Star Charge Americas Corp: SI135TULT00 {480V} outputs 133,148 W AC at 480 V, 3-phase (160.2 A continuous, 225 A OCPD), ranking #311 of 2,343 CEC inverters at 98.07% efficiency with a 810-1,050 V MPPT window and 1,050 V DC limit. All figures reconcile directly against federal energy archives, state electrical licensing boards, California Energy Commission datasheets, and National Electrical Code engineering constants.
- AC Output (Paco)
- 133,148 W
- AC Voltage
- 480 V, 3-phase
- Min PV Breaker
- 225 A (4/0 AWG Cu)
- CEC Efficiency
- 98.07%
How Does Star Charge Americas Corp: SI135TULT00 {480V} Compare Against Peer CEC Listings?
Breaker sizing (225 A), 4/0 AWG Cu wire rules, and DC input limits for Star Charge Americas Corp: SI135TULT00 {480V}.
Classified as a grid-tied PV inverter (active in CEC directory), Star Charge Americas Corp: SI135TULT00 {480V} requires 200.2 A design capacity -> 225 A breaker using 4/0 AWG Cu copper at 75 C terminals. Weighted efficiency sits at 98.07% (+1.25 pts vs overall CEC median) across 2,343 CEC models, while commercial 480 v, 3-phase switchgear interconnection uses 1,200a bus / 1,200a main (480v) or nec 705.11 supply-side tap.
Where Does Star Charge Americas Corp: SI135TULT00 {480V} Fall Across Listed CEC Models?
Output power comparison showing where Star Charge Americas Corp: SI135TULT00 {480V} sits among all 2,343 CEC-listed grid-support inverters.
What Dataset Percentiles Define Star Charge Americas Corp: SI135TULT00 {480V}?
Relative ranking of Star Charge Americas Corp: SI135TULT00 {480V} on continuous AC power, CEC weighted efficiency, and OCPD breaker current.
What Do the Dataset Ranks Show for Star Charge Americas Corp: SI135TULT00 {480V}?
Snapshot of Star Charge Americas Corp: SI135TULT00 {480V} efficiency rank (#311), OCPD breaker size, MPPT span, and busbar verdict.
98.07% CEC Weighted Efficiency
+0.05 pts vs the 98.02% 480 V median; overall power rank #290 (133,148 W, top 12.4%; higher than 87.6% of peers).
225 A Required Backfeed OCPD
125% x 160.2 A = 200.2 A -> 225 A standard OCPD using 4/0 AWG Cu (75 C).
810 V - 1,050 V (Max 1,050 V DC)
Tracking span of 240.0 V; active in CEC directory (grid-tied PV inverter).
Supply-Side Tap (705.11) / Dedicated Switchboard
Evaluated for 480 V, 3-phase switchgear (200A Bus / 200A Main (480V) to 1,200A Bus / 1,200A Main (480V)) under NEC 705.12 / 705.11.
NEC 705.12 Backfeed OCPD & 120% Busbar Formula
I_cont = 133148.0W / 480 V 3-phase -> 160.2 A | Breaker >= 1.25 * 160.2 = 200.2 A -> 225 A
CEC Inverters.csv for Star Charge Americas Corp: SI135TULT00 {480V}: Paco=133148.0 W, Vac=480 V, Vdcmax=1050.0 V, Eff=98.07%.
Result: Min 225 A breaker & 4/0 AWG Cu (75 C); 1,200A Bus / 1,200A Main (480V): PASS (120% Commercial Busbar).
What Are the Published CEC Specifications for Star Charge Americas Corp: SI135TULT00 {480V}?
Complete California Energy Commission grid-support inverter ratings and hybrid battery capabilities for Star Charge Americas Corp: SI135TULT00 {480V}.
| Parameter | Measured / Listed Value | Engineering Significance |
|---|---|---|
| Max Continuous AC Power (Paco) | 133,148 W | Determines required backfeed OCPD size via 125% continuous rule |
| Nominal AC Voltage (Vac) | 480 V, 3-phase | 240V split-phase residential vs. 208V/480V/MV commercial |
| Max DC Input Voltage (Vdcmax) | 1,050 V | Hard ceiling for cold-weather PV string Voc under NEC 690.7 |
| MPPT Operating Range | 810 V - 1,050 V | Optimal DC string Vmp window for full power harvest |
| Max Input DC Current (Idcmax) | 154.289 A | Used to verify parallel string combiner limits |
| CEC Weighted Efficiency | 98.07% | Calculated AC/DC conversion ratio from CEC test protocol |
| Inverter Topology | Hybrid: No (Grid-Tied PV) | CEC Solar Equipment List grid-support certification |
What Switchgear Limits Apply to Star Charge Americas Corp: SI135TULT00 {480V} (480 V, 3-phase)?
