Elin Energy (Sirius PV) ELNSM60M-HC-LV-475 — CEC Solar Module Specifications

Manufacturer: Elin Energy (Sirius PV) Registry: CEC Verified Engineering Specification

Elin Energy (Sirius PV) ELNSM60M-HC-LV-475 is a 475.0 W STC (448.4 W PTC) Mono-c-Si solar module ranking #4,892 of 21,677 CEC listings (top 22.9%; higher than 77.1% of peers). It delivers 22.09% efficiency, 41.82 V Voc at 25 C, and 45.25 V cold Voc at -10 C (13 panels max per 600 V string).

STC Wattage
475.0 W
PTC Wattage
448.4 W
Voc @ 25C
41.82 V
Efficiency
22.09%
Wall-mounted residential hybrid solar inverter and modular battery cabinet piped with galvanized EMT conduit
Wall-mounted residential hybrid solar inverter and modular battery cabinet piped with galvanized EMT conduit

How Does Elin Energy (Sirius PV) ELNSM60M-HC-LV-475 Compare Against Peer CEC Listings?

How Elin Energy (Sirius PV) Elin Energy (Sirius PV) ELNSM60M-HC-LV-475 handles rooftop heat (448.4 W PTC), 8 kW sizing, and cold winter string voltage.

Elin Energy (Sirius PV) builds the Elin Energy (Sirius PV) ELNSM60M-HC-LV-475 (Mono-c-Si) as a modern high-density residential and light-commercial module delivering 220.9 W/m2 (2.18 percentage points above 19.91% CEC median). Compared against CSI Solar Co Ltd CS61-60TM-470H (470.0 W), this model holds strong 94.4% PTC-to-STC heat retention (#2,840 of 21,677). Mid-range 41.82 V open-circuit voltage allows up to 13 panels per 600 V string at 14 F, while NEC 690.8 sets a 22.25 A overcurrent floor served by a 25 A breaker.

Where Does Elin Energy (Sirius PV) ELNSM60M-HC-LV-475 Fall Across Listed CEC Models?

Where Elin Energy (Sirius PV) ELNSM60M-HC-LV-475 (475.0 W) sits inside the 21,677-panel CEC STC wattage curve relative to the 385.0 W median.

STC Power Distribution Across 21,677 CEC Solar ModulesMarks where Elin Energy (Sirius PV) ELNSM60M-HC-LV-475 (475.0 W STC) stands relative to CEC photovoltaic modules. 18-79 W STC: 68 entries1879-140 W STC: 170 entries140-202 W STC: 413 entries202-263 W STC: 1,883 entries202263-325 W STC: 4,202 entries325-386 W STC: 4,219 entries386-448 W STC: 4,695 entries386448-509 W STC: 1,584 entries509-571 W STC: 2,290 entries571-632 W STC: 1,371 entries571632-694 W STC: 534 entries694-755 W STC: 248 entries694Median 385 W STCElin Energy (Siriu: 475.0 W

What Dataset Percentiles Define Elin Energy (Sirius PV) ELNSM60M-HC-LV-475?

Percentile placement of Elin Energy (Sirius PV) ELNSM60M-HC-LV-475 across power density (220.9 W/m2), thermal retention, and nameplate STC wattage.

Elin Energy (Sirius PV) ELNSM60M-HC-LV-475 Engineering BenchmarksPercentile comparison of Elin Energy (Sirius PV) ELNSM60M-HC-LV-475 wattage, thermal retention, and efficiency. 0% (Low)50% Median100% (Top)STC Wattage475.0 WPTC/STC Retention94.4%Module Efficiency22.09%

What Do the Dataset Ranks Show for Elin Energy (Sirius PV) ELNSM60M-HC-LV-475?

Four critical engineering numbers homeowners and solar installers check first when reviewing Elin Energy (Sirius PV) ELNSM60M-HC-LV-475 specifications.

Rank #4,892 / 21,677

Top 22.9% STC Output

475.0 W STC (+90.0 W vs all-CEC median) vs 410.0 W Mono-c-Si median.

Eff #2,842

22.09% Aperture Efficiency

Power density 220.9 W/m2 (2.18 percentage points above 19.91% CEC median). PTC/STC ratio: 94.4% (rank #2,840).

NEC 690.7 Limit

13 Panels Max @ -10 C (600 V)

Cold Voc reaches 45.25 V at -10 C (588.2 V string) and 46.22 V at -20 C (12 max).

