Sungrow Power Supply Co Ltd: SC1200UD-US {480V} outputs 1,203,052 W AC at 480 V, 3-phase (1447.1 A continuous, 1,850 A OCPD), ranking #357 of 2,343 CEC inverters at 97.97% efficiency with a 700-1,500 V MPPT window and 1,500 V DC limit. All figures reconcile directly against federal energy archives, state electrical licensing boards, California Energy Commission datasheets, and National Electrical Code engineering constants.
- AC Output (Paco)
- 1,203,052 W
- AC Voltage
- 480 V, 3-phase
- Min PV Breaker
- 1,850 A (parallel Cu feeders)
- CEC Efficiency
- 97.97%
How Does Sungrow Power Supply Co Ltd: SC1200UD-US {480V} Compare Against Peer CEC Listings?
NEC 705.12 breaker requirements, efficiency placement, and 480 V, 3-phase grid-support overview for Sungrow Power Supply Co Ltd: SC1200UD-US {480V}.
Rated at 1,203,052 W AC (1447.1 A continuous), Sungrow Power Supply Co Ltd: SC1200UD-US {480V} ranks #357 of 2,343 CEC units at 97.97% efficiency (-0.05 pts vs the 98.02% 480 V median). Minimum 75 C copper conductor sizing for its 1,850 A circuit is parallel Cu feeders per NEC Table 310.16. Cold-weather string Voc must remain under 1,500 V DC at record local winter lows.
Where Does Sungrow Power Supply Co Ltd: SC1200UD-US {480V} Fall Across Listed CEC Models?
Marks Sungrow Power Supply Co Ltd: SC1200UD-US {480V} (1,203,052 W AC) across the California Energy Commission inverter AC capacity distribution.
What Dataset Percentiles Define Sungrow Power Supply Co Ltd: SC1200UD-US {480V}?
Benchmarks Sungrow Power Supply Co Ltd: SC1200UD-US {480V} continuous AC output, 97.97% CEC weighted efficiency, and 1,850 A OCPD breaker demand.
What Do the Dataset Ranks Show for Sungrow Power Supply Co Ltd: SC1200UD-US {480V}?
Four key NEC 705.12 and California Energy Commission metrics defining Sungrow Power Supply Co Ltd: SC1200UD-US {480V} by Sungrow Power Supply Co Ltd.
97.97% CEC Weighted Efficiency
-0.05 pts vs the 98.02% 480 V median; overall power rank #149 (1,203,052 W, top 6.4%; higher than 93.6% of peers).
1,850 A Required Backfeed OCPD
125% x 1447.1 A = 1808.9 A -> 1,850 A standard OCPD using parallel Cu feeders (75 C).
700 V - 1,500 V (Max 1,500 V DC)
Tracking span of 800.0 V; listed since 2023-02-13 (grid-tied PV inverter).
Supply-Side Tap (705.11) / Dedicated Switchboard
Evaluated for 480 V, 3-phase switchgear (200A Bus / 200A Main (480V) to 1,200A Bus / 1,200A Main (480V)) under NEC 705.12 / 705.11.
NEC 705.12 Backfeed OCPD & 120% Busbar Formula
I_cont = 1203052.0W / 480 V 3-phase -> 1447.1 A | Breaker >= 1.25 * 1447.1 = 1808.9 A -> 1,850 A
CEC Inverters.csv for Sungrow Power Supply Co Ltd: SC1200UD-US {480V}: Paco=1203052.0 W, Vac=480 V, Vdcmax=1500.0 V, Eff=97.97%.
Result: Min 1,850 A breaker & parallel Cu feeders (75 C); 1,200A Bus / 1,200A Main (480V): Supply-Side Tap (705.11) / Dedicated Switchboard.
What Are the Published CEC Specifications for Sungrow Power Supply Co Ltd: SC1200UD-US {480V}?
Official laboratory CEC ratings, MPPT operating window, and DC voltage bounds recorded for Sungrow Power Supply Co Ltd: SC1200UD-US {480V}.
| Parameter | Measured / Listed Value | Engineering Significance |
|---|---|---|
| Max Continuous AC Power (Paco) | 1,203,052 W | Determines required backfeed OCPD size via 125% continuous rule |
| Nominal AC Voltage (Vac) | 480 V, 3-phase | 240V split-phase residential vs. 208V/480V/MV commercial |
| Max DC Input Voltage (Vdcmax) | 1,500 V | Hard ceiling for cold-weather PV string Voc under NEC 690.7 |
| MPPT Operating Range | 700 V - 1,500 V | Optimal DC string Vmp window for full power harvest |
| Max Input DC Current (Idcmax) | 1364.48 A | Used to verify parallel string combiner limits |
| CEC Weighted Efficiency | 97.97% | Calculated AC/DC conversion ratio from CEC test protocol |
| CEC Listing Date & Hybrid | 2023-02-13 / Hybrid: No (Grid-Tied PV) | Utility interconnection approval metadata |
What Switchgear Limits Apply to Sungrow Power Supply Co Ltd: SC1200UD-US {480V} (480 V, 3-phase)?
