Star Charge Americas Corp: SI125TULT10 {480V} outputs 124,346 W AC at 480 V, 3-phase (149.6 A continuous, 200 A OCPD), ranking #72 of 2,343 CEC inverters at 98.51% efficiency with a 750-1,050 V MPPT window and 1,050 V DC limit. All figures reconcile directly against federal energy archives, state electrical licensing boards, California Energy Commission datasheets, and National Electrical Code engineering constants.
- AC Output (Paco)
- 124,346 W
- AC Voltage
- 480 V, 3-phase
- Min PV Breaker
- 200 A (3/0 AWG Cu)
- CEC Efficiency
- 98.51%
How Does Star Charge Americas Corp: SI125TULT10 {480V} Compare Against Peer CEC Listings?
Breaker sizing (200 A), 3/0 AWG Cu wire rules, and DC input limits for Star Charge Americas Corp: SI125TULT10 {480V}.
Classified as a grid-tied PV inverter (active in CEC directory), Star Charge Americas Corp: SI125TULT10 {480V} requires 187.0 A design capacity -> 200 A breaker using 3/0 AWG Cu copper at 75 C terminals. Weighted efficiency sits at 98.51% (+1.69 pts vs overall CEC median) across 2,343 CEC models, while commercial 480 v, 3-phase switchgear interconnection uses 1,200a bus / 1,200a main (480v) or nec 705.11 supply-side tap.
Where Does Star Charge Americas Corp: SI125TULT10 {480V} Fall Across Listed CEC Models?
Output power comparison showing where Star Charge Americas Corp: SI125TULT10 {480V} sits among all 2,343 CEC-listed grid-support inverters.
What Dataset Percentiles Define Star Charge Americas Corp: SI125TULT10 {480V}?
Relative ranking of Star Charge Americas Corp: SI125TULT10 {480V} on continuous AC power, CEC weighted efficiency, and OCPD breaker current.
What Do the Dataset Ranks Show for Star Charge Americas Corp: SI125TULT10 {480V}?
Snapshot of Star Charge Americas Corp: SI125TULT10 {480V} efficiency rank (#72), OCPD breaker size, MPPT span, and busbar verdict.
98.51% CEC Weighted Efficiency
+0.49 pts vs the 98.02% 480 V median; overall power rank #321 (124,346 W, top 13.7%; higher than 86.3% of peers).
200 A Required Backfeed OCPD
125% x 149.6 A = 187.0 A -> 200 A standard OCPD using 3/0 AWG Cu (75 C).
750 V - 1,050 V (Max 1,050 V DC)
Tracking span of 300.0 V; active in CEC directory (grid-tied PV inverter).
Supply-Side Tap (705.11) / Dedicated Switchboard
Evaluated for 480 V, 3-phase switchgear (200A Bus / 200A Main (480V) to 1,200A Bus / 1,200A Main (480V)) under NEC 705.12 / 705.11.
NEC 705.12 Backfeed OCPD & 120% Busbar Formula
I_cont = 124346.0W / 480 V 3-phase -> 149.6 A | Breaker >= 1.25 * 149.6 = 187.0 A -> 200 A
CEC Inverters.csv for Star Charge Americas Corp: SI125TULT10 {480V}: Paco=124346.0 W, Vac=480 V, Vdcmax=1050.0 V, Eff=98.51%.
Result: Min 200 A breaker & 3/0 AWG Cu (75 C); 1,200A Bus / 1,200A Main (480V): PASS (120% Commercial Busbar).
What Are the Published CEC Specifications for Star Charge Americas Corp: SI125TULT10 {480V}?
Complete California Energy Commission grid-support inverter ratings and hybrid battery capabilities for Star Charge Americas Corp: SI125TULT10 {480V}.
| Parameter | Measured / Listed Value | Engineering Significance |
|---|---|---|
| Max Continuous AC Power (Paco) | 124,346 W | Determines required backfeed OCPD size via 125% continuous rule |
| Nominal AC Voltage (Vac) | 480 V, 3-phase | 240V split-phase residential vs. 208V/480V/MV commercial |
| Max DC Input Voltage (Vdcmax) | 1,050 V | Hard ceiling for cold-weather PV string Voc under NEC 690.7 |
| MPPT Operating Range | 750 V - 1,050 V | Optimal DC string Vmp window for full power harvest |
| Max Input DC Current (Idcmax) | 150.275 A | Used to verify parallel string combiner limits |
| CEC Weighted Efficiency | 98.51% | Calculated AC/DC conversion ratio from CEC test protocol |
| Inverter Topology | Hybrid: No (Grid-Tied PV) | CEC Solar Equipment List grid-support certification |
What Switchgear Limits Apply to Star Charge Americas Corp: SI125TULT10 {480V} (480 V, 3-phase)?
NEC 705.12(B)(3)(2) backfeed compliance table for Star Charge Americas Corp: SI125TULT10 {480V} at 480 V, 3-phase.
| Switchboard / Interconnect | 120% Max Backfeed | Required PV OCPD | Compliance Verdict |
|---|---|---|---|
| 200A Bus / 200A Main (480V) | 40 A | 200 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| 400A Bus / 400A Main (480V) | 80 A | 200 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| 600A Bus / 600A Main (480V) | 120 A | 200 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| 800A Bus / 800A Main (480V) | 160 A | 200 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| 1,200A Bus / 1,200A Main (480V) | 240 A | 200 A | PASS (120% Commercial Busbar) |
Which CEC PV Module Strings Pair With Star Charge Americas Corp: SI125TULT10 {480V}?