8 kW Reference Array

17 Panels = 8,075 W STC

Occupies 36.5 m2 (393 sq ft) producing 7,623 W PTC; NEC 690.8 OCPD floor is 22.25 A (25 A breaker).

NEC 690.7(A) Cold-Temperature Voc & 690.8 OCPD Formula

Voc_cold = 41.82 * (1 + (-0.234/100) * (-10 - 25)) = 45.25 V | OCPD = 1.56 * 14.26 = 22.25 A

Inputs from CEC Modules.csv for Elin Energy (Sirius PV) ELNSM60M-HC-LV-475: Voc=41.82 V, beta_Voc=-0.234%/C, Isc=14.26 A, STC=475.0 W, Area=2.15 m2.

Result: 13 panels max on 600 V (588.2 V); 17 panels for 8 kW (393 sq ft).

What Are the Published CEC Specifications for Elin Energy (Sirius PV) ELNSM60M-HC-LV-475?

Verified electrical STC and PTC ratings, open-circuit voltage, short-circuit current, and physical area published for Elin Energy (Sirius PV) ELNSM60M-HC-LV-475.

Official California Energy Commission (NREL SAM) test parameters for Elin Energy (Sirius PV) ELNSM60M-HC-LV-475.
ParameterMeasured / Listed ValueEngineering Significance
Nameplate Power (STC) 475.0 W Rated DC output under Standard Test Conditions (1000 W/m2, 25C cell)
Real-World Output (PTC) 448.4 W (94.4% STC) PVUSA Test Conditions rating used for utility interconnection
Open-Circuit Voltage (Voc) 41.82 V Primary cold-weather string sizing limit under NEC 690.7
Short-Circuit Current (Isc) 14.26 A Determines 156% (1.25x1.25) OCPD fuse/breaker sizing under NEC 690.8
Max Power Voltage / Current 34.78 V / 13.63 A Inverter MPPT operating window alignment
Voc Temp Coefficient (beta_Voc) -0.234 %/C Negative slope governing voltage rise below 25C
Module Efficiency & Area 22.09% (2.15 m2) Array roof footprint density
Cell Count & Technology 60 cells (Mono-c-Si) Monofacial backsheet

How Many Elin Energy (Sirius PV) ELNSM60M-HC-LV-475 Panels Build a 6 kW, 8 kW, or 10 kW Array?

Compare 6 kW, 8 kW, and 10 kW array footprints and Year-1 utility savings using Elin Energy (Sirius PV) ELNSM60M-HC-LV-475 (475.0 W).

Estimated panel count, roof square footage, and Year-1 bill offset across low, average, and high US utility tariffs (0% 25D).
Target ArrayPanelsActual DCRoof AreaUS Avg ($/yr)CA High ($/yr)
6 kW Class 13 6.17 kW 301 sq ft $1,544 $2,611
8 kW Class 17 8.07 kW 393 sq ft $2,020 $3,415
10 kW Class 22 10.45 kW 509 sq ft $2,616 $4,423

How Many Elin Energy (Sirius PV) ELNSM60M-HC-LV-475 Modules Fit in a Cold-Weather String?

Maximum series module counts for Elin Energy (Sirius PV) ELNSM60M-HC-LV-475 from 25 C down to -20 C (-4 F) under NEC 690.7.

Computed from Voc=41.82V and beta_Voc=-0.234%/C across design ambient temperatures.
Ambient Min TempCold Voc / PanelMax Panels (600 V)600 V String VocMax Panels (1000 V)
-20 C (-4 F) 46.22 V 12 panels 554.6 V 21 panels
-10 C (14 F) 45.25 V 13 panels 588.2 V 22 panels
0 C (32 F) 44.27 V 13 panels 575.5 V 22 panels
25 C (77 F STC) 41.82 V 14 panels 585.5 V 23 panels

Which Cross-Brand Solar Modules Compare Closest to Elin Energy (Sirius PV) ELNSM60M-HC-LV-475?

Alternative CEC solar modules from competing brands near Elin Energy (Sirius PV) ELNSM60M-HC-LV-475 (475.0 W), including CSI Solar Co Ltd CS61-60TM-470H.

