Sungrow Power Supply Co Ltd: SC125CX-US {480V} outputs 125,385 W AC at 480 V, 3-phase (150.8 A continuous, 200 A OCPD), ranking #130 of 2,343 CEC inverters at 98.38% efficiency with a 767-935 V MPPT window and 935 V DC limit. All figures reconcile directly against federal energy archives, state electrical licensing boards, California Energy Commission datasheets, and National Electrical Code engineering constants.
- AC Output (Paco)
- 125,385 W
- AC Voltage
- 480 V, 3-phase
- Min PV Breaker
- 200 A (3/0 AWG Cu)
- CEC Efficiency
- 98.38%
How Does Sungrow Power Supply Co Ltd: SC125CX-US {480V} Compare Against Peer CEC Listings?
CEC efficiency rank (#130), 767-935 V MPPT tracking, and panel fit for Sungrow Power Supply Co Ltd: SC125CX-US {480V}.
Operating at 480 V, 3-phase, Sungrow Power Supply Co Ltd: SC125CX-US {480V} converts DC array energy at 98.38% CEC weighted efficiency (top 5.8%; higher than 94.2% of peers) with a 935 V max DC input and 149.947 A max input current for NEC 690.7 string safety. Compare this 125,385 W grid-tied PV inverter directly with Chint Power Systems America: CPS ECB125KTL-M/US-480 {480V} (125,000 W). Commercial 480 V, 3-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (480V) or NEC 705.11 supply-side tap.
Where Does Sungrow Power Supply Co Ltd: SC125CX-US {480V} Fall Across Listed CEC Models?
CEC inverter wattage histogram highlighting Sungrow Power Supply Co Ltd: SC125CX-US {480V} at 125,385 W continuous AC output.
What Dataset Percentiles Define Sungrow Power Supply Co Ltd: SC125CX-US {480V}?
Dataset percentiles comparing Sungrow Power Supply Co Ltd: SC125CX-US {480V} against 2,343 certified grid-support inverters nationwide. Compare thermal ratings, overcurrent protection caps, and continuous load headroom carefully before expanding an existing home service panel.
What Do the Dataset Ranks Show for Sungrow Power Supply Co Ltd: SC125CX-US {480V}?
Engineering highlights for Sungrow Power Supply Co Ltd: SC125CX-US {480V} covering efficiency, 3/0 AWG Cu feeder, and panel compatibility.
98.38% CEC Weighted Efficiency
+0.36 pts vs the 98.02% 480 V median; overall power rank #294 (125,385 W, top 12.5%; higher than 87.5% of peers).
200 A Required Backfeed OCPD
125% x 150.8 A = 188.5 A -> 200 A standard OCPD using 3/0 AWG Cu (75 C).
767 V - 935 V (Max 935 V DC)
Tracking span of 168.0 V; active in CEC directory (grid-tied PV inverter).
Supply-Side Tap (705.11) / Dedicated Switchboard
Evaluated for 480 V, 3-phase switchgear (200A Bus / 200A Main (480V) to 1,200A Bus / 1,200A Main (480V)) under NEC 705.12 / 705.11.
NEC 705.12 Backfeed OCPD & 120% Busbar Formula
I_cont = 125385.0W / 480 V 3-phase -> 150.8 A | Breaker >= 1.25 * 150.8 = 188.5 A -> 200 A
CEC Inverters.csv for Sungrow Power Supply Co Ltd: SC125CX-US {480V}: Paco=125385.0 W, Vac=480 V, Vdcmax=935.0 V, Eff=98.38%.
Result: Min 200 A breaker & 3/0 AWG Cu (75 C); 1,200A Bus / 1,200A Main (480V): PASS (120% Commercial Busbar).
What Are the Published CEC Specifications for Sungrow Power Supply Co Ltd: SC125CX-US {480V}?
California Energy Commission Solar Equipment List parameters for Sungrow Power Supply Co Ltd: SC125CX-US {480V} (grid-tied PV inverter) interconnection.
| Parameter | Measured / Listed Value | Engineering Significance |
|---|---|---|
| Max Continuous AC Power (Paco) | 125,385 W | Determines required backfeed OCPD size via 125% continuous rule |
| Nominal AC Voltage (Vac) | 480 V, 3-phase | 240V split-phase residential vs. 208V/480V/MV commercial |
| Max DC Input Voltage (Vdcmax) | 935 V | Hard ceiling for cold-weather PV string Voc under NEC 690.7 |
| MPPT Operating Range | 767 V - 935 V | Optimal DC string Vmp window for full power harvest |
| Max Input DC Current (Idcmax) | 149.947 A | Used to verify parallel string combiner limits |
| CEC Weighted Efficiency | 98.38% | Calculated AC/DC conversion ratio from CEC test protocol |
| Inverter Topology | Hybrid: No (Grid-Tied PV) | CEC Solar Equipment List grid-support certification |
What Switchgear Limits Apply to Sungrow Power Supply Co Ltd: SC125CX-US {480V} (480 V, 3-phase)?