Minimum and maximum series solar module strings fitting Star Charge Americas Corp: SI125TULT10 {480V} MPPT and 1,050 V limits.
| CEC Module | STC (W) | -10 C Voc | Valid String Range | Max String DC |
|---|---|---|---|---|
| AXITEC AC-590TGB/144TS | 590.0 W | 56.24 V | 18 panels (fixed) | 10.62 kW |
| Aptos Solar Technology LLC DNA-108-MFN10-440W | 440.0 W | 42.15 V | 23 to 24 panels | 10.56 kW |
| Boviet Solar Technology Co Ltd BVM7610M-425-H-HC-BF | 425.0 W | 44.75 V | 22 to 23 panels | 9.78 kW |
| Chint New Energy Technology Co Ltd CHSM72M(DG)/F-BH-515 | 515.0 W | 53.76 V | 19 panels (fixed) | 9.79 kW |
Which Competing Grid-Support Inverters Compare to Star Charge Americas Corp: SI125TULT10 {480V}?
Peer 480 V, 3-phase CEC inverters near 124,346 W AC output such as Delta Electronics: PCS125HV {480V}. Use these verified dataset benchmarks alongside a licensed electrician load calculation to compare residential upgrade bids with confidence.
| Alternative Inverter | AC Output | Delta | Vac | Max DC | CEC Eff |
|---|---|---|---|---|---|
| Delta Electronics: PCS125HV {480V} Delta Electronics |
124,312 W | -34 W | 480.0 V | 1250.0 V | 97.65% |
| Ginlong Technologies Co Ltd: S5-GC125K-US {480V} Ginlong Technologies Co Ltd |
124,991 W | +645 W | 480.0 V | 850.0 V | 97.88% |
| Chint Power Systems America: CPS ECB125KTL-M/US-480 {480V} Chint Power Systems America |
125,000 W | +654 W | 480.0 V | 1100.0 V | 97.2% |
| Delta Electronics: DES10JB125K01 {480V} Delta Electronics |
125,000 W | +654 W | 480.0 V | 1000.0 V | 97.01% |
What Are the Interconnection Limits and Best-Fit Uses for Star Charge Americas Corp: SI125TULT10 {480V}?
Check Star Charge Americas Corp: SI125TULT10 {480V} (124,346 W AC, 200 A OCPD) against your main panel busbar, winter string Voc, and IEEE 1547 outage rules.
- Anti-islanding shutdown: grid-tied inverters shut off within 2 seconds during blackouts under IEEE 1547 unless paired with a battery microgrid interconnect.
- Busbar 120% limit: Commercial 480 V, 3-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (480V) or NEC 705.11 supply-side tap.
- Cold Voc hard ceiling: never allow winter open-circuit PV string voltage to exceed 1,050 V DC on Star Charge Americas Corp: SI125TULT10 {480V}.
Star Charge Americas Corp: SI125TULT10 {480V} Panel & Wire Spec
Size 75 C copper conductors at 3/0 AWG Cu on a 200 A OCPD breaker (149.6 A continuous).
Alternative Inverter Comparison
Compare efficiency (98.51%) and MPPT window (750-1,050 V) directly against Delta Electronics: PCS125HV {480V} (124,312 W).
Which Homeowner Electrical & Solar Questions Come Up Most Often?
Answers for Star Charge Americas Corp: SI125TULT10 {480V} by Star Charge Americas Corp covering breaker sizing, MPPT limits, and 480 V, 3-phase interconnection.
What breaker and wire size does Star Charge Americas Corp: SI125TULT10 {480V} require?
At 124,346 W continuous AC (480 V, 3-phase), continuous current is 149.6 A; 125% NEC 690.8/705.12 sizing requires a 200 A breaker and 3/0 AWG Cu (75 C) wire.
What commercial switchgear or feeder sizing does Star Charge Americas Corp: SI125TULT10 {480V} require?
At 124,346 W AC and 480 V, 3-phase, continuous line current is 149.6 A, requiring a 200 A OCPD and 1,200A Bus / 1,200A Main (480V) or NEC 705.11 interconnection.
How does Star Charge Americas Corp: SI125TULT10 {480V} compare to Delta Electronics: PCS125HV {480V}?
Star Charge Americas Corp: SI125TULT10 {480V} delivers 124,346 W AC at 98.51% CEC efficiency with a 1,050 V DC ceiling, while Delta Electronics: PCS125HV {480V} outputs 124,312 W at 480 V, 3-phase.
Sources
- CEC Solar Equipment List — Grid-Support Inverters (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
- CEC Solar Equipment List — PV Modules (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
- NFPA 70 National Electrical Code (Section Numbers & Standard Engineering Tables Only) — National Fire Protection Association (NFPA), 2020 / 2023 / 2026 Editions (retrieved 2026-11-23)