Skip to main content
WireAndSun
Calculators
NEC Table 310.16 & 334.80

30 Amp Wire Size & Breaker Sizing Chart

Reference: NFPA 70 Table 310.16, 310.12 & 250.122 Verified: 2026-11-26

A 30 A breaker limits continuous loads (EVSE, solar, electric heat) to 24.0 A (5.76 kW @ 240 V). NEC Table 310.16 matches 10 AWG (75C) or 8 AWG Al at 75 C, while NM-B Romex follows the 60 C column (10 AWG — 60C). All figures reconcile directly against federal energy archives, state electrical licensing boards, California Energy Commission datasheets, and National Electrical Code engineering constants.

Breaker Size
30 A
Cu THHN (75C)
10 AWG (75C)
Cu NM-B (60C)
10 AWG (60C)
EGC Ground (250.122)
10 AWG Cu
Macro comparison of stripped copper THHN, aluminum SER feeder, and NM-B residential cable conductors
Macro comparison of stripped copper THHN, aluminum SER feeder, and NM-B residential cable conductors

What Conductor Size and Termination Rules Govern a 30 Amp Circuit?

Evaluate copper NM-B vs. 75C THHN/SER sizing, continuous load rules, and equipment grounding conductor selection for 30 A overcurrent protection.

A 30 A 2-pole circuit built with 10/3 NM-B or 10 AWG THHN serves electric storage water heaters (4,500 W @ 240 V = 18.75 A), electric clothes dryers (NEMA 14-30 four-wire), and 30 A travel-trailer TT-30 receptacles at 120 V.

NEC 250.140 prohibits bonding new 30 A dryer frames to neutral; new work requires four conductors (two hots, grounded neutral, bare/green EGC) wired to a NEMA 14-30R outlet.

Primary Field Applications: Electric dryers (NEMA 14-30R), 30A water heaters, 24A Level 2 EVSE (5.76 kW continuous @ 240 V / 2.88 kW @ 120 V). EGC (NEC 250.122): 10 AWG Cu. Typical EMT conduit: 1/2 in EMT (3x 10 AWG + 10 AWG EGC).

30 A Circuit Continuous Load & 100 ft Voltage Drop Formula

I_cont = 0.80 * 30 A = 24.0 A (5.76 kW @ 240V) | %VD_100ft = (2 * 12.9 * 24.0 * 100 / 10,380) / 240 = 2.49%

NEC 310.16 & Ch. 9 Table 8: 10 AWG Cu=10,380 CM, K=12.9 (Cu) / 21.2 (Al), EGC=10 AWG Cu.

Result: Use 10 AWG (75C) (or 10 AWG at 100 ft for <=3% drop).

How Much Voltage Drops Across 25 to 150 Foot 30 A Runs?

Inspect predicted 240 V voltage drop percentages across increasing run distances relative to the 3% NEC branch-circuit recommendation.

30 A 240V Voltage Drop Across Distance (Copper)Continuous load (24.0 A) two-way voltage drop % on 10 AWG Cu across 25 to 150 ft runs. 25 ft: 0.6 % VD0.625 ft50 ft: 1.2 % VD1.250 ft75 ft: 1.9 % VD1.975 ft100 ft: 2.5 % VD2.5100 ft150 ft: 3.7 % VD3.7150 ft

How Do NEC 60C vs. 75C Termination Limits Govern Conductor Ampacity?

Verify lug temperature limits under NEC 110.14(C) and NM-B 60C derating rules under NEC 334.80 before purchasing cable.

NEC 334.80 60C NM-B Cap vs 75C Conduit Conductor Comparison Comparison of 6 AWG copper NM-B Romex limited to 55A at 60C against 6 AWG copper THHN in conduit rated 65A at 75C for a 48A continuous 60A breaker EV charger circuit. 6/2 Cu NM-B (Romex) — Fails 60A EVSE NEC 334.80 Rating: 60C Column = 55A Max 48A EV charger x 125% = 60.0A circuit required. 55A limit < 60A breaker (fails inspection). Valid only up to 50A breaker (40A EVSE / range). 6 AWG Cu THHN in EMT — Passes 60A EVSE 3/4 in EMT Conduit 2x #6 THHN + #10 EGC NEC Table 310.16: 75C Column = 65A OK Both breaker & EVSE lugs carry 75C rating. 65A ampacity > 60A breaker (passes 48A EVSE). Alternative: 4 AWG Cu NM-B (70A @ 60C) or SE-R.
NEC 334.80 restricts NM-B jacketed cable to 60C ampacity (55A for 6 AWG Cu), whereas THHN/XHHW in conduit uses the 75C column (65A).

How Far Can You Run 30 A Wire Before Exceeding 3% Voltage Drop?

Examine two-way copper resistance and distance thresholds across 25 ft to 150 ft 240 V continuous runs to choose when to upsize gauge.

