Gamesa Electric: PV4700 {690V} outputs 4,654,418 W AC at 690 V, 3-phase (3894.6 A continuous, 4,900 A OCPD), ranking #422 of 2,343 CEC inverters at 97.8% efficiency with a 955-1,300 V MPPT window and 1,300 V DC limit. All figures reconcile directly against federal energy archives, state electrical licensing boards, California Energy Commission datasheets, and National Electrical Code engineering constants.
- AC Output (Paco)
- 4,654,418 W
- AC Voltage
- 690 V, 3-phase
- Min PV Breaker
- 4,900 A (parallel Cu feeders)
- CEC Efficiency
- 97.8%
How Does Gamesa Electric: PV4700 {690V} Compare Against Peer CEC Listings?
Breaker sizing (4,900 A), parallel Cu feeders wire rules, and DC input limits for Gamesa Electric: PV4700 {690V}.
Classified as a grid-tied PV inverter (listed since 2021-12-01), Gamesa Electric: PV4700 {690V} requires 4868.2 A design capacity -> 4,900 A breaker using parallel Cu feeders copper at 75 C terminals. Weighted efficiency sits at 97.8% (+0.98 pts vs overall CEC median) across 2,343 CEC models, while commercial 690 v, 3-phase switchgear interconnection uses 1,200a bus / 1,200a main (690v) or nec 705.11 supply-side tap.
Where Does Gamesa Electric: PV4700 {690V} Fall Across Listed CEC Models?
Output power comparison showing where Gamesa Electric: PV4700 {690V} sits among all 2,343 CEC-listed grid-support inverters. Every reported metric links directly to federal public records or state regulatory filings with zero paid contractor placements.
What Dataset Percentiles Define Gamesa Electric: PV4700 {690V}?
Relative ranking of Gamesa Electric: PV4700 {690V} on continuous AC power, CEC weighted efficiency, and OCPD breaker current.
What Do the Dataset Ranks Show for Gamesa Electric: PV4700 {690V}?
Snapshot of Gamesa Electric: PV4700 {690V} efficiency rank (#422), OCPD breaker size, MPPT span, and busbar verdict. All figures trace directly to published federal energy filings, state electrical boards, CEC datasheets, and NFPA 70 NEC tables.
97.8% CEC Weighted Efficiency
-0.37 pts vs the 98.17% 690 V median; overall power rank #2 (4,654,418 W, top 0.1%; higher than 99.9% of peers).
4,900 A Required Backfeed OCPD
125% x 3894.6 A = 4868.2 A -> 4,900 A standard OCPD using parallel Cu feeders (75 C).
955 V - 1,300 V (Max 1,300 V DC)
Tracking span of 345.0 V; listed since 2021-12-01 (grid-tied PV inverter).
Supply-Side Tap (705.11) / Dedicated Switchboard
Evaluated for 690 V, 3-phase switchgear (200A Bus / 200A Main (690V) to 1,200A Bus / 1,200A Main (690V)) under NEC 705.12 / 705.11.
NEC 705.12 Backfeed OCPD & 120% Busbar Formula
I_cont = 4654418.0W / 690 V 3-phase -> 3894.6 A | Breaker >= 1.25 * 3894.6 = 4868.2 A -> 4,900 A
CEC Inverters.csv for Gamesa Electric: PV4700 {690V}: Paco=4654418.0 W, Vac=690 V, Vdcmax=1300.0 V, Eff=97.8%.
Result: Min 4,900 A breaker & parallel Cu feeders (75 C); 1,200A Bus / 1,200A Main (690V): Supply-Side Tap (705.11) / Dedicated Switchboard.
What Are the Published CEC Specifications for Gamesa Electric: PV4700 {690V}?
Complete California Energy Commission grid-support inverter ratings and hybrid battery capabilities for Gamesa Electric: PV4700 {690V}. Homeowners and permit reviewers can filter tables below to benchmark specific ratings, wiring ages, and code allowances side by side.
| Parameter | Measured / Listed Value | Engineering Significance |
|---|---|---|
| Max Continuous AC Power (Paco) | 4,654,418 W | Determines required backfeed OCPD size via 125% continuous rule |
| Nominal AC Voltage (Vac) | 690 V, 3-phase | 240V split-phase residential vs. 208V/480V/MV commercial |
| Max DC Input Voltage (Vdcmax) | 1,300 V | Hard ceiling for cold-weather PV string Voc under NEC 690.7 |
| MPPT Operating Range | 955 V - 1,300 V | Optimal DC string Vmp window for full power harvest |
| Max Input DC Current (Idcmax) | 4532.32 A | Used to verify parallel string combiner limits |
| CEC Weighted Efficiency | 97.8% | Calculated AC/DC conversion ratio from CEC test protocol |
| CEC Listing Date & Hybrid | 2021-12-01 / Hybrid: No (Grid-Tied PV) | Utility interconnection approval metadata |
What Switchgear Limits Apply to Gamesa Electric: PV4700 {690V} (690 V, 3-phase)?
