Star Charge Americas Corp: SI135TULT10 {480V} outputs 134,288 W AC at 480 V, 3-phase (161.5 A continuous, 225 A OCPD), ranking #155 of 2,343 CEC inverters at 98.34% efficiency with a 810-1,050 V MPPT window and 1,050 V DC limit. All figures reconcile directly against federal energy archives, state electrical licensing boards, California Energy Commission datasheets, and National Electrical Code engineering constants.
- AC Output (Paco)
- 134,288 W
- AC Voltage
- 480 V, 3-phase
- Min PV Breaker
- 225 A (4/0 AWG Cu)
- CEC Efficiency
- 98.34%
How Does Star Charge Americas Corp: SI135TULT10 {480V} Compare Against Peer CEC Listings?
CEC efficiency rank (#155), 810-1,050 V MPPT tracking, and panel fit for Star Charge Americas Corp: SI135TULT10 {480V}.
Star Charge Americas Corp: SI135TULT10 {480V} from Star Charge Americas Corp outputs 161.5 A continuous AC at 480 V, 3-phase (134,288 W AC, rank #289). Paired with 4/0 AWG Cu conductors and a 225 A OCPD, its 98.34% CEC efficiency compares closely with Chint Power Systems America: CPS ECB125KTL-M/US-480 {480V} (125,000 W). Keep NEC 690.7 winter string Voc below 1,050 V DC.
Where Does Star Charge Americas Corp: SI135TULT10 {480V} Fall Across Listed CEC Models?
CEC inverter wattage histogram highlighting Star Charge Americas Corp: SI135TULT10 {480V} at 134,288 W continuous AC output. Review related calculators, peer benchmarks, and source citations below to validate design assumptions for your electrical service.
What Dataset Percentiles Define Star Charge Americas Corp: SI135TULT10 {480V}?
Dataset percentiles comparing Star Charge Americas Corp: SI135TULT10 {480V} against 2,343 certified grid-support inverters nationwide. All figures trace directly to published federal energy filings, state electrical boards, CEC datasheets, and NFPA 70 NEC tables.
What Do the Dataset Ranks Show for Star Charge Americas Corp: SI135TULT10 {480V}?
Engineering highlights for Star Charge Americas Corp: SI135TULT10 {480V} covering efficiency, 4/0 AWG Cu feeder, and panel compatibility.
98.34% CEC Weighted Efficiency
+0.32 pts vs the 98.02% 480 V median; overall power rank #289 (134,288 W, top 12.3%; higher than 87.7% of peers).
225 A Required Backfeed OCPD
125% x 161.5 A = 201.9 A -> 225 A standard OCPD using 4/0 AWG Cu (75 C).
810 V - 1,050 V (Max 1,050 V DC)
Tracking span of 240.0 V; active in CEC directory (grid-tied PV inverter).
Supply-Side Tap (705.11) / Dedicated Switchboard
Evaluated for 480 V, 3-phase switchgear (200A Bus / 200A Main (480V) to 1,200A Bus / 1,200A Main (480V)) under NEC 705.12 / 705.11.
NEC 705.12 Backfeed OCPD & 120% Busbar Formula
I_cont = 134288.0W / 480 V 3-phase -> 161.5 A | Breaker >= 1.25 * 161.5 = 201.9 A -> 225 A
CEC Inverters.csv for Star Charge Americas Corp: SI135TULT10 {480V}: Paco=134288.0 W, Vac=480 V, Vdcmax=1050.0 V, Eff=98.34%.
Result: Min 225 A breaker & 4/0 AWG Cu (75 C); 1,200A Bus / 1,200A Main (480V): PASS (120% Commercial Busbar).
What Are the Published CEC Specifications for Star Charge Americas Corp: SI135TULT10 {480V}?
California Energy Commission Solar Equipment List parameters for Star Charge Americas Corp: SI135TULT10 {480V} (grid-tied PV inverter) interconnection.
| Parameter | Measured / Listed Value | Engineering Significance |
|---|---|---|
| Max Continuous AC Power (Paco) | 134,288 W | Determines required backfeed OCPD size via 125% continuous rule |
| Nominal AC Voltage (Vac) | 480 V, 3-phase | 240V split-phase residential vs. 208V/480V/MV commercial |
| Max DC Input Voltage (Vdcmax) | 1,050 V | Hard ceiling for cold-weather PV string Voc under NEC 690.7 |
| MPPT Operating Range | 810 V - 1,050 V | Optimal DC string Vmp window for full power harvest |
| Max Input DC Current (Idcmax) | 155.183 A | Used to verify parallel string combiner limits |
| CEC Weighted Efficiency | 98.34% | Calculated AC/DC conversion ratio from CEC test protocol |
| Inverter Topology | Hybrid: No (Grid-Tied PV) | CEC Solar Equipment List grid-support certification |
What Switchgear Limits Apply to Star Charge Americas Corp: SI135TULT10 {480V} (480 V, 3-phase)?
