JingTsing Technology Ltd: JTES-PCS450K-1600/740-L03C1 {740V} outputs 459,563 W AC at 740 V, 3-phase (358.6 A continuous, 450 A OCPD), ranking #81 of 2,343 CEC inverters at 98.48% efficiency with a 1,100-1,600 V MPPT window and 1,600 V DC limit. All figures reconcile directly against federal energy archives, state electrical licensing boards, California Energy Commission datasheets, and National Electrical Code engineering constants.
- AC Output (Paco)
- 459,563 W
- AC Voltage
- 740 V, 3-phase
- Min PV Breaker
- 450 A (parallel Cu feeders)
- CEC Efficiency
- 98.48%
How Does JingTsing Technology Ltd: JTES-PCS450K-1600/740-L03C1 {740V} Compare Against Peer CEC Listings?
CEC efficiency rank (#81), 1,100-1,600 V MPPT tracking, and panel fit for JingTsing Technology Ltd: JTES-PCS450K-1600/740-L03C1 {740V}.
Operating at 740 V, 3-phase, JingTsing Technology Ltd: JTES-PCS450K-1600/740-L03C1 {740V} converts DC array energy at 98.48% CEC weighted efficiency (top 3.6%; higher than 96.4% of peers) with a 1,600 V max DC input and 333.323 A max input current for NEC 690.7 string safety. Compare this 459,563 W grid-tied PV inverter directly with EPC Power Corp: 50-200100 {720V} (561,806 W). Commercial 740 V, 3-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (740V) or NEC 705.11 supply-side tap.
Where Does JingTsing Technology Ltd: JTES-PCS450K-1600/740-L03C1 {740V} Fall Across Listed CEC Models?
CEC inverter wattage histogram highlighting JingTsing Technology Ltd: JTES-PCS450K-1600/740-L03C1 {740V} at 459,563 W continuous AC output. All figures trace directly to published federal energy filings, state electrical boards, CEC datasheets, and NFPA 70 NEC tables.
What Dataset Percentiles Define JingTsing Technology Ltd: JTES-PCS450K-1600/740-L03C1 {740V}?
Dataset percentiles comparing JingTsing Technology Ltd: JTES-PCS450K-1600/740-L03C1 {740V} against 2,343 certified grid-support inverters nationwide. Use these verified dataset benchmarks alongside a licensed electrician load calculation to compare residential upgrade bids with confidence.
What Do the Dataset Ranks Show for JingTsing Technology Ltd: JTES-PCS450K-1600/740-L03C1 {740V}?
Engineering highlights for JingTsing Technology Ltd: JTES-PCS450K-1600/740-L03C1 {740V} covering efficiency, parallel Cu feeders feeder, and panel compatibility.
98.48% CEC Weighted Efficiency
equal to the 98.48% 740 V median; overall power rank #205 (459,563 W, top 8.7%; higher than 91.3% of peers).
450 A Required Backfeed OCPD
125% x 358.6 A = 448.2 A -> 450 A standard OCPD using parallel Cu feeders (75 C).
1,100 V - 1,600 V (Max 1,600 V DC)
Tracking span of 500.0 V; active in CEC directory (grid-tied PV inverter).
Supply-Side Tap (705.11) / Dedicated Switchboard
Evaluated for 740 V, 3-phase switchgear (200A Bus / 200A Main (740V) to 1,200A Bus / 1,200A Main (740V)) under NEC 705.12 / 705.11.
NEC 705.12 Backfeed OCPD & 120% Busbar Formula
I_cont = 459563.0W / 740 V 3-phase -> 358.6 A | Breaker >= 1.25 * 358.6 = 448.2 A -> 450 A
CEC Inverters.csv for JingTsing Technology Ltd: JTES-PCS450K-1600/740-L03C1 {740V}: Paco=459563.0 W, Vac=740 V, Vdcmax=1600.0 V, Eff=98.48%.
Result: Min 450 A breaker & parallel Cu feeders (75 C); 1,200A Bus / 1,200A Main (740V): Supply-Side Tap (705.11) / Dedicated Switchboard.
What Are the Published CEC Specifications for JingTsing Technology Ltd: JTES-PCS450K-1600/740-L03C1 {740V}?
California Energy Commission Solar Equipment List parameters for JingTsing Technology Ltd: JTES-PCS450K-1600/740-L03C1 {740V} (grid-tied PV inverter) interconnection.
| Parameter | Measured / Listed Value | Engineering Significance |
|---|---|---|
| Max Continuous AC Power (Paco) | 459,563 W | Determines required backfeed OCPD size via 125% continuous rule |
| Nominal AC Voltage (Vac) | 740 V, 3-phase | 240V split-phase residential vs. 208V/480V/MV commercial |
| Max DC Input Voltage (Vdcmax) | 1,600 V | Hard ceiling for cold-weather PV string Voc under NEC 690.7 |
| MPPT Operating Range | 1,100 V - 1,600 V | Optimal DC string Vmp window for full power harvest |
| Max Input DC Current (Idcmax) | 333.323 A | Used to verify parallel string combiner limits |
| CEC Weighted Efficiency | 98.48% | Calculated AC/DC conversion ratio from CEC test protocol |
| Inverter Topology | Hybrid: No (Grid-Tied PV) | CEC Solar Equipment List grid-support certification |
What Switchgear Limits Apply to JingTsing Technology Ltd: JTES-PCS450K-1600/740-L03C1 {740V} (740 V, 3-phase)?
