Sungrow Power Supply Co Ltd: SC210HX-US {690V} outputs 212,078 W AC at 690 V, 3-phase (177.5 A continuous, 225 A OCPD), ranking #79 of 2,343 CEC inverters at 98.49% efficiency with a 1,000-1,500 V MPPT window and 1,500 V DC limit. All figures reconcile directly against federal energy archives, state electrical licensing boards, California Energy Commission datasheets, and National Electrical Code engineering constants.
- AC Output (Paco)
- 212,078 W
- AC Voltage
- 690 V, 3-phase
- Min PV Breaker
- 225 A (4/0 AWG Cu)
- CEC Efficiency
- 98.49%
How Does Sungrow Power Supply Co Ltd: SC210HX-US {690V} Compare Against Peer CEC Listings?
Breaker sizing (225 A), 4/0 AWG Cu wire rules, and DC input limits for Sungrow Power Supply Co Ltd: SC210HX-US {690V}.
Classified as a grid-tied PV inverter (active in CEC directory), Sungrow Power Supply Co Ltd: SC210HX-US {690V} requires 221.9 A design capacity -> 225 A breaker using 4/0 AWG Cu copper at 75 C terminals. Weighted efficiency sits at 98.49% (+1.67 pts vs overall CEC median) across 2,343 CEC models, while commercial 690 v, 3-phase switchgear interconnection uses 1,200a bus / 1,200a main (690v) or nec 705.11 supply-side tap.
Where Does Sungrow Power Supply Co Ltd: SC210HX-US {690V} Fall Across Listed CEC Models?
Output power comparison showing where Sungrow Power Supply Co Ltd: SC210HX-US {690V} sits among all 2,343 CEC-listed grid-support inverters.
What Dataset Percentiles Define Sungrow Power Supply Co Ltd: SC210HX-US {690V}?
Relative ranking of Sungrow Power Supply Co Ltd: SC210HX-US {690V} on continuous AC power, CEC weighted efficiency, and OCPD breaker current.
What Do the Dataset Ranks Show for Sungrow Power Supply Co Ltd: SC210HX-US {690V}?
Snapshot of Sungrow Power Supply Co Ltd: SC210HX-US {690V} efficiency rank (#79), OCPD breaker size, MPPT span, and busbar verdict.
98.49% CEC Weighted Efficiency
+0.32 pts vs the 98.17% 690 V median; overall power rank #244 (212,078 W, top 10.4%; higher than 89.6% of peers).
225 A Required Backfeed OCPD
125% x 177.5 A = 221.9 A -> 225 A standard OCPD using 4/0 AWG Cu (75 C).
1,000 V - 1,500 V (Max 1,500 V DC)
Tracking span of 500.0 V; active in CEC directory (grid-tied PV inverter).
Supply-Side Tap (705.11) / Dedicated Switchboard
Evaluated for 690 V, 3-phase switchgear (200A Bus / 200A Main (690V) to 1,200A Bus / 1,200A Main (690V)) under NEC 705.12 / 705.11.
NEC 705.12 Backfeed OCPD & 120% Busbar Formula
I_cont = 212078.0W / 690 V 3-phase -> 177.5 A | Breaker >= 1.25 * 177.5 = 221.9 A -> 225 A
CEC Inverters.csv for Sungrow Power Supply Co Ltd: SC210HX-US {690V}: Paco=212078.0 W, Vac=690 V, Vdcmax=1500.0 V, Eff=98.49%.
Result: Min 225 A breaker & 4/0 AWG Cu (75 C); 1,200A Bus / 1,200A Main (690V): PASS (120% Commercial Busbar).
What Are the Published CEC Specifications for Sungrow Power Supply Co Ltd: SC210HX-US {690V}?
Complete California Energy Commission grid-support inverter ratings and hybrid battery capabilities for Sungrow Power Supply Co Ltd: SC210HX-US {690V}.
| Parameter | Measured / Listed Value | Engineering Significance |
|---|---|---|
| Max Continuous AC Power (Paco) | 212,078 W | Determines required backfeed OCPD size via 125% continuous rule |
| Nominal AC Voltage (Vac) | 690 V, 3-phase | 240V split-phase residential vs. 208V/480V/MV commercial |
| Max DC Input Voltage (Vdcmax) | 1,500 V | Hard ceiling for cold-weather PV string Voc under NEC 690.7 |
| MPPT Operating Range | 1,000 V - 1,500 V | Optimal DC string Vmp window for full power harvest |
| Max Input DC Current (Idcmax) | 172.263 A | Used to verify parallel string combiner limits |
| CEC Weighted Efficiency | 98.49% | Calculated AC/DC conversion ratio from CEC test protocol |
| Inverter Topology | Hybrid: No (Grid-Tied PV) | CEC Solar Equipment List grid-support certification |
What Switchgear Limits Apply to Sungrow Power Supply Co Ltd: SC210HX-US {690V} (690 V, 3-phase)?
NEC 705.12(B)(3)(2) backfeed compliance table for Sungrow Power Supply Co Ltd: SC210HX-US {690V} at 690 V, 3-phase.
| Switchboard / Interconnect | 120% Max Backfeed | Required PV OCPD | Compliance Verdict |
|---|---|---|---|
| 200A Bus / 200A Main (690V) | 40 A | 225 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| 400A Bus / 400A Main (690V) | 80 A | 225 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| 600A Bus / 600A Main (690V) | 120 A | 225 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| 800A Bus / 800A Main (690V) | 160 A | 225 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| 1,200A Bus / 1,200A Main (690V) | 240 A | 225 A | PASS (120% Commercial Busbar) |
Which CEC PV Module Strings Pair With Sungrow Power Supply Co Ltd: SC210HX-US {690V}?