Panelboard and switchgear backfeed allowances for Star Charge Americas Corp: SI135TULT10 {480V} (225 A OCPD). Compare thermal ratings, overcurrent protection caps, and continuous load headroom carefully before expanding an existing home service panel.
| Switchboard / Interconnect | 120% Max Backfeed | Required PV OCPD | Compliance Verdict |
|---|---|---|---|
| 200A Bus / 200A Main (480V) | 40 A | 225 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| 400A Bus / 400A Main (480V) | 80 A | 225 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| 600A Bus / 600A Main (480V) | 120 A | 225 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| 800A Bus / 800A Main (480V) | 160 A | 225 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| 1,200A Bus / 1,200A Main (480V) | 240 A | 225 A | PASS (120% Commercial Busbar) |
Which Competing Grid-Support Inverters Compare to Star Charge Americas Corp: SI135TULT10 {480V}?
Four alternative CEC inverters matched to Star Charge Americas Corp: SI135TULT10 {480V} (134,288 W AC), led by Chint Power Systems America: CPS ECB125KTL-M/US-480 {480V}.
| Alternative Inverter | AC Output | Delta | Vac | Max DC | CEC Eff |
|---|---|---|---|---|---|
| Chint Power Systems America: CPS ECB125KTL-M/US-480 {480V} Chint Power Systems America |
125,000 W | -9288 W | 480.0 V | 1100.0 V | 97.2% |
| Delta Electronics: DES10JB125K01 {480V} Delta Electronics |
125,000 W | -9288 W | 480.0 V | 1000.0 V | 97.01% |
| Delta Electronics: PCS125 {480V} Delta Electronics |
125,000 W | -9288 W | 480.0 V | 1000.0 V | 97.01% |
| Ginlong Technologies Co Ltd: S5-GC125K-US {480V} Ginlong Technologies Co Ltd |
124,991 W | -9297 W | 480.0 V | 850.0 V | 97.88% |
What Are the Interconnection Limits and Best-Fit Uses for Star Charge Americas Corp: SI135TULT10 {480V}?
Check Star Charge Americas Corp: SI135TULT10 {480V} (134,288 W AC, 225 A OCPD) against your main panel busbar, winter string Voc, and IEEE 1547 outage rules.
- Anti-islanding shutdown: grid-tied inverters shut off within 2 seconds during blackouts under IEEE 1547 unless paired with a battery microgrid interconnect.
- Busbar 120% limit: Commercial 480 V, 3-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (480V) or NEC 705.11 supply-side tap.
- Cold Voc hard ceiling: never allow winter open-circuit PV string voltage to exceed 1,050 V DC on Star Charge Americas Corp: SI135TULT10 {480V}.
Star Charge Americas Corp: SI135TULT10 {480V} Panel & Wire Spec
Size 75 C copper conductors at 4/0 AWG Cu on a 225 A OCPD breaker (161.5 A continuous).
Alternative Inverter Comparison
Compare efficiency (98.34%) and MPPT window (810-1,050 V) directly against Chint Power Systems America: CPS ECB125KTL-M/US-480 {480V} (125,000 W).
Which Homeowner Electrical & Solar Questions Come Up Most Often?
Answers for Star Charge Americas Corp: SI135TULT10 {480V} by Star Charge Americas Corp covering breaker sizing, MPPT limits, and 480 V, 3-phase interconnection.
What breaker and wire size does Star Charge Americas Corp: SI135TULT10 {480V} require?
At 134,288 W continuous AC (480 V, 3-phase), continuous current is 161.5 A; 125% NEC 690.8/705.12 sizing requires a 225 A breaker and 4/0 AWG Cu (75 C) wire.
What commercial switchgear or feeder sizing does Star Charge Americas Corp: SI135TULT10 {480V} require?
At 134,288 W AC and 480 V, 3-phase, continuous line current is 161.5 A, requiring a 225 A OCPD and 1,200A Bus / 1,200A Main (480V) or NEC 705.11 interconnection.
How does Star Charge Americas Corp: SI135TULT10 {480V} compare to Chint Power Systems America: CPS ECB125KTL-M/US-480 {480V}?
Star Charge Americas Corp: SI135TULT10 {480V} delivers 134,288 W AC at 98.34% CEC efficiency with a 1,050 V DC ceiling, while Chint Power Systems America: CPS ECB125KTL-M/US-480 {480V} outputs 125,000 W at 480 V, 3-phase.
Sources
- CEC Solar Equipment List — Grid-Support Inverters (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
- CEC Solar Equipment List — PV Modules (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
- NFPA 70 National Electrical Code (Section Numbers & Standard Engineering Tables Only) — National Fire Protection Association (NFPA), 2020 / 2023 / 2026 Editions (retrieved 2026-11-23)