Chint Power Systems America: CPS SCH125KTL-DO/US-600 {600V} outputs 125,000 W AC at 600 V, 3-phase (120.3 A continuous, 175 A OCPD), ranking #238 of 2,343 CEC inverters at 98.21% efficiency with a 870-1,300 V MPPT window and 1,300 V DC limit. All figures reconcile directly against federal energy archives, state electrical licensing boards, California Energy Commission datasheets, and National Electrical Code engineering constants.
- AC Output (Paco)
- 125,000 W
- AC Voltage
- 600 V, 3-phase
- Min PV Breaker
- 175 A (2/0 AWG Cu)
- CEC Efficiency
- 98.21%
How Does Chint Power Systems America: CPS SCH125KTL-DO/US-600 {600V} Compare Against Peer CEC Listings?
Breaker sizing (175 A), 2/0 AWG Cu wire rules, and DC input limits for Chint Power Systems America: CPS SCH125KTL-DO/US-600 {600V}.
Classified as a grid-tied PV inverter (listed since 2022-06-13), Chint Power Systems America: CPS SCH125KTL-DO/US-600 {600V} requires 150.4 A design capacity -> 175 A breaker using 2/0 AWG Cu copper at 75 C terminals. Weighted efficiency sits at 98.21% (+1.39 pts vs overall CEC median) across 2,343 CEC models, while commercial 600 v, 3-phase switchgear interconnection uses 1,200a bus / 1,200a main (600v) or nec 705.11 supply-side tap.
Where Does Chint Power Systems America: CPS SCH125KTL-DO/US-600 {600V} Fall Across Listed CEC Models?
Output power comparison showing where Chint Power Systems America: CPS SCH125KTL-DO/US-600 {600V} sits among all 2,343 CEC-listed grid-support inverters.
What Dataset Percentiles Define Chint Power Systems America: CPS SCH125KTL-DO/US-600 {600V}?
Relative ranking of Chint Power Systems America: CPS SCH125KTL-DO/US-600 {600V} on continuous AC power, CEC weighted efficiency, and OCPD breaker current.
What Do the Dataset Ranks Show for Chint Power Systems America: CPS SCH125KTL-DO/US-600 {600V}?
Snapshot of Chint Power Systems America: CPS SCH125KTL-DO/US-600 {600V} efficiency rank (#238), OCPD breaker size, MPPT span, and busbar verdict.
98.21% CEC Weighted Efficiency
-0.07 pts vs the 98.28% 600 V median; overall power rank #300 (125,000 W, top 13.4%; higher than 86.6% of peers).
175 A Required Backfeed OCPD
125% x 120.3 A = 150.4 A -> 175 A standard OCPD using 2/0 AWG Cu (75 C).
870 V - 1,300 V (Max 1,300 V DC)
Tracking span of 430.0 V; listed since 2022-06-13 (grid-tied PV inverter).
Supply-Side Tap (705.11) / Dedicated Switchboard
Evaluated for 600 V, 3-phase switchgear (200A Bus / 200A Main (600V) to 1,200A Bus / 1,200A Main (600V)) under NEC 705.12 / 705.11.
NEC 705.12 Backfeed OCPD & 120% Busbar Formula
I_cont = 125000.0W / 600 V 3-phase -> 120.3 A | Breaker >= 1.25 * 120.3 = 150.4 A -> 175 A
CEC Inverters.csv for Chint Power Systems America: CPS SCH125KTL-DO/US-600 {600V}: Paco=125000.0 W, Vac=600 V, Vdcmax=1300.0 V, Eff=98.21%.
Result: Min 175 A breaker & 2/0 AWG Cu (75 C); 1,200A Bus / 1,200A Main (600V): PASS (120% Commercial Busbar).
What Are the Published CEC Specifications for Chint Power Systems America: CPS SCH125KTL-DO/US-600 {600V}?
Complete California Energy Commission grid-support inverter ratings and hybrid battery capabilities for Chint Power Systems America: CPS SCH125KTL-DO/US-600 {600V}.
| Parameter | Measured / Listed Value | Engineering Significance |
|---|---|---|
| Max Continuous AC Power (Paco) | 125,000 W | Determines required backfeed OCPD size via 125% continuous rule |
| Nominal AC Voltage (Vac) | 600 V, 3-phase | 240V split-phase residential vs. 208V/480V/MV commercial |
| Max DC Input Voltage (Vdcmax) | 1,300 V | Hard ceiling for cold-weather PV string Voc under NEC 690.7 |
| MPPT Operating Range | 870 V - 1,300 V | Optimal DC string Vmp window for full power harvest |
| Max Input DC Current (Idcmax) | 127.274 A | Used to verify parallel string combiner limits |
| CEC Weighted Efficiency | 98.21% | Calculated AC/DC conversion ratio from CEC test protocol |
| CEC Listing Date & Hybrid | 2022-06-13 / Hybrid: No (Grid-Tied PV) | Utility interconnection approval metadata |
What Switchgear Limits Apply to Chint Power Systems America: CPS SCH125KTL-DO/US-600 {600V} (600 V, 3-phase)?
