Sungrow: SG36CX-US {480V} outputs 36,046 W AC at 480 V, 3-phase (43.4 A continuous, 60 A OCPD), ranking #350 of 2,343 CEC inverters at 97.99% efficiency with a 550-850 V MPPT window and 850 V DC limit. All figures reconcile directly against federal energy archives, state electrical licensing boards, California Energy Commission datasheets, and National Electrical Code engineering constants.
- AC Output (Paco)
- 36,046 W
- AC Voltage
- 480 V, 3-phase
- Min PV Breaker
- 60 A (6 AWG Cu)
- CEC Efficiency
- 97.99%
How Does Sungrow: SG36CX-US {480V} Compare Against Peer CEC Listings?
NEC 705.12 breaker requirements, efficiency placement, and 480 V, 3-phase grid-support overview for Sungrow: SG36CX-US {480V}. Published percentiles compare local state, county, metro, and certified equipment metrics against nationwide residential electrical baselines.
Rated at 36,046 W AC (43.4 A continuous), Sungrow: SG36CX-US {480V} ranks #350 of 2,343 CEC units at 97.99% efficiency (-0.03 pts vs the 98.02% 480 V median). Minimum 75 C copper conductor sizing for its 60 A circuit is 6 AWG Cu per NEC Table 310.16. Cold-weather string Voc must remain under 850 V DC at record local winter lows.
Where Does Sungrow: SG36CX-US {480V} Fall Across Listed CEC Models?
Marks Sungrow: SG36CX-US {480V} (36,046 W AC) across the California Energy Commission inverter AC capacity distribution. Review related calculators, peer benchmarks, and source citations below to validate design assumptions for your electrical service.
What Dataset Percentiles Define Sungrow: SG36CX-US {480V}?
Benchmarks Sungrow: SG36CX-US {480V} continuous AC output, 97.99% CEC weighted efficiency, and 60 A OCPD breaker demand. Data intervals combine current 2025 federal utility and BLS wage releases with verified state electrical board rosters.
What Do the Dataset Ranks Show for Sungrow: SG36CX-US {480V}?
Four key NEC 705.12 and California Energy Commission metrics defining Sungrow: SG36CX-US {480V} by Sungrow. Always verify current state NEC adoption cycles, local utility interconnection tariffs, and panel busbar ratings before pulling project permits.
97.99% CEC Weighted Efficiency
-0.03 pts vs the 98.02% 480 V median; overall power rank #509 (36,046 W, top 21.7%; higher than 78.3% of peers).
60 A Required Backfeed OCPD
125% x 43.4 A = 54.2 A -> 60 A standard OCPD using 6 AWG Cu (75 C).
550 V - 850 V (Max 850 V DC)
Tracking span of 300.0 V; listed since 2024-09-23 (grid-tied PV inverter).
PASS (120% Commercial Busbar)
Evaluated for 480 V, 3-phase switchgear (200A Bus / 200A Main (480V) to 1,200A Bus / 1,200A Main (480V)) under NEC 705.12 / 705.11.
NEC 705.12 Backfeed OCPD & 120% Busbar Formula
I_cont = 36046.0W / 480 V 3-phase -> 43.4 A | Breaker >= 1.25 * 43.4 = 54.2 A -> 60 A
CEC Inverters.csv for Sungrow: SG36CX-US {480V}: Paco=36046.0 W, Vac=480 V, Vdcmax=850.0 V, Eff=97.99%.
Result: Min 60 A breaker & 6 AWG Cu (75 C); 1,200A Bus / 1,200A Main (480V): PASS (120% Commercial Busbar).
What Are the Published CEC Specifications for Sungrow: SG36CX-US {480V}?
Official laboratory CEC ratings, MPPT operating window, and DC voltage bounds recorded for Sungrow: SG36CX-US {480V}. Compare thermal ratings, overcurrent protection caps, and continuous load headroom carefully before expanding an existing home service panel.
| Parameter | Measured / Listed Value | Engineering Significance |
|---|---|---|
| Max Continuous AC Power (Paco) | 36,046 W | Determines required backfeed OCPD size via 125% continuous rule |
| Nominal AC Voltage (Vac) | 480 V, 3-phase | 240V split-phase residential vs. 208V/480V/MV commercial |
| Max DC Input Voltage (Vdcmax) | 850 V | Hard ceiling for cold-weather PV string Voc under NEC 690.7 |
| MPPT Operating Range | 550 V - 850 V | Optimal DC string Vmp window for full power harvest |
| Max Input DC Current (Idcmax) | 51.8112 A | Used to verify parallel string combiner limits |
| CEC Weighted Efficiency | 97.99% | Calculated AC/DC conversion ratio from CEC test protocol |
| CEC Listing Date & Hybrid | 2024-09-23 / Hybrid: No (Grid-Tied PV) | Utility interconnection approval metadata |
What Switchgear Limits Apply to Sungrow: SG36CX-US {480V} (480 V, 3-phase)?
