Sungrow Power Supply Co Ltd: SG3150UD-MV-US {600V} outputs 1,053,000 W AC at 600 V, 3-phase (1013.3 A continuous, 1,300 A OCPD), ranking #1,002 of 2,343 CEC inverters at 97.01% efficiency with a 875-1,438 V MPPT window and 1,438 V DC limit. All figures reconcile directly against federal energy archives, state electrical licensing boards, California Energy Commission datasheets, and National Electrical Code engineering constants.
- AC Output (Paco)
- 1,053,000 W
- AC Voltage
- 600 V, 3-phase
- Min PV Breaker
- 1,300 A (parallel Cu feeders)
- CEC Efficiency
- 97.01%
How Does Sungrow Power Supply Co Ltd: SG3150UD-MV-US {600V} Compare Against Peer CEC Listings?
NEC 705.12 breaker requirements, efficiency placement, and 600 V, 3-phase grid-support overview for Sungrow Power Supply Co Ltd: SG3150UD-MV-US {600V}.
Ranking #160 of 2,343 CEC inverters (top 6.8%; higher than 93.2% of peers), Sungrow Power Supply Co Ltd: SG3150UD-MV-US {600V} is a hybrid battery-capable inverter delivering 1,053,000 W continuous AC at 600 V, 3-phase (1013.3 A continuous). Commercial 600 V, 3-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (600V) or NEC 705.11 supply-side tap. Weighted CEC efficiency reaches 97.01% (-1.27 pts vs the 98.28% 600 V median) against peers like Yaskawa Solectria Solar: XGI 1500-1MW-600 {600V} (1,000,000 W).
Where Does Sungrow Power Supply Co Ltd: SG3150UD-MV-US {600V} Fall Across Listed CEC Models?
Marks Sungrow Power Supply Co Ltd: SG3150UD-MV-US {600V} (1,053,000 W AC) across the California Energy Commission inverter AC capacity distribution.
What Dataset Percentiles Define Sungrow Power Supply Co Ltd: SG3150UD-MV-US {600V}?
Benchmarks Sungrow Power Supply Co Ltd: SG3150UD-MV-US {600V} continuous AC output, 97.01% CEC weighted efficiency, and 1,300 A OCPD breaker demand.
What Do the Dataset Ranks Show for Sungrow Power Supply Co Ltd: SG3150UD-MV-US {600V}?
Four key NEC 705.12 and California Energy Commission metrics defining Sungrow Power Supply Co Ltd: SG3150UD-MV-US {600V} by Sungrow Power Supply Co Ltd.
97.01% CEC Weighted Efficiency
-1.27 pts vs the 98.28% 600 V median; overall power rank #160 (1,053,000 W, top 6.8%; higher than 93.2% of peers).
1,300 A Required Backfeed OCPD
125% x 1013.3 A = 1266.6 A -> 1,300 A standard OCPD using parallel Cu feeders (75 C).
875 V - 1,438 V (Max 1,438 V DC)
Tracking span of 563.0 V; listed since 2024-04-11 (hybrid battery-capable inverter).
Supply-Side Tap (705.11) / Dedicated Switchboard
Evaluated for 600 V, 3-phase switchgear (200A Bus / 200A Main (600V) to 1,200A Bus / 1,200A Main (600V)) under NEC 705.12 / 705.11.
NEC 705.12 Backfeed OCPD & 120% Busbar Formula
I_cont = 1053000.0W / 600 V 3-phase -> 1013.3 A | Breaker >= 1.25 * 1013.3 = 1266.6 A -> 1,300 A
CEC Inverters.csv for Sungrow Power Supply Co Ltd: SG3150UD-MV-US {600V}: Paco=1053000.0 W, Vac=600 V, Vdcmax=1438.0 V, Eff=97.01%.
Result: Min 1,300 A breaker & parallel Cu feeders (75 C); 1,200A Bus / 1,200A Main (600V): Supply-Side Tap (705.11) / Dedicated Switchboard.
What Are the Published CEC Specifications for Sungrow Power Supply Co Ltd: SG3150UD-MV-US {600V}?
Official laboratory CEC ratings, MPPT operating window, and DC voltage bounds recorded for Sungrow Power Supply Co Ltd: SG3150UD-MV-US {600V}.
| Parameter | Measured / Listed Value | Engineering Significance |
|---|---|---|
| Max Continuous AC Power (Paco) | 1,053,000 W | Determines required backfeed OCPD size via 125% continuous rule |
| Nominal AC Voltage (Vac) | 600 V, 3-phase | 240V split-phase residential vs. 208V/480V/MV commercial |
| Max DC Input Voltage (Vdcmax) | 1,438 V | Hard ceiling for cold-weather PV string Voc under NEC 690.7 |
| MPPT Operating Range | 875 V - 1,438 V | Optimal DC string Vmp window for full power harvest |
| Max Input DC Current (Idcmax) | 986.828 A | Used to verify parallel string combiner limits |
| CEC Weighted Efficiency | 97.01% | Calculated AC/DC conversion ratio from CEC test protocol |
| CEC Listing Date & Hybrid | 2024-04-11 / Hybrid: Yes (Battery Capable) | Utility interconnection approval metadata |
What Switchgear Limits Apply to Sungrow Power Supply Co Ltd: SG3150UD-MV-US {600V} (600 V, 3-phase)?