NEC 705.12(B)(3)(2) backfeed compliance table for Star Charge Americas Corp: SI135TULT00 {480V} at 480 V, 3-phase.
| Switchboard / Interconnect | 120% Max Backfeed | Required PV OCPD | Compliance Verdict |
|---|---|---|---|
| 200A Bus / 200A Main (480V) | 40 A | 225 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| 400A Bus / 400A Main (480V) | 80 A | 225 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| 600A Bus / 600A Main (480V) | 120 A | 225 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| 800A Bus / 800A Main (480V) | 160 A | 225 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| 1,200A Bus / 1,200A Main (480V) | 240 A | 225 A | PASS (120% Commercial Busbar) |
Which Competing Grid-Support Inverters Compare to Star Charge Americas Corp: SI135TULT00 {480V}?
Peer 480 V, 3-phase CEC inverters near 133,148 W AC output such as Chint Power Systems America: CPS ECB125KTL-M/US-480 {480V}.
| Alternative Inverter | AC Output | Delta | Vac | Max DC | CEC Eff |
|---|---|---|---|---|---|
| Chint Power Systems America: CPS ECB125KTL-M/US-480 {480V} Chint Power Systems America |
125,000 W | -8148 W | 480.0 V | 1100.0 V | 97.2% |
| Delta Electronics: DES10JB125K01 {480V} Delta Electronics |
125,000 W | -8148 W | 480.0 V | 1000.0 V | 97.01% |
| Delta Electronics: PCS125 {480V} Delta Electronics |
125,000 W | -8148 W | 480.0 V | 1000.0 V | 97.01% |
| Ginlong Technologies Co Ltd: S5-GC125K-US {480V} Ginlong Technologies Co Ltd |
124,991 W | -8157 W | 480.0 V | 850.0 V | 97.88% |
What Are the Interconnection Limits and Best-Fit Uses for Star Charge Americas Corp: SI135TULT00 {480V}?
Check Star Charge Americas Corp: SI135TULT00 {480V} (133,148 W AC, 225 A OCPD) against your main panel busbar, winter string Voc, and IEEE 1547 outage rules.
- Anti-islanding shutdown: grid-tied inverters shut off within 2 seconds during blackouts under IEEE 1547 unless paired with a battery microgrid interconnect.
- Busbar 120% limit: Commercial 480 V, 3-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (480V) or NEC 705.11 supply-side tap.
- Cold Voc hard ceiling: never allow winter open-circuit PV string voltage to exceed 1,050 V DC on Star Charge Americas Corp: SI135TULT00 {480V}.
Star Charge Americas Corp: SI135TULT00 {480V} Panel & Wire Spec
Size 75 C copper conductors at 4/0 AWG Cu on a 225 A OCPD breaker (160.2 A continuous).
Alternative Inverter Comparison
Compare efficiency (98.07%) and MPPT window (810-1,050 V) directly against Chint Power Systems America: CPS ECB125KTL-M/US-480 {480V} (125,000 W).
Which Homeowner Electrical & Solar Questions Come Up Most Often?
Answers for Star Charge Americas Corp: SI135TULT00 {480V} by Star Charge Americas Corp covering breaker sizing, MPPT limits, and 480 V, 3-phase interconnection.
What breaker and wire size does Star Charge Americas Corp: SI135TULT00 {480V} require?
At 133,148 W continuous AC (480 V, 3-phase), continuous current is 160.2 A; 125% NEC 690.8/705.12 sizing requires a 225 A breaker and 4/0 AWG Cu (75 C) wire.
What commercial switchgear or feeder sizing does Star Charge Americas Corp: SI135TULT00 {480V} require?
At 133,148 W AC and 480 V, 3-phase, continuous line current is 160.2 A, requiring a 225 A OCPD and 1,200A Bus / 1,200A Main (480V) or NEC 705.11 interconnection.
How does Star Charge Americas Corp: SI135TULT00 {480V} compare to Chint Power Systems America: CPS ECB125KTL-M/US-480 {480V}?
Star Charge Americas Corp: SI135TULT00 {480V} delivers 133,148 W AC at 98.07% CEC efficiency with a 1,050 V DC ceiling, while Chint Power Systems America: CPS ECB125KTL-M/US-480 {480V} outputs 125,000 W at 480 V, 3-phase.