Nearest CEC-listed competing brands by STC power and open-circuit voltage.
Alternative ModuleSTC (W)Delta vs ThisVoc (V)Eff (%)PTC/STC
CSI Solar Co Ltd CS61-60TM-470H
CSI Solar Co Ltd
470.0 W -5.0 W 42.0 V 21.46% 94.6%
Aptos Solar Technology LLC DNA-120-BFN10-470W-DG
Aptos Solar Technology LLC
470.0 W -5.0 W 42.38 V 21.76% 94.9%
Aptos Solar Technology LLC DNA-120-BFN10-480W-DG
Aptos Solar Technology LLC
480.0 W +5.0 W 42.61 V 22.22% 94.9%
Auxin Solar AXN10M470W
Auxin Solar
470.0 W -5.0 W 43.78 V 21.86% 92.0%
What to Check & Best-Fit Scenarios

What Are the Design Limits and Best-Fit Uses for Elin Energy (Sirius PV) ELNSM60M-HC-LV-475?

Evaluate Elin Energy (Sirius PV) ELNSM60M-HC-LV-475 (475.0 W STC, 41.82 V Voc) against your roof geometry, winter climate, and inverter voltage ceiling before finalizing bids.

  • Winter overvoltage boundary: at -20 C (-4 F), Elin Energy (Sirius PV) ELNSM60M-HC-LV-475 reaches 46.22 V per panel—exceeding 12 panels in series voids 600 V inverter warranties.
  • Footprint constraint: 17 panels for an 8 kW build require 393 sq ft of unshaded roof plane — well-proportioned for residential pitched roofs needing 17 panels (393 sq ft) for an 8 kW array.
  • 2026 tax credit baseline: cash residential installs of Elin Energy (Sirius PV) ELNSM60M-HC-LV-475 carry 0% federal 25D credit after 2025-12-31, making 18.54 c/kWh+ utility avoidance key.

Elin Energy (Sirius PV) ELNSM60M-HC-LV-475 8 kW Residential Fit

Needs 17 modules (393 sq ft) with a 25 A string OCPD, offsetting ~$2,020/yr at US average tariffs.

Cold-Climate String Design (-10 C / -20 C)

Cap 600 V series strings at 13 panels (-10 C) or 12 panels (-20 C), or compare CSI Solar Co Ltd CS61-60TM-470H.

Bifacial / High-Heat Roof Check

Monofacial backsheet sealing targets flush dark shingle rooftop mounts. Real-world output tracks 448.4 W PTC.

Which Homeowner Electrical & Solar Questions Come Up Most Often?

Technical answers for Elin Energy (Sirius PV) ELNSM60M-HC-LV-475 by Elin Energy (Sirius PV) grounded in CEC test data and NEC 690.7/690.8 limits.

What fuse or breaker size does NEC 690.8 require for Elin Energy (Sirius PV) ELNSM60M-HC-LV-475?

Multiplying Elin Energy (Sirius PV) ELNSM60M-HC-LV-475's 14.26 A short-circuit current by 1.56 equals 22.25 A minimum ampacity, requiring at least a 25 A overcurrent fuse or breaker.

Can Elin Energy (Sirius PV) ELNSM60M-HC-LV-475 pair with microinverters instead of a 600 V string inverter?

Yes—if the microinverter DC input ceiling exceeds 45.25 V cold Voc at 14 F and handles 14.26 A Isc; string inverters cap Elin Energy (Sirius PV) ELNSM60M-HC-LV-475 at 13 panels on 600 V.

Is Elin Energy (Sirius PV) ELNSM60M-HC-LV-475 eligible for the 30% federal 25D solar credit in 2026?

No. Federal Section 25D expired December 31, 2025 under Public Law 119-21, so 2026 cash installs of Elin Energy (Sirius PV) ELNSM60M-HC-LV-475 rely on utility bill offset (~$2,020/yr at 8 kW) rather than 25D.

Sources

  1. CEC Solar Equipment List — PV Modules (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
  2. NFPA 70 National Electrical Code (Section Numbers & Standard Engineering Tables Only) — National Fire Protection Association (NFPA), 2020 / 2023 / 2026 Editions (retrieved 2026-11-23)

Which Regional Electrical & Panel Upgrade Metros Compare Closest?

Check Wiring & Solar Numbers Before Getting Quotes

Verify panel capacity for solar, electrical box space, proper wire gauge for EV chargers, and 2026 home solar payback using local utility rates.

Verify State-Licensed Electricians & Safety Recalls

Look up active state electrician licenses (TX, WA, CO, OR, DE), check local power-outage history, and inspect federal product recall notices.