Yaskawa Solectria Solar: PVI-36TL-480-V2 {480V} — CEC Inverter Specifications

Manufacturer: Yaskawa Solectria Solar Registry: CEC Verified Engineering Specification

Yaskawa Solectria Solar: PVI-36TL-480-V2 {480V} outputs 36,000 W AC at 480 V, 3-phase (43.3 A continuous, 60 A OCPD), ranking #500 of 2,343 CEC inverters at 97.62% efficiency with a 400-850 V MPPT window and 850 V DC limit. All figures reconcile directly against federal energy archives, state electrical licensing boards, California Energy Commission datasheets, and National Electrical Code engineering constants.

AC Output (Paco)
36,000 W
AC Voltage
480 V, 3-phase
Min PV Breaker
60 A (6 AWG Cu)
CEC Efficiency
97.62%
Wall-mounted residential hybrid solar inverter and modular battery cabinet piped with galvanized EMT conduit
Wall-mounted residential hybrid solar inverter and modular battery cabinet piped with galvanized EMT conduit

How Does Yaskawa Solectria Solar: PVI-36TL-480-V2 {480V} Compare Against Peer CEC Listings?

How Yaskawa Solectria Solar Yaskawa Solectria Solar: PVI-36TL-480-V2 {480V} compares on 97.62% efficiency, MPPT span, and 120% busbar interconnection.

Yaskawa Solectria Solar certifies Yaskawa Solectria Solar: PVI-36TL-480-V2 {480V} (grid-tied PV inverter, active in CEC directory) at 36,000 W AC (14,000 W below the 50,000 W 480 V median). Its 850 V DC ceiling pairs with an MPPT window of 400-850 V (span 450.0 V). Under NEC 690.8/705.12, 125% sizing demands 6 AWG Cu conductors on a 60 A OCPD.

Where Does Yaskawa Solectria Solar: PVI-36TL-480-V2 {480V} Fall Across Listed CEC Models?

Position of Yaskawa Solectria Solar: PVI-36TL-480-V2 {480V} (36,000 W AC) relative to the 7,680 W CEC median inverter.

AC Power Distribution Across Listed CEC Inverters (up to 25 kW)Shows where Yaskawa Solectria Solar: PVI-36TL-480-V2 {480V} (36,000 W AC) sits across CEC inverters. 190-2258 W AC: 584 entries1902258-4325 W AC: 158 entries4325-6392 W AC: 259 entries6392-8460 W AC: 270 entries63928460-10528 W AC: 258 entries10528-12595 W AC: 116 entries12595-14662 W AC: 17 entries1259514662-16730 W AC: 37 entries16730-18798 W AC: 7 entries18798-20865 W AC: 11 entries1879820865-22932 W AC: 5 entries22932-25000 W AC: 26 entries22932Median 7,680 W ACYaskawa Solectria : 36,000 W

What Dataset Percentiles Define Yaskawa Solectria Solar: PVI-36TL-480-V2 {480V}?

Percentile placement of Yaskawa Solectria Solar: PVI-36TL-480-V2 {480V} across AC power class, conversion efficiency, and backfeed breaker size.

Yaskawa Solectria Solar: PVI-36TL-480-V2 {480V} Technical ThresholdsPercentile comparison for Yaskawa Solectria Solar: PVI-36TL-480-V2 {480V} AC output, weighted CEC efficiency, and OCPD sizing. 0% (Low)50% Median100% (Top)Rated AC Output36,000 WCEC Efficiency97.62%Backfeed Breaker60 A

What Do the Dataset Ranks Show for Yaskawa Solectria Solar: PVI-36TL-480-V2 {480V}?

Primary electrical sizing limits, efficiency ranks, and NEC 705.12 / 690.7 thresholds for Yaskawa Solectria Solar: PVI-36TL-480-V2 {480V}. Published percentiles compare local state, county, metro, and certified equipment metrics against nationwide residential electrical baselines.

Eff #500 / 2,343

97.62% CEC Weighted Efficiency

-0.40 pts vs the 98.02% 480 V median; overall power rank #510 (36,000 W, top 22.2%; higher than 77.8% of peers).

NEC 705.12 Check

60 A Required Backfeed OCPD

125% x 43.3 A = 54.1 A -> 60 A standard OCPD using 6 AWG Cu (75 C).

