Canadian Solar Inc: CSI-36KTL-GS-FL {480V} outputs 36,000 W AC at 480 V, 3-phase (43.3 A continuous, 60 A OCPD), ranking #318 of 2,343 CEC inverters at 98.05% efficiency with a 580-780 V MPPT window and 780 V DC limit. All figures reconcile directly against federal energy archives, state electrical licensing boards, California Energy Commission datasheets, and National Electrical Code engineering constants.
- AC Output (Paco)
- 36,000 W
- AC Voltage
- 480 V, 3-phase
- Min PV Breaker
- 60 A (6 AWG Cu)
- CEC Efficiency
- 98.05%
How Does Canadian Solar Inc: CSI-36KTL-GS-FL {480V} Compare Against Peer CEC Listings?
Breaker sizing (60 A), 6 AWG Cu wire rules, and DC input limits for Canadian Solar Inc: CSI-36KTL-GS-FL {480V}.
Classified as a grid-tied PV inverter (listed since 2019-11-15), Canadian Solar Inc: CSI-36KTL-GS-FL {480V} requires 54.1 A design capacity -> 60 A breaker using 6 AWG Cu copper at 75 C terminals. Weighted efficiency sits at 98.05% (+1.23 pts vs overall CEC median) across 2,343 CEC models, while commercial 480 v, 3-phase switchgear interconnection uses 1,200a bus / 1,200a main (480v) or nec 705.11 supply-side tap.
Where Does Canadian Solar Inc: CSI-36KTL-GS-FL {480V} Fall Across Listed CEC Models?
Output power comparison showing where Canadian Solar Inc: CSI-36KTL-GS-FL {480V} sits among all 2,343 CEC-listed grid-support inverters. Published percentiles compare local state, county, metro, and certified equipment metrics against nationwide residential electrical baselines.
What Dataset Percentiles Define Canadian Solar Inc: CSI-36KTL-GS-FL {480V}?
Relative ranking of Canadian Solar Inc: CSI-36KTL-GS-FL {480V} on continuous AC power, CEC weighted efficiency, and OCPD breaker current.
What Do the Dataset Ranks Show for Canadian Solar Inc: CSI-36KTL-GS-FL {480V}?
Snapshot of Canadian Solar Inc: CSI-36KTL-GS-FL {480V} efficiency rank (#318), OCPD breaker size, MPPT span, and busbar verdict.
98.05% CEC Weighted Efficiency
+0.03 pts vs the 98.02% 480 V median; overall power rank #510 (36,000 W, top 22.2%; higher than 77.8% of peers).
60 A Required Backfeed OCPD
125% x 43.3 A = 54.1 A -> 60 A standard OCPD using 6 AWG Cu (75 C).
580 V - 780 V (Max 780 V DC)
Tracking span of 200.0 V; listed since 2019-11-15 (grid-tied PV inverter).
PASS (120% Commercial Busbar)
Evaluated for 480 V, 3-phase switchgear (200A Bus / 200A Main (480V) to 1,200A Bus / 1,200A Main (480V)) under NEC 705.12 / 705.11.
NEC 705.12 Backfeed OCPD & 120% Busbar Formula
I_cont = 36000.0W / 480 V 3-phase -> 43.3 A | Breaker >= 1.25 * 43.3 = 54.1 A -> 60 A
CEC Inverters.csv for Canadian Solar Inc: CSI-36KTL-GS-FL {480V}: Paco=36000.0 W, Vac=480 V, Vdcmax=780.0 V, Eff=98.05%.
Result: Min 60 A breaker & 6 AWG Cu (75 C); 1,200A Bus / 1,200A Main (480V): PASS (120% Commercial Busbar).
What Are the Published CEC Specifications for Canadian Solar Inc: CSI-36KTL-GS-FL {480V}?
Complete California Energy Commission grid-support inverter ratings and hybrid battery capabilities for Canadian Solar Inc: CSI-36KTL-GS-FL {480V}. Cross-check local Authority Having Jurisdiction amendments and serving utility net-metering terms before finalizing project sizing.
| Parameter | Measured / Listed Value | Engineering Significance |
|---|---|---|
| Max Continuous AC Power (Paco) | 36,000 W | Determines required backfeed OCPD size via 125% continuous rule |
| Nominal AC Voltage (Vac) | 480 V, 3-phase | 240V split-phase residential vs. 208V/480V/MV commercial |
| Max DC Input Voltage (Vdcmax) | 780 V | Hard ceiling for cold-weather PV string Voc under NEC 690.7 |
| MPPT Operating Range | 580 V - 780 V | Optimal DC string Vmp window for full power harvest |
| Max Input DC Current (Idcmax) | 56.4834 A | Used to verify parallel string combiner limits |
| CEC Weighted Efficiency | 98.05% | Calculated AC/DC conversion ratio from CEC test protocol |
| CEC Listing Date & Hybrid | 2019-11-15 / Hybrid: No (Grid-Tied PV) | Utility interconnection approval metadata |
What Switchgear Limits Apply to Canadian Solar Inc: CSI-36KTL-GS-FL {480V} (480 V, 3-phase)?