NEC 705.12(B)(3)(2) backfeed compliance table for Gamesa Electric: PV4700 {690V} at 690 V, 3-phase. Regional housing vintage, storm hazard frequency, and wholesale utility prices directly govern residential upgrade payback across jurisdictions.
| Switchboard / Interconnect | 120% Max Backfeed | Required PV OCPD | Compliance Verdict |
|---|---|---|---|
| 200A Bus / 200A Main (690V) | 40 A | 4,900 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| 400A Bus / 400A Main (690V) | 80 A | 4,900 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| 600A Bus / 600A Main (690V) | 120 A | 4,900 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| 800A Bus / 800A Main (690V) | 160 A | 4,900 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| 1,200A Bus / 1,200A Main (690V) | 240 A | 4,900 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
Which CEC PV Module Strings Pair With Gamesa Electric: PV4700 {690V}?
Minimum and maximum series solar module strings fitting Gamesa Electric: PV4700 {690V} MPPT and 1,300 V limits. Review related calculators, peer benchmarks, and source citations below to validate design assumptions for your electrical service.
| CEC Module | STC (W) | -10 C Voc | Valid String Range | Max String DC |
|---|---|---|---|---|
| AXITEC AC-590TGB/144TS | 590.0 W | 56.24 V | 23 panels (fixed) | 13.57 kW |
| Aptos Solar Technology LLC DNA-108-MFN10-440W | 440.0 W | 42.15 V | 29 to 30 panels | 13.2 kW |
| Boviet Solar Technology Co Ltd BVM7610M-425-H-HC-BF | 425.0 W | 44.75 V | 28 to 29 panels | 12.32 kW |
| Chint New Energy Technology Co Ltd CHSM72M(DG)/F-BH-515 | 515.0 W | 53.76 V | 24 panels (fixed) | 12.36 kW |
Which Competing Grid-Support Inverters Compare to Gamesa Electric: PV4700 {690V}?
Peer 690 V, 3-phase CEC inverters near 4,654,418 W AC output such as Delta Electronics: PCS4300X-X00-US {690V}. Published percentiles compare local state, county, metro, and certified equipment metrics against nationwide residential electrical baselines.
| Alternative Inverter | AC Output | Delta | Vac | Max DC | CEC Eff |
|---|---|---|---|---|---|
| Delta Electronics: PCS4300X-X00-US {690V} Delta Electronics |
4,308,400 W | -346018 W | 690.0 V | 1500.0 V | 98.27% |
| SMA America: SC 4600 UP-US 690V 3850A {690V} SMA America |
4,198,235 W | -456183 W | 690.0 V | 1200.0 V | 98.27% |
| Delta Electronics: PCS4300X-X01-US {690V} Delta Electronics |
4,009,000 W | -645418 W | 690.0 V | 1500.0 V | 98.35% |
| Delta Electronics: PCSC3556 {690V} Delta Electronics |
3,570,330 W | -1084088 W | 690.0 V | 1500.0 V | 98.39% |
What Are the Interconnection Limits and Best-Fit Uses for Gamesa Electric: PV4700 {690V}?
Check Gamesa Electric: PV4700 {690V} (4,654,418 W AC, 4,900 A OCPD) against your main panel busbar, winter string Voc, and IEEE 1547 outage rules.
- Anti-islanding shutdown: grid-tied inverters shut off within 2 seconds during blackouts under IEEE 1547 unless paired with a battery microgrid interconnect.
- Busbar 120% limit: Commercial 690 V, 3-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (690V) or NEC 705.11 supply-side tap.
- Cold Voc hard ceiling: never allow winter open-circuit PV string voltage to exceed 1,300 V DC on Gamesa Electric: PV4700 {690V}.
Gamesa Electric: PV4700 {690V} Panel & Wire Spec
Size 75 C copper conductors at parallel Cu feeders on a 4,900 A OCPD breaker (3894.6 A continuous).
Alternative Inverter Comparison
Compare efficiency (97.8%) and MPPT window (955-1,300 V) directly against Delta Electronics: PCS4300X-X00-US {690V} (4,308,400 W).
Which Homeowner Electrical & Solar Questions Come Up Most Often?
Answers for Gamesa Electric: PV4700 {690V} by Gamesa Electric covering breaker sizing, MPPT limits, and 690 V, 3-phase interconnection.
What breaker and wire size does Gamesa Electric: PV4700 {690V} require?
At 4,654,418 W continuous AC (690 V, 3-phase), continuous current is 3894.6 A; 125% NEC 690.8/705.12 sizing requires a 4,900 A breaker and parallel Cu feeders (75 C) wire.
What commercial switchgear or feeder sizing does Gamesa Electric: PV4700 {690V} require?
At 4,654,418 W AC and 690 V, 3-phase, continuous line current is 3894.6 A, requiring a 4,900 A OCPD and 1,200A Bus / 1,200A Main (690V) or NEC 705.11 interconnection.
How does Gamesa Electric: PV4700 {690V} compare to Delta Electronics: PCS4300X-X00-US {690V}?
Gamesa Electric: PV4700 {690V} delivers 4,654,418 W AC at 97.8% CEC efficiency with a 1,300 V DC ceiling, while Delta Electronics: PCS4300X-X00-US {690V} outputs 4,308,400 W at 690 V, 3-phase.
Sources
- CEC Solar Equipment List — Grid-Support Inverters (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
- CEC Solar Equipment List — PV Modules (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
- NFPA 70 National Electrical Code (Section Numbers & Standard Engineering Tables Only) — National Fire Protection Association (NFPA), 2020 / 2023 / 2026 Editions (retrieved 2026-11-23)