Fronius International GmbH: Fronius Symo 125-3 480 {480V} outputs 12,500 W AC at 480 V, 3-phase (15.0 A continuous, 20 A OCPD), ranking #522 of 2,343 CEC inverters at 97.57% efficiency with a 350-800 V MPPT window and 800 V DC limit. All figures reconcile directly against federal energy archives, state electrical licensing boards, California Energy Commission datasheets, and National Electrical Code engineering constants.
- AC Output (Paco)
- 12,500 W
- AC Voltage
- 480 V, 3-phase
- Min PV Breaker
- 20 A (12 AWG Cu)
- CEC Efficiency
- 97.57%
How Does Fronius International GmbH: Fronius Symo 125-3 480 {480V} Compare Against Peer CEC Listings?
CEC efficiency rank (#522), 350-800 V MPPT tracking, and panel fit for Fronius International GmbH: Fronius Symo 125-3 480 {480V}.
Operating at 480 V, 3-phase, Fronius International GmbH: Fronius Symo 125-3 480 {480V} converts DC array energy at 97.57% CEC weighted efficiency (top 22.4%; higher than 77.6% of peers) with a 800 V max DC input and 18.7032 A max input current for NEC 690.7 string safety. Compare this 12,500 W grid-tied PV inverter directly with Chint Power Systems America: CPS SCA20KTL-DO-R/US-480 {480V} (20,000 W). Commercial 480 V, 3-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (480V) or NEC 705.11 supply-side tap.
Where Does Fronius International GmbH: Fronius Symo 125-3 480 {480V} Fall Across Listed CEC Models?
CEC inverter wattage histogram highlighting Fronius International GmbH: Fronius Symo 125-3 480 {480V} at 12,500 W continuous AC output.
What Dataset Percentiles Define Fronius International GmbH: Fronius Symo 125-3 480 {480V}?
Dataset percentiles comparing Fronius International GmbH: Fronius Symo 125-3 480 {480V} against 2,343 certified grid-support inverters nationwide. Compare thermal ratings, overcurrent protection caps, and continuous load headroom carefully before expanding an existing home service panel.
What Do the Dataset Ranks Show for Fronius International GmbH: Fronius Symo 125-3 480 {480V}?
Engineering highlights for Fronius International GmbH: Fronius Symo 125-3 480 {480V} covering efficiency, 12 AWG Cu feeder, and panel compatibility.
97.57% CEC Weighted Efficiency
-0.45 pts vs the 98.02% 480 V median; overall power rank #699 (12,500 W, top 29.9%; higher than 70.1% of peers).
20 A Required Backfeed OCPD
125% x 15.0 A = 18.8 A -> 20 A standard OCPD using 12 AWG Cu (75 C).
350 V - 800 V (Max 800 V DC)
Tracking span of 450.0 V; listed since 2019-03-01 (grid-tied PV inverter).
PASS (120% Commercial Busbar)
Evaluated for 480 V, 3-phase switchgear (200A Bus / 200A Main (480V) to 1,200A Bus / 1,200A Main (480V)) under NEC 705.12 / 705.11.
NEC 705.12 Backfeed OCPD & 120% Busbar Formula
I_cont = 12500.0W / 480 V 3-phase -> 15.0 A | Breaker >= 1.25 * 15.0 = 18.8 A -> 20 A
CEC Inverters.csv for Fronius International GmbH: Fronius Symo 125-3 480 {480V}: Paco=12500.0 W, Vac=480 V, Vdcmax=800.0 V, Eff=97.57%.
Result: Min 20 A breaker & 12 AWG Cu (75 C); 1,200A Bus / 1,200A Main (480V): PASS (120% Commercial Busbar).
What Are the Published CEC Specifications for Fronius International GmbH: Fronius Symo 125-3 480 {480V}?
California Energy Commission Solar Equipment List parameters for Fronius International GmbH: Fronius Symo 125-3 480 {480V} (grid-tied PV inverter) interconnection.
| Parameter | Measured / Listed Value | Engineering Significance |
|---|---|---|
| Max Continuous AC Power (Paco) | 12,500 W | Determines required backfeed OCPD size via 125% continuous rule |
| Nominal AC Voltage (Vac) | 480 V, 3-phase | 240V split-phase residential vs. 208V/480V/MV commercial |
| Max DC Input Voltage (Vdcmax) | 800 V | Hard ceiling for cold-weather PV string Voc under NEC 690.7 |
| MPPT Operating Range | 350 V - 800 V | Optimal DC string Vmp window for full power harvest |
| Max Input DC Current (Idcmax) | 18.7032 A | Used to verify parallel string combiner limits |
| CEC Weighted Efficiency | 97.57% | Calculated AC/DC conversion ratio from CEC test protocol |
| CEC Listing Date & Hybrid | 2019-03-01 / Hybrid: No (Grid-Tied PV) | Utility interconnection approval metadata |
What Switchgear Limits Apply to Fronius International GmbH: Fronius Symo 125-3 480 {480V} (480 V, 3-phase)?
