Ginlong Technologies Co Ltd: Solis-36K-US {480V} outputs 36,000 W AC at 480 V, 3-phase (43.3 A continuous, 60 A OCPD), ranking #318 of 2,343 CEC inverters at 98.05% efficiency with a 580-780 V MPPT window and 780 V DC limit. All figures reconcile directly against federal energy archives, state electrical licensing boards, California Energy Commission datasheets, and National Electrical Code engineering constants.
- AC Output (Paco)
- 36,000 W
- AC Voltage
- 480 V, 3-phase
- Min PV Breaker
- 60 A (6 AWG Cu)
- CEC Efficiency
- 98.05%
How Does Ginlong Technologies Co Ltd: Solis-36K-US {480V} Compare Against Peer CEC Listings?
CEC efficiency rank (#318), 580-780 V MPPT tracking, and panel fit for Ginlong Technologies Co Ltd: Solis-36K-US {480V}.
Operating at 480 V, 3-phase, Ginlong Technologies Co Ltd: Solis-36K-US {480V} converts DC array energy at 98.05% CEC weighted efficiency (top 14.1%; higher than 85.9% of peers) with a 780 V max DC input and 56.4834 A max input current for NEC 690.7 string safety. Compare this 36,000 W grid-tied PV inverter directly with Canadian Solar Inc: CSI-36KTL-CT {480V} (36,000 W). Commercial 480 V, 3-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (480V) or NEC 705.11 supply-side tap.
Where Does Ginlong Technologies Co Ltd: Solis-36K-US {480V} Fall Across Listed CEC Models?
CEC inverter wattage histogram highlighting Ginlong Technologies Co Ltd: Solis-36K-US {480V} at 36,000 W continuous AC output. Review related calculators, peer benchmarks, and source citations below to validate design assumptions for your electrical service.
What Dataset Percentiles Define Ginlong Technologies Co Ltd: Solis-36K-US {480V}?
Dataset percentiles comparing Ginlong Technologies Co Ltd: Solis-36K-US {480V} against 2,343 certified grid-support inverters nationwide. Every reported metric links directly to federal public records or state regulatory filings with zero paid contractor placements.
What Do the Dataset Ranks Show for Ginlong Technologies Co Ltd: Solis-36K-US {480V}?
Engineering highlights for Ginlong Technologies Co Ltd: Solis-36K-US {480V} covering efficiency, 6 AWG Cu feeder, and panel compatibility.
98.05% CEC Weighted Efficiency
+0.03 pts vs the 98.02% 480 V median; overall power rank #510 (36,000 W, top 22.2%; higher than 77.8% of peers).
60 A Required Backfeed OCPD
125% x 43.3 A = 54.1 A -> 60 A standard OCPD using 6 AWG Cu (75 C).
580 V - 780 V (Max 780 V DC)
Tracking span of 200.0 V; listed since 2019-11-15 (grid-tied PV inverter).
PASS (120% Commercial Busbar)
Evaluated for 480 V, 3-phase switchgear (200A Bus / 200A Main (480V) to 1,200A Bus / 1,200A Main (480V)) under NEC 705.12 / 705.11.
NEC 705.12 Backfeed OCPD & 120% Busbar Formula
I_cont = 36000.0W / 480 V 3-phase -> 43.3 A | Breaker >= 1.25 * 43.3 = 54.1 A -> 60 A
CEC Inverters.csv for Ginlong Technologies Co Ltd: Solis-36K-US {480V}: Paco=36000.0 W, Vac=480 V, Vdcmax=780.0 V, Eff=98.05%.
Result: Min 60 A breaker & 6 AWG Cu (75 C); 1,200A Bus / 1,200A Main (480V): PASS (120% Commercial Busbar).
What Are the Published CEC Specifications for Ginlong Technologies Co Ltd: Solis-36K-US {480V}?
California Energy Commission Solar Equipment List parameters for Ginlong Technologies Co Ltd: Solis-36K-US {480V} (grid-tied PV inverter) interconnection.
| Parameter | Measured / Listed Value | Engineering Significance |
|---|---|---|
| Max Continuous AC Power (Paco) | 36,000 W | Determines required backfeed OCPD size via 125% continuous rule |
| Nominal AC Voltage (Vac) | 480 V, 3-phase | 240V split-phase residential vs. 208V/480V/MV commercial |
| Max DC Input Voltage (Vdcmax) | 780 V | Hard ceiling for cold-weather PV string Voc under NEC 690.7 |
| MPPT Operating Range | 580 V - 780 V | Optimal DC string Vmp window for full power harvest |
| Max Input DC Current (Idcmax) | 56.4834 A | Used to verify parallel string combiner limits |
| CEC Weighted Efficiency | 98.05% | Calculated AC/DC conversion ratio from CEC test protocol |
| CEC Listing Date & Hybrid | 2019-11-15 / Hybrid: No (Grid-Tied PV) | Utility interconnection approval metadata |
What Switchgear Limits Apply to Ginlong Technologies Co Ltd: Solis-36K-US {480V} (480 V, 3-phase)?