Evaluates Sungrow: SG36CX-US {480V} (60 A OCPD) across standard 100 A to 225 A busbars or commercial switchboards.
| Switchboard / Interconnect | 120% Max Backfeed | Required PV OCPD | Compliance Verdict |
|---|---|---|---|
| 200A Bus / 200A Main (480V) | 40 A | 60 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| 400A Bus / 400A Main (480V) | 80 A | 60 A | PASS (120% Commercial Busbar) |
| 600A Bus / 600A Main (480V) | 120 A | 60 A | PASS (120% Commercial Busbar) |
| 800A Bus / 800A Main (480V) | 160 A | 60 A | PASS (120% Commercial Busbar) |
| 1,200A Bus / 1,200A Main (480V) | 240 A | 60 A | PASS (120% Commercial Busbar) |
Which CEC PV Module Strings Pair With Sungrow: SG36CX-US {480V}?
Sample PV string lengths aligned within 550-850 V MPPT and 850 V DC max at -10 C. Homeowners and permit reviewers can filter tables below to benchmark specific ratings, wiring ages, and code allowances side by side.
| CEC Module | STC (W) | -10 C Voc | Valid String Range | Max String DC |
|---|---|---|---|---|
| AXITEC AC-590TGB/144TS | 590.0 W | 56.24 V | 13 to 15 panels | 8.85 kW |
| Aptos Solar Technology LLC DNA-108-MFN10-440W | 440.0 W | 42.15 V | 17 to 20 panels | 8.8 kW |
| Boviet Solar Technology Co Ltd BVM7610M-425-H-HC-BF | 425.0 W | 44.75 V | 16 to 18 panels | 7.65 kW |
| CSI Solar Co Ltd CS6P-200P | 200.0 W | 40.6 V | 20 panels (fixed) | 4.0 kW |
Which Competing Grid-Support Inverters Compare to Sungrow: SG36CX-US {480V}?
Competing CEC grid-support inverters near 36,046 W AC and 480 V, 3-phase, led by Canadian Solar Inc: CSI-36KTL-CT {480V}.
| Alternative Inverter | AC Output | Delta | Vac | Max DC | CEC Eff |
|---|---|---|---|---|---|
| Canadian Solar Inc: CSI-36KTL-CT {480V} Canadian Solar Inc |
36,000 W | -46 W | 480.0 V | 800.0 V | 98.09% |
| Canadian Solar Inc: CSI-36KTL-GS-FL {480V} Canadian Solar Inc |
36,000 W | -46 W | 480.0 V | 780.0 V | 98.05% |
| Chint Power Systems America: CPS SCA36KTL-DO/US-480 {480V} Chint Power Systems America |
36,000 W | -46 W | 480.0 V | 850.0 V | 97.62% |
| Chint Power Systems America: CPS SCA36KTL-DO/US {480V} Chint Power Systems America |
36,000 W | -46 W | 480.0 V | 800.0 V | 98.09% |
What Are the Interconnection Limits and Best-Fit Uses for Sungrow: SG36CX-US {480V}?
Check Sungrow: SG36CX-US {480V} (36,046 W AC, 60 A OCPD) against your main panel busbar, winter string Voc, and IEEE 1547 outage rules.
- Anti-islanding shutdown: grid-tied inverters shut off within 2 seconds during blackouts under IEEE 1547 unless paired with a battery microgrid interconnect.
- Busbar 120% limit: Commercial 480 V, 3-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (480V) or NEC 705.11 supply-side tap.
- Cold Voc hard ceiling: never allow winter open-circuit PV string voltage to exceed 850 V DC on Sungrow: SG36CX-US {480V}.
Sungrow: SG36CX-US {480V} Panel & Wire Spec
Size 75 C copper conductors at 6 AWG Cu on a 60 A OCPD breaker (43.4 A continuous).
Alternative Inverter Comparison
Compare efficiency (97.99%) and MPPT window (550-850 V) directly against Canadian Solar Inc: CSI-36KTL-CT {480V} (36,000 W).
Which Homeowner Electrical & Solar Questions Come Up Most Often?
Answers for Sungrow: SG36CX-US {480V} by Sungrow covering breaker sizing, MPPT limits, and 480 V, 3-phase interconnection. All figures trace directly to published federal energy filings, state electrical boards, CEC datasheets, and NFPA 70 NEC tables.
What breaker and wire size does Sungrow: SG36CX-US {480V} require?
At 36,046 W continuous AC (480 V, 3-phase), continuous current is 43.4 A; 125% NEC 690.8/705.12 sizing requires a 60 A breaker and 6 AWG Cu (75 C) wire.
What commercial switchgear or feeder sizing does Sungrow: SG36CX-US {480V} require?
At 36,046 W AC and 480 V, 3-phase, continuous line current is 43.4 A, requiring a 60 A OCPD and 1,200A Bus / 1,200A Main (480V) or NEC 705.11 interconnection.
How does Sungrow: SG36CX-US {480V} compare to Canadian Solar Inc: CSI-36KTL-CT {480V}?
Sungrow: SG36CX-US {480V} delivers 36,046 W AC at 97.99% CEC efficiency with a 850 V DC ceiling, while Canadian Solar Inc: CSI-36KTL-CT {480V} outputs 36,000 W at 480 V, 3-phase.
Sources
- CEC Solar Equipment List — Grid-Support Inverters (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
- CEC Solar Equipment List — PV Modules (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
- NFPA 70 National Electrical Code (Section Numbers & Standard Engineering Tables Only) — National Fire Protection Association (NFPA), 2020 / 2023 / 2026 Editions (retrieved 2026-11-23)