Evaluates Sungrow Power Supply Co Ltd: SC1200UD-US {480V} (1,850 A OCPD) across standard 100 A to 225 A busbars or commercial switchboards.
| Switchboard / Interconnect | 120% Max Backfeed | Required PV OCPD | Compliance Verdict |
|---|---|---|---|
| 200A Bus / 200A Main (480V) | 40 A | 1,850 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| 400A Bus / 400A Main (480V) | 80 A | 1,850 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| 600A Bus / 600A Main (480V) | 120 A | 1,850 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| 800A Bus / 800A Main (480V) | 160 A | 1,850 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| 1,200A Bus / 1,200A Main (480V) | 240 A | 1,850 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
Which CEC PV Module Strings Pair With Sungrow Power Supply Co Ltd: SC1200UD-US {480V}?
Sample PV string lengths aligned within 700-1,500 V MPPT and 1,500 V DC max at -10 C. Cross-check local Authority Having Jurisdiction amendments and serving utility net-metering terms before finalizing project sizing.
| CEC Module | STC (W) | -10 C Voc | Valid String Range | Max String DC |
|---|---|---|---|---|
| AXITEC AC-590TGB/144TS | 590.0 W | 56.24 V | 17 to 26 panels | 15.34 kW |
| Aptos Solar Technology LLC DNA-108-MFN10-440W | 440.0 W | 42.15 V | 21 to 35 panels | 15.4 kW |
| Boviet Solar Technology Co Ltd BVM7610M-425-H-HC-BF | 425.0 W | 44.75 V | 21 to 33 panels | 14.03 kW |
| CSI Solar Co Ltd CS6P-200P | 200.0 W | 40.6 V | 25 to 36 panels | 7.2 kW |
Which Competing Grid-Support Inverters Compare to Sungrow Power Supply Co Ltd: SC1200UD-US {480V}?
Competing CEC grid-support inverters near 1,203,052 W AC and 480 V, 3-phase, led by DYNAPOWER COMPANY LLC: CPS-1500 Gen4 {480V}.
| Alternative Inverter | AC Output | Delta | Vac | Max DC | CEC Eff |
|---|---|---|---|---|---|
| DYNAPOWER COMPANY LLC: CPS-1500 Gen4 {480V} DYNAPOWER COMPANY LLC |
1,199,640 W | -3412 W | 480.0 V | 1500.0 V | 96.13% |
| Delta Electronics: EPCS-1200US {480V} Delta Electronics |
1,216,710 W | +13658 W | 480.0 V | 1500.0 V | 97.82% |
| EPC Power Corp: 50-100181 {480V} EPC Power Corp |
1,044,200 W | -158852 W | 480.0 V | 1500.0 V | 97.49% |
| EPC Power Corp: 50-100100 {480V} EPC Power Corp |
1,036,840 W | -166212 W | 480.0 V | 1250.0 V | 95.42% |
What Are the Interconnection Limits and Best-Fit Uses for Sungrow Power Supply Co Ltd: SC1200UD-US {480V}?
Check Sungrow Power Supply Co Ltd: SC1200UD-US {480V} (1,203,052 W AC, 1,850 A OCPD) against your main panel busbar, winter string Voc, and IEEE 1547 outage rules.
- Anti-islanding shutdown: grid-tied inverters shut off within 2 seconds during blackouts under IEEE 1547 unless paired with a battery microgrid interconnect.
- Busbar 120% limit: Commercial 480 V, 3-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (480V) or NEC 705.11 supply-side tap.
- Cold Voc hard ceiling: never allow winter open-circuit PV string voltage to exceed 1,500 V DC on Sungrow Power Supply Co Ltd: SC1200UD-US {480V}.
Sungrow Power Supply Co Ltd: SC1200UD-US {480V} Panel & Wire Spec
Size 75 C copper conductors at parallel Cu feeders on a 1,850 A OCPD breaker (1447.1 A continuous).
Alternative Inverter Comparison
Compare efficiency (97.97%) and MPPT window (700-1,500 V) directly against DYNAPOWER COMPANY LLC: CPS-1500 Gen4 {480V} (1,199,640 W).
Which Homeowner Electrical & Solar Questions Come Up Most Often?
Answers for Sungrow Power Supply Co Ltd: SC1200UD-US {480V} by Sungrow Power Supply Co Ltd covering breaker sizing, MPPT limits, and 480 V, 3-phase interconnection.
What breaker and wire size does Sungrow Power Supply Co Ltd: SC1200UD-US {480V} require?
At 1,203,052 W continuous AC (480 V, 3-phase), continuous current is 1447.1 A; 125% NEC 690.8/705.12 sizing requires a 1,850 A breaker and parallel Cu feeders (75 C) wire.
What commercial switchgear or feeder sizing does Sungrow Power Supply Co Ltd: SC1200UD-US {480V} require?
At 1,203,052 W AC and 480 V, 3-phase, continuous line current is 1447.1 A, requiring a 1,850 A OCPD and 1,200A Bus / 1,200A Main (480V) or NEC 705.11 interconnection.
How does Sungrow Power Supply Co Ltd: SC1200UD-US {480V} compare to DYNAPOWER COMPANY LLC: CPS-1500 Gen4 {480V}?
Sungrow Power Supply Co Ltd: SC1200UD-US {480V} delivers 1,203,052 W AC at 97.97% CEC efficiency with a 1,500 V DC ceiling, while DYNAPOWER COMPANY LLC: CPS-1500 Gen4 {480V} outputs 1,199,640 W at 480 V, 3-phase.
Sources
- CEC Solar Equipment List — Grid-Support Inverters (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
- CEC Solar Equipment List — PV Modules (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
- NFPA 70 National Electrical Code (Section Numbers & Standard Engineering Tables Only) — National Fire Protection Association (NFPA), 2020 / 2023 / 2026 Editions (retrieved 2026-11-23)