Ginlong Technologies Co Ltd: Solis-36K-US-LSW {480V} outputs 35,925 W AC at 480 V, 3-phase (43.2 A continuous, 60 A OCPD), ranking #175 of 2,343 CEC inverters at 98.32% efficiency with a 500-800 V MPPT window and 800 V DC limit. All figures reconcile directly against federal energy archives, state electrical licensing boards, California Energy Commission datasheets, and National Electrical Code engineering constants.
- AC Output (Paco)
- 35,925 W
- AC Voltage
- 480 V, 3-phase
- Min PV Breaker
- 60 A (6 AWG Cu)
- CEC Efficiency
- 98.32%
How Does Ginlong Technologies Co Ltd: Solis-36K-US-LSW {480V} Compare Against Peer CEC Listings?
Breaker sizing (60 A), 6 AWG Cu wire rules, and DC input limits for Ginlong Technologies Co Ltd: Solis-36K-US-LSW {480V}.
Classified as a grid-tied PV inverter (active in CEC directory), Ginlong Technologies Co Ltd: Solis-36K-US-LSW {480V} requires 54.0 A design capacity -> 60 A breaker using 6 AWG Cu copper at 75 C terminals. Weighted efficiency sits at 98.32% (+1.50 pts vs overall CEC median) across 2,343 CEC models, while commercial 480 v, 3-phase switchgear interconnection uses 1,200a bus / 1,200a main (480v) or nec 705.11 supply-side tap.
Where Does Ginlong Technologies Co Ltd: Solis-36K-US-LSW {480V} Fall Across Listed CEC Models?
Output power comparison showing where Ginlong Technologies Co Ltd: Solis-36K-US-LSW {480V} sits among all 2,343 CEC-listed grid-support inverters.
What Dataset Percentiles Define Ginlong Technologies Co Ltd: Solis-36K-US-LSW {480V}?
Relative ranking of Ginlong Technologies Co Ltd: Solis-36K-US-LSW {480V} on continuous AC power, CEC weighted efficiency, and OCPD breaker current.
What Do the Dataset Ranks Show for Ginlong Technologies Co Ltd: Solis-36K-US-LSW {480V}?
Snapshot of Ginlong Technologies Co Ltd: Solis-36K-US-LSW {480V} efficiency rank (#175), OCPD breaker size, MPPT span, and busbar verdict.
98.32% CEC Weighted Efficiency
+0.30 pts vs the 98.02% 480 V median; overall power rank #521 (35,925 W, top 22.3%; higher than 77.7% of peers).
60 A Required Backfeed OCPD
125% x 43.2 A = 54.0 A -> 60 A standard OCPD using 6 AWG Cu (75 C).
500 V - 800 V (Max 800 V DC)
Tracking span of 300.0 V; active in CEC directory (grid-tied PV inverter).
PASS (120% Commercial Busbar)
Evaluated for 480 V, 3-phase switchgear (200A Bus / 200A Main (480V) to 1,200A Bus / 1,200A Main (480V)) under NEC 705.12 / 705.11.
NEC 705.12 Backfeed OCPD & 120% Busbar Formula
I_cont = 35925.0W / 480 V 3-phase -> 43.2 A | Breaker >= 1.25 * 43.2 = 54.0 A -> 60 A
CEC Inverters.csv for Ginlong Technologies Co Ltd: Solis-36K-US-LSW {480V}: Paco=35925.0 W, Vac=480 V, Vdcmax=800.0 V, Eff=98.32%.
Result: Min 60 A breaker & 6 AWG Cu (75 C); 1,200A Bus / 1,200A Main (480V): PASS (120% Commercial Busbar).
What Are the Published CEC Specifications for Ginlong Technologies Co Ltd: Solis-36K-US-LSW {480V}?
Complete California Energy Commission grid-support inverter ratings and hybrid battery capabilities for Ginlong Technologies Co Ltd: Solis-36K-US-LSW {480V}.
| Parameter | Measured / Listed Value | Engineering Significance |
|---|---|---|
| Max Continuous AC Power (Paco) | 35,925 W | Determines required backfeed OCPD size via 125% continuous rule |
| Nominal AC Voltage (Vac) | 480 V, 3-phase | 240V split-phase residential vs. 208V/480V/MV commercial |
| Max DC Input Voltage (Vdcmax) | 800 V | Hard ceiling for cold-weather PV string Voc under NEC 690.7 |
| MPPT Operating Range | 500 V - 800 V | Optimal DC string Vmp window for full power harvest |
| Max Input DC Current (Idcmax) | 52.1979 A | Used to verify parallel string combiner limits |
| CEC Weighted Efficiency | 98.32% | Calculated AC/DC conversion ratio from CEC test protocol |
| Inverter Topology | Hybrid: No (Grid-Tied PV) | CEC Solar Equipment List grid-support certification |
What Switchgear Limits Apply to Ginlong Technologies Co Ltd: Solis-36K-US-LSW {480V} (480 V, 3-phase)?
NEC 705.12(B)(3)(2) backfeed compliance table for Ginlong Technologies Co Ltd: Solis-36K-US-LSW {480V} at 480 V, 3-phase.
| Switchboard / Interconnect | 120% Max Backfeed | Required PV OCPD | Compliance Verdict |
|---|---|---|---|
| 200A Bus / 200A Main (480V) | 40 A | 60 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| 400A Bus / 400A Main (480V) | 80 A | 60 A | PASS (120% Commercial Busbar) |
| 600A Bus / 600A Main (480V) | 120 A | 60 A | PASS (120% Commercial Busbar) |
| 800A Bus / 800A Main (480V) | 160 A | 60 A | PASS (120% Commercial Busbar) |
| 1,200A Bus / 1,200A Main (480V) | 240 A | 60 A | PASS (120% Commercial Busbar) |
Which CEC PV Module Strings Pair With Ginlong Technologies Co Ltd: Solis-36K-US-LSW {480V}?