Panelboard and switchgear backfeed allowances for Fronius International GmbH: Fronius Symo 125-3 480 {480V} (20 A OCPD). Data intervals combine current 2025 federal utility and BLS wage releases with verified state electrical board rosters.
| Switchboard / Interconnect | 120% Max Backfeed | Required PV OCPD | Compliance Verdict |
|---|---|---|---|
| 200A Bus / 200A Main (480V) | 40 A | 20 A | PASS (120% Commercial Busbar) |
| 400A Bus / 400A Main (480V) | 80 A | 20 A | PASS (120% Commercial Busbar) |
| 600A Bus / 600A Main (480V) | 120 A | 20 A | PASS (120% Commercial Busbar) |
| 800A Bus / 800A Main (480V) | 160 A | 20 A | PASS (120% Commercial Busbar) |
| 1,200A Bus / 1,200A Main (480V) | 240 A | 20 A | PASS (120% Commercial Busbar) |
Which CEC PV Module Strings Pair With Fronius International GmbH: Fronius Symo 125-3 480 {480V}?
Representative PV panel pairings verified under NEC 690.7 cold Voc for Fronius International GmbH: Fronius Symo 125-3 480 {480V}.
| CEC Module | STC (W) | -10 C Voc | Valid String Range | Max String DC |
|---|---|---|---|---|
| AXITEC AC-590TGB/144TS | 590.0 W | 56.24 V | 9 to 14 panels | 8.26 kW |
| Aptos Solar Technology LLC DNA-108-MFN10-440W | 440.0 W | 42.15 V | 11 to 18 panels | 7.92 kW |
| Boviet Solar Technology Co Ltd BVM7610M-425-H-HC-BF | 425.0 W | 44.75 V | 11 to 17 panels | 7.22 kW |
| CSI Solar Co Ltd CS6P-200P | 200.0 W | 40.6 V | 13 to 19 panels | 3.8 kW |
Which Competing Grid-Support Inverters Compare to Fronius International GmbH: Fronius Symo 125-3 480 {480V}?
Four alternative CEC inverters matched to Fronius International GmbH: Fronius Symo 125-3 480 {480V} (12,500 W AC), led by Chint Power Systems America: CPS SCA20KTL-DO-R/US-480 {480V}.
| Alternative Inverter | AC Output | Delta | Vac | Max DC | CEC Eff |
|---|---|---|---|---|---|
| Chint Power Systems America: CPS SCA20KTL-DO-R/US-480 {480V} Chint Power Systems America |
20,000 W | +7500 W | 480.0 V | 850.0 V | 97.86% |
| Altenergy Power System Inc: QT2-480 {480V} Altenergy Power System Inc |
1,821 W | -10679 W | 480.0 V | 42.0 V | 96.02% |
| Altenergy Power System Inc: QT2 {480V} Altenergy Power System Inc |
1,821 W | -10679 W | 480.0 V | 42.0 V | 96.02% |
| CSI Solar Co Ltd: CSI-25K-T480GL03-U {480V} CSI Solar Co Ltd |
24,888 W | +12388 W | 480.0 V | 850.0 V | 98.37% |
What Are the Interconnection Limits and Best-Fit Uses for Fronius International GmbH: Fronius Symo 125-3 480 {480V}?
Check Fronius International GmbH: Fronius Symo 125-3 480 {480V} (12,500 W AC, 20 A OCPD) against your main panel busbar, winter string Voc, and IEEE 1547 outage rules.
- Anti-islanding shutdown: grid-tied inverters shut off within 2 seconds during blackouts under IEEE 1547 unless paired with a battery microgrid interconnect.
- Busbar 120% limit: Commercial 480 V, 3-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (480V) or NEC 705.11 supply-side tap.
- Cold Voc hard ceiling: never allow winter open-circuit PV string voltage to exceed 800 V DC on Fronius International GmbH: Fronius Symo 125-3 480 {480V}.
Fronius International GmbH: Fronius Symo 125-3 480 {480V} Panel & Wire Spec
Size 75 C copper conductors at 12 AWG Cu on a 20 A OCPD breaker (15.0 A continuous).
Alternative Inverter Comparison
Compare efficiency (97.57%) and MPPT window (350-800 V) directly against Chint Power Systems America: CPS SCA20KTL-DO-R/US-480 {480V} (20,000 W).
Which Homeowner Electrical & Solar Questions Come Up Most Often?
Answers for Fronius International GmbH: Fronius Symo 125-3 480 {480V} by Fronius International GmbH covering breaker sizing, MPPT limits, and 480 V, 3-phase interconnection.
What breaker and wire size does Fronius International GmbH: Fronius Symo 125-3 480 {480V} require?
At 12,500 W continuous AC (480 V, 3-phase), continuous current is 15.0 A; 125% NEC 690.8/705.12 sizing requires a 20 A breaker and 12 AWG Cu (75 C) wire.
What commercial switchgear or feeder sizing does Fronius International GmbH: Fronius Symo 125-3 480 {480V} require?
At 12,500 W AC and 480 V, 3-phase, continuous line current is 15.0 A, requiring a 20 A OCPD and 1,200A Bus / 1,200A Main (480V) or NEC 705.11 interconnection.
How does Fronius International GmbH: Fronius Symo 125-3 480 {480V} compare to Chint Power Systems America: CPS SCA20KTL-DO-R/US-480 {480V}?
Fronius International GmbH: Fronius Symo 125-3 480 {480V} delivers 12,500 W AC at 97.57% CEC efficiency with a 800 V DC ceiling, while Chint Power Systems America: CPS SCA20KTL-DO-R/US-480 {480V} outputs 20,000 W at 480 V, 3-phase.
Sources
- CEC Solar Equipment List — Grid-Support Inverters (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
- CEC Solar Equipment List — PV Modules (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
- NFPA 70 National Electrical Code (Section Numbers & Standard Engineering Tables Only) — National Fire Protection Association (NFPA), 2020 / 2023 / 2026 Editions (retrieved 2026-11-23)