NEC 705.12(B)(3)(2) backfeed compliance table for Chint Power Systems America: CPS SCH125KTL-DO/US-600 {600V} at 600 V, 3-phase.
| Switchboard / Interconnect | 120% Max Backfeed | Required PV OCPD | Compliance Verdict |
|---|---|---|---|
| 200A Bus / 200A Main (600V) | 40 A | 175 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| 400A Bus / 400A Main (600V) | 80 A | 175 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| 600A Bus / 600A Main (600V) | 120 A | 175 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| 800A Bus / 800A Main (600V) | 160 A | 175 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| 1,200A Bus / 1,200A Main (600V) | 240 A | 175 A | PASS (120% Commercial Busbar) |
Which CEC PV Module Strings Pair With Chint Power Systems America: CPS SCH125KTL-DO/US-600 {600V}?
Minimum and maximum series solar module strings fitting Chint Power Systems America: CPS SCH125KTL-DO/US-600 {600V} MPPT and 1,300 V limits.
| CEC Module | STC (W) | -10 C Voc | Valid String Range | Max String DC |
|---|---|---|---|---|
| AXITEC AC-590TGB/144TS | 590.0 W | 56.24 V | 21 to 23 panels | 13.57 kW |
| Aptos Solar Technology LLC DNA-108-MFN10-440W | 440.0 W | 42.15 V | 26 to 30 panels | 13.2 kW |
| Boviet Solar Technology Co Ltd BVM7610M-425-H-HC-BF | 425.0 W | 44.75 V | 26 to 29 panels | 12.32 kW |
| CSI Solar Co Ltd CS6P-200P | 200.0 W | 40.6 V | 31 to 32 panels | 6.4 kW |
Which Competing Grid-Support Inverters Compare to Chint Power Systems America: CPS SCH125KTL-DO/US-600 {600V}?
Peer 600 V, 3-phase CEC inverters near 125,000 W AC output such as CSI Solar Co Ltd: CSI-125KTL-GS-E {600V}.
| Alternative Inverter | AC Output | Delta | Vac | Max DC | CEC Eff |
|---|---|---|---|---|---|
| CSI Solar Co Ltd: CSI-125KTL-GS-E {600V} CSI Solar Co Ltd |
125,000 W | Tie (0 W) | 600.0 V | 1250.0 V | 98.63% |
| Ginlong Technologies Co Ltd: Solis-125K-EHV-5G {600V} Ginlong Technologies Co Ltd |
125,000 W | Tie (0 W) | 600.0 V | 1250.0 V | 98.63% |
| Schneider Electric USA Inc: Conext CL125 {600V} Schneider Electric USA Inc |
125,000 W | Tie (0 W) | 600.0 V | 1200.0 V | 98.1% |
| Sungrow Power Supply Co Ltd: SG125HV {600V} Sungrow Power Supply Co Ltd |
125,000 W | Tie (0 W) | 600.0 V | 1200.0 V | 98.1% |
What Are the Interconnection Limits and Best-Fit Uses for Chint Power Systems America: CPS SCH125KTL-DO/US-600 {600V}?
Check Chint Power Systems America: CPS SCH125KTL-DO/US-600 {600V} (125,000 W AC, 175 A OCPD) against your main panel busbar, winter string Voc, and IEEE 1547 outage rules.
- Anti-islanding shutdown: grid-tied inverters shut off within 2 seconds during blackouts under IEEE 1547 unless paired with a battery microgrid interconnect.
- Busbar 120% limit: Commercial 600 V, 3-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (600V) or NEC 705.11 supply-side tap.
- Cold Voc hard ceiling: never allow winter open-circuit PV string voltage to exceed 1,300 V DC on Chint Power Systems America: CPS SCH125KTL-DO/US-600 {600V}.
Chint Power Systems America: CPS SCH125KTL-DO/US-600 {600V} Panel & Wire Spec
Size 75 C copper conductors at 2/0 AWG Cu on a 175 A OCPD breaker (120.3 A continuous).
Alternative Inverter Comparison
Compare efficiency (98.21%) and MPPT window (870-1,300 V) directly against CSI Solar Co Ltd: CSI-125KTL-GS-E {600V} (125,000 W).
Which Homeowner Electrical & Solar Questions Come Up Most Often?
Answers for Chint Power Systems America: CPS SCH125KTL-DO/US-600 {600V} by Chint Power Systems America covering breaker sizing, MPPT limits, and 600 V, 3-phase interconnection.
What breaker and wire size does Chint Power Systems America: CPS SCH125KTL-DO/US-600 {600V} require?
At 125,000 W continuous AC (600 V, 3-phase), continuous current is 120.3 A; 125% NEC 690.8/705.12 sizing requires a 175 A breaker and 2/0 AWG Cu (75 C) wire.
What commercial switchgear or feeder sizing does Chint Power Systems America: CPS SCH125KTL-DO/US-600 {600V} require?
At 125,000 W AC and 600 V, 3-phase, continuous line current is 120.3 A, requiring a 175 A OCPD and 1,200A Bus / 1,200A Main (600V) or NEC 705.11 interconnection.
How does Chint Power Systems America: CPS SCH125KTL-DO/US-600 {600V} compare to CSI Solar Co Ltd: CSI-125KTL-GS-E {600V}?
Chint Power Systems America: CPS SCH125KTL-DO/US-600 {600V} delivers 125,000 W AC at 98.21% CEC efficiency with a 1,300 V DC ceiling, while CSI Solar Co Ltd: CSI-125KTL-GS-E {600V} outputs 125,000 W at 600 V, 3-phase.