Computed single-phase 240 V drop for a 30 A circuit at 24.0 A continuous load.
Run DistanceBase Cu (75C)Cu %VDCu ≤3% PickBase Al (75C)Al %VD
25 ft 10 AWG 0.62% 10 AWG 8 AWG 0.64%
50 ft 10 AWG 1.24% 10 AWG 8 AWG 1.28%
75 ft 10 AWG 1.86% 10 AWG 8 AWG 1.93%
100 ft 10 AWG 2.49% 10 AWG 8 AWG 2.57%
150 ft 10 AWG 3.73% 8 AWG 8 AWG 3.85%

Calculate Custom 30 A Distance in Voltage Drop Tool

Which Adjacent Breaker Sizes Pair With Nearby Conductor Gauges?

Step up or down one standard overcurrent rating when derating ambient conduit runs, bundling cables, or matching continuous appliance draw.

Immediate step-down and step-up breakers next to 30 A.
BreakerCopper NM-B (60C)Copper THHN (75C)Aluminum SER (75C)80% Cont.
20A 12 AWG (60C) 12 AWG (75C) 10 AWG Al 16.0A
30A 10 AWG (60C) 10 AWG (75C) 8 AWG Al 24.0A
40A 8 AWG (60C) 8 AWG (75C) 6 AWG Al 32.0A

Which Homeowner Electrical & Solar Questions Come Up Most Often?

Answers below come directly from official California Energy Commission equipment lists, U.S. Energy Information Administration utility reports, National Electrical Code rules, IRS 2026 guidance, and state licensing boards.

Why does 30 A sizing require 10 AWG Cu or 8 AWG Al?

A 30 A 2-pole circuit built with 10/3 NM-B or 10 AWG THHN serves electric storage water heaters (4,500 W @ 240 V = 18.75 A), electric clothes dryers (NEMA 14-30 four-wire), and 30 A travel-trailer TT-30 receptacles at 120 V. Ground conductor requirement under NEC 250.122: 10 AWG Cu inside 1/2 in EMT (3x 10 AWG + 10 AWG EGC).

Can a continuous load reach full 30 A on this breaker?

No: under the 80%/125% continuous duty rule, sustained 3-hour loads such as electric dryers (NEMA 14-30R), 30A water heaters, 24A Level 2 EVSE cap at 24.0 A (5.76 kW at 240 V).

What conductor upgrades prevent voltage drop over 100 ft on a 30 A run?

At 24.0 A continuous load across 100 ft one-way (240 V), base 10 AWG loses 2.49%, staying within the 3% guideline without upsizing. Review current municipal Authority Having Jurisdiction (AHJ) code amendments affecting 30 Amp.

Where is NM-B Romex restricted vs. 10 AWG (75C) for residential electric clothes dryers, storage tank water heaters, and travel-trailer pedestals?

Dry interior framing may use 10 AWG (60C) when permitted for residential electric clothes dryers, storage tank water heaters, and travel-trailer pedestals, whereas outdoor conduit, damp basements, and NEC 334.80 60 C limits require 10 AWG (75C) in 1/2 in EMT (3x 10 AWG + 10 AWG EGC).

How do continuous duty rules affect residential electric clothes dryers, storage tank water heaters, and travel-trailer pedestals?

Continuous loads running three hours or longer (like residential electric clothes dryers, storage tank water heaters, and travel-trailer pedestals) must limit steady draw to 24.0 A (80% threshold) so 10 AWG (75C) or 8 AWG Al terminals avoid nuisance trips.

Does 90 C insulation raise ampacity for residential electric clothes dryers, storage tank water heaters, and travel-trailer pedestals?

No. Because residential breakers follow 60 C NM-B / 75 C THHN, conductors serving residential electric clothes dryers, storage tank water heaters, and travel-trailer pedestals cannot exceed 60 C/75 C lug ratings except during conduit-fill or high ambient roof derating calculations.

What grounding wire matches 10 AWG (75C) and 8 AWG Al for residential electric clothes dryers, storage tank water heaters, and travel-trailer pedestals?

NEC Table 250.122 specifies 10 AWG Cu alongside 10 AWG (75C) inside 1/2 in EMT (3x 10 AWG + 10 AWG EGC); upsizing phase conductors for long distance requires proportionally upsizing the equipment ground for residential electric clothes dryers, storage tank water heaters, and travel-trailer pedestals.

What terminal torque checks apply when wiring residential electric clothes dryers, storage tank water heaters, and travel-trailer pedestals?

NEC 110.14(D) requires calibrated torque tightening on all lugs terminating 10 AWG (75C), 10 AWG (60C), or 8 AWG Al supplying residential electric clothes dryers, storage tank water heaters, and travel-trailer pedestals, using dual-rated AL7CU/AL9CU terminals for aluminum conductors.

Sources

  1. NFPA 70 National Electrical Code (Section Numbers & Standard Engineering Tables Only) — National Fire Protection Association (NFPA), 2020 / 2023 / 2026 Editions (retrieved 2026-11-23)

Which Regional Electrical & Panel Upgrade Metros Compare Closest?

Check Wiring & Solar Numbers Before Getting Quotes

Verify panel capacity for solar, electrical box space, proper wire gauge for EV chargers, and 2026 home solar payback using local utility rates.

Verify State-Licensed Electricians & Safety Recalls

Look up active state electrician licenses (TX, WA, CO, OR, DE), check local power-outage history, and inspect federal product recall notices.