Panelboard and switchgear backfeed allowances for Sungrow Power Supply Co Ltd: SC125CX-US {480V} (200 A OCPD). Inspect manufacturer nameplate documentation, UL listing boundaries, and utility rate schedules closely before ordering electrical hardware.
| Switchboard / Interconnect | 120% Max Backfeed | Required PV OCPD | Compliance Verdict |
|---|---|---|---|
| 200A Bus / 200A Main (480V) | 40 A | 200 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| 400A Bus / 400A Main (480V) | 80 A | 200 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| 600A Bus / 600A Main (480V) | 120 A | 200 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| 800A Bus / 800A Main (480V) | 160 A | 200 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| 1,200A Bus / 1,200A Main (480V) | 240 A | 200 A | PASS (120% Commercial Busbar) |
Which Competing Grid-Support Inverters Compare to Sungrow Power Supply Co Ltd: SC125CX-US {480V}?
Four alternative CEC inverters matched to Sungrow Power Supply Co Ltd: SC125CX-US {480V} (125,385 W AC), led by Chint Power Systems America: CPS ECB125KTL-M/US-480 {480V}.
| Alternative Inverter | AC Output | Delta | Vac | Max DC | CEC Eff |
|---|---|---|---|---|---|
| Chint Power Systems America: CPS ECB125KTL-M/US-480 {480V} Chint Power Systems America |
125,000 W | -385 W | 480.0 V | 1100.0 V | 97.2% |
| Delta Electronics: DES10JB125K01 {480V} Delta Electronics |
125,000 W | -385 W | 480.0 V | 1000.0 V | 97.01% |
| Delta Electronics: PCS125 {480V} Delta Electronics |
125,000 W | -385 W | 480.0 V | 1000.0 V | 97.01% |
| Ginlong Technologies Co Ltd: S5-GC125K-US {480V} Ginlong Technologies Co Ltd |
124,991 W | -394 W | 480.0 V | 850.0 V | 97.88% |
What Are the Interconnection Limits and Best-Fit Uses for Sungrow Power Supply Co Ltd: SC125CX-US {480V}?
Check Sungrow Power Supply Co Ltd: SC125CX-US {480V} (125,385 W AC, 200 A OCPD) against your main panel busbar, winter string Voc, and IEEE 1547 outage rules.
- Anti-islanding shutdown: grid-tied inverters shut off within 2 seconds during blackouts under IEEE 1547 unless paired with a battery microgrid interconnect.
- Busbar 120% limit: Commercial 480 V, 3-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (480V) or NEC 705.11 supply-side tap.
- Cold Voc hard ceiling: never allow winter open-circuit PV string voltage to exceed 935 V DC on Sungrow Power Supply Co Ltd: SC125CX-US {480V}.
Sungrow Power Supply Co Ltd: SC125CX-US {480V} Panel & Wire Spec
Size 75 C copper conductors at 3/0 AWG Cu on a 200 A OCPD breaker (150.8 A continuous).
Alternative Inverter Comparison
Compare efficiency (98.38%) and MPPT window (767-935 V) directly against Chint Power Systems America: CPS ECB125KTL-M/US-480 {480V} (125,000 W).
Which Homeowner Electrical & Solar Questions Come Up Most Often?
Answers for Sungrow Power Supply Co Ltd: SC125CX-US {480V} by Sungrow Power Supply Co Ltd covering breaker sizing, MPPT limits, and 480 V, 3-phase interconnection.
What breaker and wire size does Sungrow Power Supply Co Ltd: SC125CX-US {480V} require?
At 125,385 W continuous AC (480 V, 3-phase), continuous current is 150.8 A; 125% NEC 690.8/705.12 sizing requires a 200 A breaker and 3/0 AWG Cu (75 C) wire.
What commercial switchgear or feeder sizing does Sungrow Power Supply Co Ltd: SC125CX-US {480V} require?
At 125,385 W AC and 480 V, 3-phase, continuous line current is 150.8 A, requiring a 200 A OCPD and 1,200A Bus / 1,200A Main (480V) or NEC 705.11 interconnection.
How does Sungrow Power Supply Co Ltd: SC125CX-US {480V} compare to Chint Power Systems America: CPS ECB125KTL-M/US-480 {480V}?
Sungrow Power Supply Co Ltd: SC125CX-US {480V} delivers 125,385 W AC at 98.38% CEC efficiency with a 935 V DC ceiling, while Chint Power Systems America: CPS ECB125KTL-M/US-480 {480V} outputs 125,000 W at 480 V, 3-phase.
Sources
- CEC Solar Equipment List — Grid-Support Inverters (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
- CEC Solar Equipment List — PV Modules (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
- NFPA 70 National Electrical Code (Section Numbers & Standard Engineering Tables Only) — National Fire Protection Association (NFPA), 2020 / 2023 / 2026 Editions (retrieved 2026-11-23)