Evaluates Sungrow Power Supply Co Ltd: SG3150UD-MV-US {600V} (1,300 A OCPD) across standard 100 A to 225 A busbars or commercial switchboards.
| Switchboard / Interconnect | 120% Max Backfeed | Required PV OCPD | Compliance Verdict |
|---|---|---|---|
| 200A Bus / 200A Main (600V) | 40 A | 1,300 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| 400A Bus / 400A Main (600V) | 80 A | 1,300 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| 600A Bus / 600A Main (600V) | 120 A | 1,300 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| 800A Bus / 800A Main (600V) | 160 A | 1,300 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| 1,200A Bus / 1,200A Main (600V) | 240 A | 1,300 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
Which CEC PV Module Strings Pair With Sungrow Power Supply Co Ltd: SG3150UD-MV-US {600V}?
Sample PV string lengths aligned within 875-1,438 V MPPT and 1,438 V DC max at -10 C. Every reported metric links directly to federal public records or state regulatory filings with zero paid contractor placements.
| CEC Module | STC (W) | -10 C Voc | Valid String Range | Max String DC |
|---|---|---|---|---|
| AXITEC AC-590TGB/144TS | 590.0 W | 56.24 V | 21 to 25 panels | 14.75 kW |
| Aptos Solar Technology LLC DNA-108-MFN10-440W | 440.0 W | 42.15 V | 27 to 34 panels | 14.96 kW |
| Boviet Solar Technology Co Ltd BVM7610M-425-H-HC-BF | 425.0 W | 44.75 V | 26 to 32 panels | 13.6 kW |
| CSI Solar Co Ltd CS6P-200P | 200.0 W | 40.6 V | 31 to 35 panels | 7.0 kW |
Which Competing Grid-Support Inverters Compare to Sungrow Power Supply Co Ltd: SG3150UD-MV-US {600V}?
Competing CEC grid-support inverters near 1,053,000 W AC and 600 V, 3-phase, led by Yaskawa Solectria Solar: XGI 1500-1MW-600 {600V}.
| Alternative Inverter | AC Output | Delta | Vac | Max DC | CEC Eff |
|---|---|---|---|---|---|
| Yaskawa Solectria Solar: XGI 1500-1MW-600 {600V} Yaskawa Solectria Solar |
1,000,000 W | -53000 W | 600.0 V | 1250.0 V | 98.47% |
| DYNAPOWER COMPANY LLC: CPS-1250 Gen5 {600V} DYNAPOWER COMPANY LLC |
999,576 W | -53424 W | 600.0 V | 1500.0 V | 98.44% |
| Yaskawa Solectria Solar: XGI 1500-099MW-600 {600V} Yaskawa Solectria Solar |
999,000 W | -54000 W | 600.0 V | 1250.0 V | 98.47% |
| Power Electronics: FS1100CU15O3 {600V} Power Electronics |
1,176,440 W | +123440 W | 600.0 V | 1200.0 V | 97.93% |
What Are the Interconnection Limits and Best-Fit Uses for Sungrow Power Supply Co Ltd: SG3150UD-MV-US {600V}?
Check Sungrow Power Supply Co Ltd: SG3150UD-MV-US {600V} (1,053,000 W AC, 1,300 A OCPD) against your main panel busbar, winter string Voc, and IEEE 1547 outage rules.
- Anti-islanding shutdown: grid-tied inverters shut off within 2 seconds during blackouts under IEEE 1547 unless paired with a battery microgrid interconnect.
- Busbar 120% limit: Commercial 600 V, 3-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (600V) or NEC 705.11 supply-side tap.
- Cold Voc hard ceiling: never allow winter open-circuit PV string voltage to exceed 1,438 V DC on Sungrow Power Supply Co Ltd: SG3150UD-MV-US {600V}.
Sungrow Power Supply Co Ltd: SG3150UD-MV-US {600V} Panel & Wire Spec
Size 75 C copper conductors at parallel Cu feeders on a 1,300 A OCPD breaker (1013.3 A continuous).
Alternative Inverter Comparison
Compare efficiency (97.01%) and MPPT window (875-1,438 V) directly against Yaskawa Solectria Solar: XGI 1500-1MW-600 {600V} (1,000,000 W).
Which Homeowner Electrical & Solar Questions Come Up Most Often?
Answers for Sungrow Power Supply Co Ltd: SG3150UD-MV-US {600V} by Sungrow Power Supply Co Ltd covering breaker sizing, MPPT limits, and 600 V, 3-phase interconnection.
What breaker and wire size does Sungrow Power Supply Co Ltd: SG3150UD-MV-US {600V} require?
At 1,053,000 W continuous AC (600 V, 3-phase), continuous current is 1013.3 A; 125% NEC 690.8/705.12 sizing requires a 1,300 A breaker and parallel Cu feeders (75 C) wire.
What commercial switchgear or feeder sizing does Sungrow Power Supply Co Ltd: SG3150UD-MV-US {600V} require?
At 1,053,000 W AC and 600 V, 3-phase, continuous line current is 1013.3 A, requiring a 1,300 A OCPD and 1,200A Bus / 1,200A Main (600V) or NEC 705.11 interconnection.
How does Sungrow Power Supply Co Ltd: SG3150UD-MV-US {600V} compare to Yaskawa Solectria Solar: XGI 1500-1MW-600 {600V}?
Sungrow Power Supply Co Ltd: SG3150UD-MV-US {600V} delivers 1,053,000 W AC at 97.01% CEC efficiency with a 1,438 V DC ceiling, while Yaskawa Solectria Solar: XGI 1500-1MW-600 {600V} outputs 1,000,000 W at 600 V, 3-phase.
Sources
- CEC Solar Equipment List — Grid-Support Inverters (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
- CEC Solar Equipment List — PV Modules (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
- NFPA 70 National Electrical Code (Section Numbers & Standard Engineering Tables Only) — National Fire Protection Association (NFPA), 2020 / 2023 / 2026 Editions (retrieved 2026-11-23)