MPPT Window

400 V - 850 V (Max 850 V DC)

Tracking span of 450.0 V; active in CEC directory (grid-tied PV inverter).

Commercial / 3-Phase Fit

PASS (120% Commercial Busbar)

Evaluated for 480 V, 3-phase switchgear (200A Bus / 200A Main (480V) to 1,200A Bus / 1,200A Main (480V)) under NEC 705.12 / 705.11.

NEC 705.12 Backfeed OCPD & 120% Busbar Formula

I_cont = 36000.0W / 480 V 3-phase -> 43.3 A | Breaker >= 1.25 * 43.3 = 54.1 A -> 60 A

CEC Inverters.csv for Yaskawa Solectria Solar: PVI-36TL-480-V2 {480V}: Paco=36000.0 W, Vac=480 V, Vdcmax=850.0 V, Eff=97.62%.

Result: Min 60 A breaker & 6 AWG Cu (75 C); 1,200A Bus / 1,200A Main (480V): PASS (120% Commercial Busbar).

What Are the Published CEC Specifications for Yaskawa Solectria Solar: PVI-36TL-480-V2 {480V}?

Official California Energy Commission electrical test parameters, AC voltage, and DC limits for Yaskawa Solectria Solar: PVI-36TL-480-V2 {480V}.

Official California Energy Commission (NREL SAM) test parameters for Yaskawa Solectria Solar: PVI-36TL-480-V2 {480V}.
ParameterMeasured / Listed ValueEngineering Significance
Max Continuous AC Power (Paco) 36,000 W Determines required backfeed OCPD size via 125% continuous rule
Nominal AC Voltage (Vac) 480 V, 3-phase 240V split-phase residential vs. 208V/480V/MV commercial
Max DC Input Voltage (Vdcmax) 850 V Hard ceiling for cold-weather PV string Voc under NEC 690.7
MPPT Operating Range 400 V - 850 V Optimal DC string Vmp window for full power harvest
Max Input DC Current (Idcmax) 59.0038 A Used to verify parallel string combiner limits
CEC Weighted Efficiency 97.62% Calculated AC/DC conversion ratio from CEC test protocol
Inverter Topology Hybrid: No (Grid-Tied PV) CEC Solar Equipment List grid-support certification

What Switchgear Limits Apply to Yaskawa Solectria Solar: PVI-36TL-480-V2 {480V} (480 V, 3-phase)?

Check whether Yaskawa Solectria Solar: PVI-36TL-480-V2 {480V} (60 A breaker) fits without main breaker derate or supply-side taps.

Evaluates Yaskawa Solectria Solar: PVI-36TL-480-V2 {480V} (60 A required OCPD at 480 V, 3-phase) across standard distribution busbars.
Switchboard / Interconnect120% Max BackfeedRequired PV OCPDCompliance Verdict
200A Bus / 200A Main (480V) 40 A 60 A Supply-Side Tap (705.11) / Dedicated Switchboard
400A Bus / 400A Main (480V) 80 A 60 A PASS (120% Commercial Busbar)
600A Bus / 600A Main (480V) 120 A 60 A PASS (120% Commercial Busbar)
800A Bus / 800A Main (480V) 160 A 60 A PASS (120% Commercial Busbar)
1,200A Bus / 1,200A Main (480V) 240 A 60 A PASS (120% Commercial Busbar)

Which CEC PV Module Strings Pair With Yaskawa Solectria Solar: PVI-36TL-480-V2 {480V}?

Verified cold-weather (-10 C) series module counts matched to Yaskawa Solectria Solar: PVI-36TL-480-V2 {480V}'s 850 V DC ceiling.

Sampled CEC PV modules aligned within 400.0-850.0 V MPPT and 850.0 V max DC at -10 C.
CEC ModuleSTC (W)-10 C VocValid String RangeMax String DC
AXITEC AC-590TGB/144TS 590.0 W 56.24 V 10 to 15 panels 8.85 kW
Aptos Solar Technology LLC DNA-108-MFN10-440W 440.0 W 42.15 V 12 to 20 panels 8.8 kW
Boviet Solar Technology Co Ltd BVM7610M-425-H-HC-BF 425.0 W 44.75 V 12 to 18 panels 7.65 kW
CSI Solar Co Ltd CS6P-200P 200.0 W 40.6 V 14 to 20 panels 4.0 kW

Which Competing Grid-Support Inverters Compare to Yaskawa Solectria Solar: PVI-36TL-480-V2 {480V}?