Minimum and maximum series solar module strings fitting Sungrow Power Supply Co Ltd: SC210HX-US {690V} MPPT and 1,500 V limits.
| CEC Module | STC (W) | -10 C Voc | Valid String Range | Max String DC |
|---|---|---|---|---|
| AXITEC AC-590TGB/144TS | 590.0 W | 56.24 V | 24 to 26 panels | 15.34 kW |
| Aptos Solar Technology LLC DNA-108-MFN10-440W | 440.0 W | 42.15 V | 30 to 35 panels | 15.4 kW |
| Boviet Solar Technology Co Ltd BVM7610M-425-H-HC-BF | 425.0 W | 44.75 V | 30 to 33 panels | 14.03 kW |
| CSI Solar Co Ltd CS6P-200P | 200.0 W | 40.6 V | 35 to 36 panels | 7.2 kW |
Which Competing Grid-Support Inverters Compare to Sungrow Power Supply Co Ltd: SC210HX-US {690V}?
Peer 690 V, 3-phase CEC inverters near 212,078 W AC output such as CSI Solar Co Ltd: CSEC-215K-T6901A-U {690V}.
| Alternative Inverter | AC Output | Delta | Vac | Max DC | CEC Eff |
|---|---|---|---|---|---|
| CSI Solar Co Ltd: CSEC-215K-T6901A-U {690V} CSI Solar Co Ltd |
215,937 W | +3859 W | 690.0 V | 1500.0 V | 98.38% |
| Shenzhen Cubenergy Co Ltd: EH-0200-HA-M-US {690V} Shenzhen Cubenergy Co Ltd |
220,432 W | +8354 W | 690.0 V | 1346.0 V | 97.54% |
| SINENG ELECTRIC CO LTD: EH-0200-HA-M-US {690V} SINENG ELECTRIC CO LTD |
220,432 W | +8354 W | 690.0 V | 1346.0 V | 97.54% |
| CSI Solar Co Ltd: CSEC-200K-T6901A-U {690V} CSI Solar Co Ltd |
200,706 W | -11372 W | 690.0 V | 1500.0 V | 98.42% |
What Are the Interconnection Limits and Best-Fit Uses for Sungrow Power Supply Co Ltd: SC210HX-US {690V}?
Check Sungrow Power Supply Co Ltd: SC210HX-US {690V} (212,078 W AC, 225 A OCPD) against your main panel busbar, winter string Voc, and IEEE 1547 outage rules.
- Anti-islanding shutdown: grid-tied inverters shut off within 2 seconds during blackouts under IEEE 1547 unless paired with a battery microgrid interconnect.
- Busbar 120% limit: Commercial 690 V, 3-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (690V) or NEC 705.11 supply-side tap.
- Cold Voc hard ceiling: never allow winter open-circuit PV string voltage to exceed 1,500 V DC on Sungrow Power Supply Co Ltd: SC210HX-US {690V}.
Sungrow Power Supply Co Ltd: SC210HX-US {690V} Panel & Wire Spec
Size 75 C copper conductors at 4/0 AWG Cu on a 225 A OCPD breaker (177.5 A continuous).
Alternative Inverter Comparison
Compare efficiency (98.49%) and MPPT window (1,000-1,500 V) directly against CSI Solar Co Ltd: CSEC-215K-T6901A-U {690V} (215,937 W).
Which Homeowner Electrical & Solar Questions Come Up Most Often?
Answers for Sungrow Power Supply Co Ltd: SC210HX-US {690V} by Sungrow Power Supply Co Ltd covering breaker sizing, MPPT limits, and 690 V, 3-phase interconnection.
What breaker and wire size does Sungrow Power Supply Co Ltd: SC210HX-US {690V} require?
At 212,078 W continuous AC (690 V, 3-phase), continuous current is 177.5 A; 125% NEC 690.8/705.12 sizing requires a 225 A breaker and 4/0 AWG Cu (75 C) wire.
What commercial switchgear or feeder sizing does Sungrow Power Supply Co Ltd: SC210HX-US {690V} require?
At 212,078 W AC and 690 V, 3-phase, continuous line current is 177.5 A, requiring a 225 A OCPD and 1,200A Bus / 1,200A Main (690V) or NEC 705.11 interconnection.
How does Sungrow Power Supply Co Ltd: SC210HX-US {690V} compare to CSI Solar Co Ltd: CSEC-215K-T6901A-U {690V}?
Sungrow Power Supply Co Ltd: SC210HX-US {690V} delivers 212,078 W AC at 98.49% CEC efficiency with a 1,500 V DC ceiling, while CSI Solar Co Ltd: CSEC-215K-T6901A-U {690V} outputs 215,937 W at 690 V, 3-phase.
Sources
- CEC Solar Equipment List — Grid-Support Inverters (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
- CEC Solar Equipment List — PV Modules (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
- NFPA 70 National Electrical Code (Section Numbers & Standard Engineering Tables Only) — National Fire Protection Association (NFPA), 2020 / 2023 / 2026 Editions (retrieved 2026-11-23)