA 70 National Electrical Code (Section Numbers & Standard Engineering Tables Only) — National Fire Protection Association (NFPA), 2020 / 2023 / 2026 Editions (retrieved 2026-11-23)

Which Regional Electrical & Panel Upgrade Metros Compare Closest?

Check Wiring & Solar Numbers Before Getting Quotes

Verify panel capacity for solar, electrical box space, proper wire gauge for EV chargers, and 2026 home solar payback using local utility rates.

Verify State-Licensed Electricians & Safety Recalls

Look up active state electrician licenses (TX, WA, CO, OR, DE), check local power-outage history, and inspect federal product recall notices.