Panelboard and switchgear backfeed allowances for Ginlong Technologies Co Ltd: Solis-36K-US {480V} (60 A OCPD). Cross-check local Authority Having Jurisdiction amendments and serving utility net-metering terms before finalizing project sizing.
| Switchboard / Interconnect | 120% Max Backfeed | Required PV OCPD | Compliance Verdict |
|---|---|---|---|
| 200A Bus / 200A Main (480V) | 40 A | 60 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| 400A Bus / 400A Main (480V) | 80 A | 60 A | PASS (120% Commercial Busbar) |
| 600A Bus / 600A Main (480V) | 120 A | 60 A | PASS (120% Commercial Busbar) |
| 800A Bus / 800A Main (480V) | 160 A | 60 A | PASS (120% Commercial Busbar) |
| 1,200A Bus / 1,200A Main (480V) | 240 A | 60 A | PASS (120% Commercial Busbar) |
Which CEC PV Module Strings Pair With Ginlong Technologies Co Ltd: Solis-36K-US {480V}?
Representative PV panel pairings verified under NEC 690.7 cold Voc for Ginlong Technologies Co Ltd: Solis-36K-US {480V}. Regional housing vintage, storm hazard frequency, and wholesale utility prices directly govern residential upgrade payback across jurisdictions.
| CEC Module | STC (W) | -10 C Voc | Valid String Range | Max String DC |
|---|---|---|---|---|
| Aptos Solar Technology LLC DNA-108-MFN10-440W | 440.0 W | 42.15 V | 18 panels (fixed) | 7.92 kW |
| Boviet Solar Technology Co Ltd BVM7610M-425-H-HC-BF | 425.0 W | 44.75 V | 17 panels (fixed) | 7.22 kW |
| G-Star Pte Ltd GSN8K66T(H)740WT | 740.0 W | 54.38 V | 14 panels (fixed) | 10.36 kW |
Which Competing Grid-Support Inverters Compare to Ginlong Technologies Co Ltd: Solis-36K-US {480V}?
Four alternative CEC inverters matched to Ginlong Technologies Co Ltd: Solis-36K-US {480V} (36,000 W AC), led by Canadian Solar Inc: CSI-36KTL-CT {480V}.
| Alternative Inverter | AC Output | Delta | Vac | Max DC | CEC Eff |
|---|---|---|---|---|---|
| Canadian Solar Inc: CSI-36KTL-CT {480V} Canadian Solar Inc |
36,000 W | Tie (0 W) | 480.0 V | 800.0 V | 98.09% |
| Canadian Solar Inc: CSI-36KTL-GS-FL {480V} Canadian Solar Inc |
36,000 W | Tie (0 W) | 480.0 V | 780.0 V | 98.05% |
| Chint Power Systems America: CPS SCA36KTL-DO/US-480 {480V} Chint Power Systems America |
36,000 W | Tie (0 W) | 480.0 V | 850.0 V | 97.62% |
| Chint Power Systems America: CPS SCA36KTL-DO/US {480V} Chint Power Systems America |
36,000 W | Tie (0 W) | 480.0 V | 800.0 V | 98.09% |
What Are the Interconnection Limits and Best-Fit Uses for Ginlong Technologies Co Ltd: Solis-36K-US {480V}?
Check Ginlong Technologies Co Ltd: Solis-36K-US {480V} (36,000 W AC, 60 A OCPD) against your main panel busbar, winter string Voc, and IEEE 1547 outage rules.
- Anti-islanding shutdown: grid-tied inverters shut off within 2 seconds during blackouts under IEEE 1547 unless paired with a battery microgrid interconnect.
- Busbar 120% limit: Commercial 480 V, 3-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (480V) or NEC 705.11 supply-side tap.
- Cold Voc hard ceiling: never allow winter open-circuit PV string voltage to exceed 780 V DC on Ginlong Technologies Co Ltd: Solis-36K-US {480V}.
Ginlong Technologies Co Ltd: Solis-36K-US {480V} Panel & Wire Spec
Size 75 C copper conductors at 6 AWG Cu on a 60 A OCPD breaker (43.3 A continuous).
Alternative Inverter Comparison
Compare efficiency (98.05%) and MPPT window (580-780 V) directly against Canadian Solar Inc: CSI-36KTL-CT {480V} (36,000 W).
Which Homeowner Electrical & Solar Questions Come Up Most Often?
Answers for Ginlong Technologies Co Ltd: Solis-36K-US {480V} by Ginlong Technologies Co Ltd covering breaker sizing, MPPT limits, and 480 V, 3-phase interconnection.
What breaker and wire size does Ginlong Technologies Co Ltd: Solis-36K-US {480V} require?
At 36,000 W continuous AC (480 V, 3-phase), continuous current is 43.3 A; 125% NEC 690.8/705.12 sizing requires a 60 A breaker and 6 AWG Cu (75 C) wire.
What commercial switchgear or feeder sizing does Ginlong Technologies Co Ltd: Solis-36K-US {480V} require?
At 36,000 W AC and 480 V, 3-phase, continuous line current is 43.3 A, requiring a 60 A OCPD and 1,200A Bus / 1,200A Main (480V) or NEC 705.11 interconnection.
How does Ginlong Technologies Co Ltd: Solis-36K-US {480V} compare to Canadian Solar Inc: CSI-36KTL-CT {480V}?
Ginlong Technologies Co Ltd: Solis-36K-US {480V} delivers 36,000 W AC at 98.05% CEC efficiency with a 780 V DC ceiling, while Canadian Solar Inc: CSI-36KTL-CT {480V} outputs 36,000 W at 480 V, 3-phase.
Sources
- CEC Solar Equipment List — Grid-Support Inverters (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
- CEC Solar Equipment List — PV Modules (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
- NFPA 70 National Electrical Code (Section Numbers & Standard Engineering Tables Only) — National Fire Protection Association (NFPA), 2020 / 2023 / 2026 Editions (retrieved 2026-11-23)