Panelboard and switchgear backfeed allowances for JingTsing Technology Ltd: JTES-PCS450K-1600/740-L03C1 {740V} (450 A OCPD). Review related calculators, peer benchmarks, and source citations below to validate design assumptions for your electrical service.
| Switchboard / Interconnect | 120% Max Backfeed | Required PV OCPD | Compliance Verdict |
|---|---|---|---|
| 200A Bus / 200A Main (740V) | 40 A | 450 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| 400A Bus / 400A Main (740V) | 80 A | 450 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| 600A Bus / 600A Main (740V) | 120 A | 450 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| 800A Bus / 800A Main (740V) | 160 A | 450 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| 1,200A Bus / 1,200A Main (740V) | 240 A | 450 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
Which CEC PV Module Strings Pair With JingTsing Technology Ltd: JTES-PCS450K-1600/740-L03C1 {740V}?
Representative PV panel pairings verified under NEC 690.7 cold Voc for JingTsing Technology Ltd: JTES-PCS450K-1600/740-L03C1 {740V}. Every reported metric links directly to federal public records or state regulatory filings with zero paid contractor placements.
| CEC Module | STC (W) | -10 C Voc | Valid String Range | Max String DC |
|---|---|---|---|---|
| AXITEC AC-590TGB/144TS | 590.0 W | 56.24 V | 26 to 28 panels | 16.52 kW |
| Aptos Solar Technology LLC DNA-108-MFN10-440W | 440.0 W | 42.15 V | 33 to 37 panels | 16.28 kW |
| Boviet Solar Technology Co Ltd BVM7610M-425-H-HC-BF | 425.0 W | 44.75 V | 32 to 35 panels | 14.88 kW |
| CSI Solar Co Ltd CS6P-200P | 200.0 W | 40.6 V | 39 panels (fixed) | 7.8 kW |
Which Competing Grid-Support Inverters Compare to JingTsing Technology Ltd: JTES-PCS450K-1600/740-L03C1 {740V}?
Four alternative CEC inverters matched to JingTsing Technology Ltd: JTES-PCS450K-1600/740-L03C1 {740V} (459,563 W AC), led by EPC Power Corp: 50-200100 {720V}.
| Alternative Inverter | AC Output | Delta | Vac | Max DC | CEC Eff |
|---|---|---|---|---|---|
| EPC Power Corp: 50-200100 {720V} EPC Power Corp |
561,806 W | +102243 W | 720.0 V | 1500.0 V | 98.58% |
| ABB: PVS-175-TL-POWER-MODULE-1-US {800V} ABB |
179,574 W | -279989 W | 800.0 V | 1200.0 V | 97.39% |
| LS Energy Solutions LLC: PBE-6140-R61-1A0-1000 {600V} LS Energy Solutions LLC |
139,449 W | -320114 W | 600.0 V | 1350.0 V | 98.27% |
| SMA America: SHP FLEX-US-21 {385V} SMA America |
100,842 W | -358721 W | 385.0 V | 1195.0 V | 97.8% |
What Are the Interconnection Limits and Best-Fit Uses for JingTsing Technology Ltd: JTES-PCS450K-1600/740-L03C1 {740V}?
Check JingTsing Technology Ltd: JTES-PCS450K-1600/740-L03C1 {740V} (459,563 W AC, 450 A OCPD) against your main panel busbar, winter string Voc, and IEEE 1547 outage rules.
- Anti-islanding shutdown: grid-tied inverters shut off within 2 seconds during blackouts under IEEE 1547 unless paired with a battery microgrid interconnect.
- Busbar 120% limit: Commercial 740 V, 3-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (740V) or NEC 705.11 supply-side tap.
- Cold Voc hard ceiling: never allow winter open-circuit PV string voltage to exceed 1,600 V DC on JingTsing Technology Ltd: JTES-PCS450K-1600/740-L03C1 {740V}.
JingTsing Technology Ltd: JTES-PCS450K-1600/740-L03C1 {740V} Panel & Wire Spec
Size 75 C copper conductors at parallel Cu feeders on a 450 A OCPD breaker (358.6 A continuous).
Alternative Inverter Comparison
Compare efficiency (98.48%) and MPPT window (1,100-1,600 V) directly against EPC Power Corp: 50-200100 {720V} (561,806 W).
Which Homeowner Electrical & Solar Questions Come Up Most Often?
Answers for JingTsing Technology Ltd: JTES-PCS450K-1600/740-L03C1 {740V} by JingTsing Technology Ltd covering breaker sizing, MPPT limits, and 740 V, 3-phase interconnection.
What breaker and wire size does JingTsing Technology Ltd: JTES-PCS450K-1600/740-L03C1 {740V} require?
At 459,563 W continuous AC (740 V, 3-phase), continuous current is 358.6 A; 125% NEC 690.8/705.12 sizing requires a 450 A breaker and parallel Cu feeders (75 C) wire.
What commercial switchgear or feeder sizing does JingTsing Technology Ltd: JTES-PCS450K-1600/740-L03C1 {740V} require?
At 459,563 W AC and 740 V, 3-phase, continuous line current is 358.6 A, requiring a 450 A OCPD and 1,200A Bus / 1,200A Main (740V) or NEC 705.11 interconnection.
How does JingTsing Technology Ltd: JTES-PCS450K-1600/740-L03C1 {740V} compare to EPC Power Corp: 50-200100 {720V}?
JingTsing Technology Ltd: JTES-PCS450K-1600/740-L03C1 {740V} delivers 459,563 W AC at 98.48% CEC efficiency with a 1,600 V DC ceiling, while EPC Power Corp: 50-200100 {720V} outputs 561,806 W at 740 V, 3-phase.
Sources
- CEC Solar Equipment List — Grid-Support Inverters (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
- CEC Solar Equipment List — PV Modules (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
- NFPA 70 National Electrical Code (Section Numbers & Standard Engineering Tables Only) — National Fire Protection Association (NFPA), 2020 / 2023 / 2026 Editions (retrieved 2026-11-23)