Alternative CEC inverters comparable to Yaskawa Solectria Solar: PVI-36TL-480-V2 {480V}, including Canadian Solar Inc: CSI-36KTL-CT {480V} (36,000 W) at 480 V, 3-phase.

Alternative CEC inverters at comparable AC output power and voltage class.
Alternative InverterAC OutputDeltaVacMax DCCEC Eff
Canadian Solar Inc: CSI-36KTL-CT {480V}
Canadian Solar Inc
36,000 W Tie (0 W) 480.0 V 800.0 V 98.09%
Canadian Solar Inc: CSI-36KTL-GS-FL {480V}
Canadian Solar Inc
36,000 W Tie (0 W) 480.0 V 780.0 V 98.05%
Chint Power Systems America: CPS SCA36KTL-DO/US-480 {480V}
Chint Power Systems America
36,000 W Tie (0 W) 480.0 V 850.0 V 97.62%
Chint Power Systems America: CPS SCA36KTL-DO/US {480V}
Chint Power Systems America
36,000 W Tie (0 W) 480.0 V 800.0 V 98.09%
What to Check & Best-Fit Scenarios

What Are the Interconnection Limits and Best-Fit Uses for Yaskawa Solectria Solar: PVI-36TL-480-V2 {480V}?

Check Yaskawa Solectria Solar: PVI-36TL-480-V2 {480V} (36,000 W AC, 60 A OCPD) against your main panel busbar, winter string Voc, and IEEE 1547 outage rules.

  • Anti-islanding shutdown: grid-tied inverters shut off within 2 seconds during blackouts under IEEE 1547 unless paired with a battery microgrid interconnect.
  • Busbar 120% limit: Commercial 480 V, 3-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (480V) or NEC 705.11 supply-side tap.
  • Cold Voc hard ceiling: never allow winter open-circuit PV string voltage to exceed 850 V DC on Yaskawa Solectria Solar: PVI-36TL-480-V2 {480V}.

Yaskawa Solectria Solar: PVI-36TL-480-V2 {480V} Panel & Wire Spec

Size 75 C copper conductors at 6 AWG Cu on a 60 A OCPD breaker (43.3 A continuous).

Alternative Inverter Comparison

Compare efficiency (97.62%) and MPPT window (400-850 V) directly against Canadian Solar Inc: CSI-36KTL-CT {480V} (36,000 W).

Which Homeowner Electrical & Solar Questions Come Up Most Often?

Answers for Yaskawa Solectria Solar: PVI-36TL-480-V2 {480V} by Yaskawa Solectria Solar covering breaker sizing, MPPT limits, and 480 V, 3-phase interconnection.

What breaker and wire size does Yaskawa Solectria Solar: PVI-36TL-480-V2 {480V} require?

At 36,000 W continuous AC (480 V, 3-phase), continuous current is 43.3 A; 125% NEC 690.8/705.12 sizing requires a 60 A breaker and 6 AWG Cu (75 C) wire.

What commercial switchgear or feeder sizing does Yaskawa Solectria Solar: PVI-36TL-480-V2 {480V} require?

At 36,000 W AC and 480 V, 3-phase, continuous line current is 43.3 A, requiring a 60 A OCPD and 1,200A Bus / 1,200A Main (480V) or NEC 705.11 interconnection.

How does Yaskawa Solectria Solar: PVI-36TL-480-V2 {480V} compare to Canadian Solar Inc: CSI-36KTL-CT {480V}?

Yaskawa Solectria Solar: PVI-36TL-480-V2 {480V} delivers 36,000 W AC at 97.62% CEC efficiency with a 850 V DC ceiling, while Canadian Solar Inc: CSI-36KTL-CT {480V} outputs 36,000 W at 480 V, 3-phase.

Sources

  1. CEC Solar Equipment List — Grid-Support Inverters (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
  2. CEC Solar Equipment List — PV Modules (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
  3. NFPA 70 National Electrical Code (Section Numbers & Standard Engineering Tables Only) — National Fire Protection Association (NFPA), 2020 / 2023 / 2026 Editions (retrieved 2026-11-23)

Which Regional Electrical & Panel Upgrade Metros Compare Closest?