NEC 705.12(B)(3)(2) backfeed compliance table for Canadian Solar Inc: CSI-36KTL-GS-FL {480V} at 480 V, 3-phase.
| Switchboard / Interconnect | 120% Max Backfeed | Required PV OCPD | Compliance Verdict |
|---|---|---|---|
| 200A Bus / 200A Main (480V) | 40 A | 60 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| 400A Bus / 400A Main (480V) | 80 A | 60 A | PASS (120% Commercial Busbar) |
| 600A Bus / 600A Main (480V) | 120 A | 60 A | PASS (120% Commercial Busbar) |
| 800A Bus / 800A Main (480V) | 160 A | 60 A | PASS (120% Commercial Busbar) |
| 1,200A Bus / 1,200A Main (480V) | 240 A | 60 A | PASS (120% Commercial Busbar) |
Which CEC PV Module Strings Pair With Canadian Solar Inc: CSI-36KTL-GS-FL {480V}?
Minimum and maximum series solar module strings fitting Canadian Solar Inc: CSI-36KTL-GS-FL {480V} MPPT and 780 V limits.
| CEC Module | STC (W) | -10 C Voc | Valid String Range | Max String DC |
|---|---|---|---|---|
| Aptos Solar Technology LLC DNA-108-MFN10-440W | 440.0 W | 42.15 V | 18 panels (fixed) | 7.92 kW |
| Boviet Solar Technology Co Ltd BVM7610M-425-H-HC-BF | 425.0 W | 44.75 V | 17 panels (fixed) | 7.22 kW |
| G-Star Pte Ltd GSN8K66T(H)740WT | 740.0 W | 54.38 V | 14 panels (fixed) | 10.36 kW |
Which Competing Grid-Support Inverters Compare to Canadian Solar Inc: CSI-36KTL-GS-FL {480V}?
Peer 480 V, 3-phase CEC inverters near 36,000 W AC output such as Chint Power Systems America: CPS SCA36KTL-DO/US-480 {480V}.
| Alternative Inverter | AC Output | Delta | Vac | Max DC | CEC Eff |
|---|---|---|---|---|---|
| Chint Power Systems America: CPS SCA36KTL-DO/US-480 {480V} Chint Power Systems America |
36,000 W | Tie (0 W) | 480.0 V | 850.0 V | 97.62% |
| Chint Power Systems America: CPS SCA36KTL-DO/US {480V} Chint Power Systems America |
36,000 W | Tie (0 W) | 480.0 V | 800.0 V | 98.09% |
| CSI Solar Co Ltd: CSI-36KTL-GS-FLB {480V} CSI Solar Co Ltd |
36,000 W | Tie (0 W) | 480.0 V | 780.0 V | 98.11% |
| CSI Solar Co Ltd: CSI-36K-T480GL01-UB {480V} CSI Solar Co Ltd |
35,925 W | -75 W | 480.0 V | 800.0 V | 98.32% |
What Are the Interconnection Limits and Best-Fit Uses for Canadian Solar Inc: CSI-36KTL-GS-FL {480V}?
Check Canadian Solar Inc: CSI-36KTL-GS-FL {480V} (36,000 W AC, 60 A OCPD) against your main panel busbar, winter string Voc, and IEEE 1547 outage rules.
- Anti-islanding shutdown: grid-tied inverters shut off within 2 seconds during blackouts under IEEE 1547 unless paired with a battery microgrid interconnect.
- Busbar 120% limit: Commercial 480 V, 3-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (480V) or NEC 705.11 supply-side tap.
- Cold Voc hard ceiling: never allow winter open-circuit PV string voltage to exceed 780 V DC on Canadian Solar Inc: CSI-36KTL-GS-FL {480V}.
Canadian Solar Inc: CSI-36KTL-GS-FL {480V} Panel & Wire Spec
Size 75 C copper conductors at 6 AWG Cu on a 60 A OCPD breaker (43.3 A continuous).
Alternative Inverter Comparison
Compare efficiency (98.05%) and MPPT window (580-780 V) directly against Chint Power Systems America: CPS SCA36KTL-DO/US-480 {480V} (36,000 W).
Which Homeowner Electrical & Solar Questions Come Up Most Often?
Answers for Canadian Solar Inc: CSI-36KTL-GS-FL {480V} by Canadian Solar Inc covering breaker sizing, MPPT limits, and 480 V, 3-phase interconnection.
What breaker and wire size does Canadian Solar Inc: CSI-36KTL-GS-FL {480V} require?
At 36,000 W continuous AC (480 V, 3-phase), continuous current is 43.3 A; 125% NEC 690.8/705.12 sizing requires a 60 A breaker and 6 AWG Cu (75 C) wire.
What commercial switchgear or feeder sizing does Canadian Solar Inc: CSI-36KTL-GS-FL {480V} require?
At 36,000 W AC and 480 V, 3-phase, continuous line current is 43.3 A, requiring a 60 A OCPD and 1,200A Bus / 1,200A Main (480V) or NEC 705.11 interconnection.
How does Canadian Solar Inc: CSI-36KTL-GS-FL {480V} compare to Chint Power Systems America: CPS SCA36KTL-DO/US-480 {480V}?
Canadian Solar Inc: CSI-36KTL-GS-FL {480V} delivers 36,000 W AC at 98.05% CEC efficiency with a 780 V DC ceiling, while Chint Power Systems America: CPS SCA36KTL-DO/US-480 {480V} outputs 36,000 W at 480 V, 3-phase.
Sources
- CEC Solar Equipment List — Grid-Support Inverters (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
- CEC Solar Equipment List — PV Modules (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
- NFPA 70 National Electrical Code (Section Numbers & Standard Engineering Tables Only) — National Fire Protection Association (NFPA), 2020 / 2023 / 2026 Editions (retrieved 2026-11-23)