Minimum and maximum series solar module strings fitting Ginlong Technologies Co Ltd: Solis-36K-US-LSW {480V} MPPT and 800 V limits.
| CEC Module | STC (W) | -10 C Voc | Valid String Range | Max String DC |
|---|---|---|---|---|
| AXITEC AC-590TGB/144TS | 590.0 W | 56.24 V | 12 to 14 panels | 8.26 kW |
| Aptos Solar Technology LLC DNA-108-MFN10-440W | 440.0 W | 42.15 V | 15 to 18 panels | 7.92 kW |
| Boviet Solar Technology Co Ltd BVM7610M-425-H-HC-BF | 425.0 W | 44.75 V | 15 to 17 panels | 7.22 kW |
| CSI Solar Co Ltd CS6P-200P | 200.0 W | 40.6 V | 18 to 19 panels | 3.8 kW |
Which Competing Grid-Support Inverters Compare to Ginlong Technologies Co Ltd: Solis-36K-US-LSW {480V}?
Peer 480 V, 3-phase CEC inverters near 35,925 W AC output such as CSI Solar Co Ltd: CSI-36K-T480GL01-UB {480V}.
| Alternative Inverter | AC Output | Delta | Vac | Max DC | CEC Eff |
|---|---|---|---|---|---|
| CSI Solar Co Ltd: CSI-36K-T480GL01-UB {480V} CSI Solar Co Ltd |
35,925 W | Tie (0 W) | 480.0 V | 800.0 V | 98.32% |
| CSI Solar Co Ltd: CSI-36K-T480GL03-U {480V} CSI Solar Co Ltd |
35,866 W | -59 W | 480.0 V | 850.0 V | 98.21% |
| Canadian Solar Inc: CSI-36KTL-CT {480V} Canadian Solar Inc |
36,000 W | +75 W | 480.0 V | 800.0 V | 98.09% |
| Canadian Solar Inc: CSI-36KTL-GS-FL {480V} Canadian Solar Inc |
36,000 W | +75 W | 480.0 V | 780.0 V | 98.05% |
What Are the Interconnection Limits and Best-Fit Uses for Ginlong Technologies Co Ltd: Solis-36K-US-LSW {480V}?
Check Ginlong Technologies Co Ltd: Solis-36K-US-LSW {480V} (35,925 W AC, 60 A OCPD) against your main panel busbar, winter string Voc, and IEEE 1547 outage rules.
- Anti-islanding shutdown: grid-tied inverters shut off within 2 seconds during blackouts under IEEE 1547 unless paired with a battery microgrid interconnect.
- Busbar 120% limit: Commercial 480 V, 3-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (480V) or NEC 705.11 supply-side tap.
- Cold Voc hard ceiling: never allow winter open-circuit PV string voltage to exceed 800 V DC on Ginlong Technologies Co Ltd: Solis-36K-US-LSW {480V}.
Ginlong Technologies Co Ltd: Solis-36K-US-LSW {480V} Panel & Wire Spec
Size 75 C copper conductors at 6 AWG Cu on a 60 A OCPD breaker (43.2 A continuous).
Alternative Inverter Comparison
Compare efficiency (98.32%) and MPPT window (500-800 V) directly against CSI Solar Co Ltd: CSI-36K-T480GL01-UB {480V} (35,925 W).
Which Homeowner Electrical & Solar Questions Come Up Most Often?
Answers for Ginlong Technologies Co Ltd: Solis-36K-US-LSW {480V} by Ginlong Technologies Co Ltd covering breaker sizing, MPPT limits, and 480 V, 3-phase interconnection.
What breaker and wire size does Ginlong Technologies Co Ltd: Solis-36K-US-LSW {480V} require?
At 35,925 W continuous AC (480 V, 3-phase), continuous current is 43.2 A; 125% NEC 690.8/705.12 sizing requires a 60 A breaker and 6 AWG Cu (75 C) wire.
What commercial switchgear or feeder sizing does Ginlong Technologies Co Ltd: Solis-36K-US-LSW {480V} require?
At 35,925 W AC and 480 V, 3-phase, continuous line current is 43.2 A, requiring a 60 A OCPD and 1,200A Bus / 1,200A Main (480V) or NEC 705.11 interconnection.
How does Ginlong Technologies Co Ltd: Solis-36K-US-LSW {480V} compare to CSI Solar Co Ltd: CSI-36K-T480GL01-UB {480V}?
Ginlong Technologies Co Ltd: Solis-36K-US-LSW {480V} delivers 35,925 W AC at 98.32% CEC efficiency with a 800 V DC ceiling, while CSI Solar Co Ltd: CSI-36K-T480GL01-UB {480V} outputs 35,925 W at 480 V, 3-phase.
Sources
- CEC Solar Equipment List — Grid-Support Inverters (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
- CEC Solar Equipment List — PV Modules (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
- NFPA 70 National Electrical Code (Section Numbers & Standard Engineering Tables Only) — National Fire Protection Association (NFPA), 2020 / 2023 / 2026 Editions (retrieved 2026-11-23)